Startup, Adjustment and Shutdown

Note

The Specifications section and Table 1 

provide the maximum pressure 

capabilities for each regulator 

construction. Use pressure gauges 

to monitor inlet pressure and control 

pressure during startup.  

Startup

1.  Slowly open the outlet block valve, if used, to 

vapor recovery system and leave it fully open. 

2. 

Slowly open the shutoff valve (for Type T208M, 

open the control line shutoff valve first followed by 

the inlet shutoff valve) between the tank and vapor 

recovery regulator.

3.  Use gauges to monitor pressure.

Adjustment

 

 WARNING

To avoid personal injury, property 

damage, or equipment damage caused 

by bursting of pressure containing 

parts or explosion of accumulated 

gas, never adjust the control spring to 

maintain a control pressure higher than 

the upper limit of the control pressure 

range for that particular spring. If the 

desired control pressure is not within 

the range of the spring, install a spring 

of the proper range according to the 

Diaphragm and Spring Case Area 

section of the maintenance procedure.

Adjust the regulator control pressure setting to meet 

the requirements of the specific application. The range 

of allowable pressure setting is stamped on the 

nameplate. If a pressure setting beyond the stamped 

range is required, install a spring with the desired 

range by following the procedures for changing 

the spring in the Maintenance section. To adjust 

the pressure setting, perform the following steps 

(key numbers are referenced in Figures 4, 5 and 6).

For internal flat circular adjusting screw

1.  Remove the closing cap (key 22).
2. 

Use a 1 in. / 25 mm hex rod or flat screwdriver 

 

to turn the adjusting screw (key 35) either clockwise 

to increase control pressure or counterclockwise to 

decrease control pressure. The regulator will go into 

immediate operation. To ensure correct operation, 

always use a pressure gauge to monitor the vapor 

recovery pressure when making adjustments.

3.  After making the adjustment, replace the closing 

cap gasket (key 25) and install the closing cap 

(key 22).

4.  To remotely vent the regulator, remove the vent 

assembly (key 26) and install obstruction-free 

tubing or piping into the 1/4 NPT vent tapping. 

Provide protection on a remote vent by installing 

a screened vent cap into the remote end of the 

vent pipe. If continuous operation of the system is 

required during inspection or maintenance, install 

a three-way bypass valve around the regulator.

5.  The Type T208M requires a control line. Be sure to 

install the control line before putting the regulator 

into operation. Make the control line as short 

and straight as possible and do not install it in a 

location where flow may be turbulent. Significant 

restrictions in the control line can prevent proper 

pressure registration. When using a hand valve, it 

should be a full flow valve, such as a full port ball 

valve. Install the control line sloping downward 

toward the tank to prevent condensation buildup 

and avoid low points (or traps) that could catch 

liquid. The sensing line must enter the tank 

above the liquid level at a point that senses the 

vapor space pressure and is free from turbulence 

associated with tank nozzles or vents. The control 

line pipe should be at least 1/2 in. / 13 mm in 

diameter and increase 1 pipe size for every  

10 ft. / 3.05 m of control line, with setpoint less 

than 5 in. w.c / 12 mbar.

6.  Vapor recovery regulators are used to maintain 

a constant inlet (blanket) pressure with the outlet 

flowing to a system whose pressure is lower than 

that at the inlet. The recovery regulators are not 

intended to be used as an ASME certified relief 

device for overpressure protection on a tank. They 

are to be used as part of a gas blanketing system 

to control outflow of blanketing gas under normal 

conditions and collect tank vapors for the vapor 

disposal reclamation system. Provide alternate 

methods of emergency overpressure protection.

5

T208 Series

Содержание FISHER T208 Series

Страница 1: ...Emerson instructions If the regulator discharges process fluid or a leak develops in the system service to the unit may be required Failure to correct trouble could result in a hazardous condition Call a qualified service person to service the unit Installation operation and maintenance procedures performed by unqualified person may result in improper adjustment and unsafe operation Either conditi...

Страница 2: ...ing Case Vent Connection 1 4 NPT Diaphragm Case Control Line Connection Type T208M 1 2 NPT Approximate Weight 17 7 lbs 8 kgs 1 The pressure temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded 2 See Table 4 for operating temperature ranges for available trim combinations 3 Special low temperature constructions for process temperatures ...

Страница 3: ...s STEM ORIFICE LEVER PIPE PLUG DIAPHRAGM TYPE Y602 1 VENT CONTROLSPRING BACK DISK SPRING DISK STEM SEAL O RING LEVER CONTROLLINECONNECTION DIAPHRAGM TYPE Y602 1 VENT CONTROL SPRING BACK DISK SPRING DISK ORIFICE THROAT SEAL INLET PRESSURE OUTLET PRESSURE ATMOSPHERICPRESSURE INLET PRESSURE OUTLET PRESSURE ATMOSPHERICPRESSURE 3 T208 Series ...

Страница 4: ...e personal injury death or property damage due to fire or explosion Vent a regulator in hazardous gas service to a remote safe location away from air intakes or any hazardous area The vent line or stack opening must be protected against condensation or clogging 3 To keep the vent assembly key 26 from being plugged or the spring case key 3 from collecting moisture corrosive chemicals or other forei...

Страница 5: ... use a pressure gauge to monitor the vapor recovery pressure when making adjustments 3 After making the adjustment replace the closing cap gasket key 25 and install the closing cap key 22 4 To remotely vent the regulator remove the vent assembly key 26 and install obstruction free tubing or piping into the 1 4 NPT vent tapping Provide protection on a remote vent by installing a screened vent cap i...

Страница 6: ...ect and replace the disk assembly key 13 remove the back body cap key 43 2 Remove the disk assembly key 13 from the disk spacer key 44 and replace if necessary 3 To inspect the orifice key 5 on Types T208 and T208M or throat seal O ring key 31 and machine screw key 34 on the Type T208M remove the cap screws key 2 and separate the diaphragm casing key 4 from the body key 1 4 Remove and inspect the ...

Страница 7: ...hragm case assembly before performing these steps Key numbers are referenced in Figures 4 5 and 6 1 For internal flat circular adjusting screw remove the closing cap key 22 closing cap gasket key 25 and adjusting screw key 35 For external square head adjusting screw remove the adjusting screw key 35 locknut key 20 closing cap key 22 closing cap gasket key 25 and upper spring seat key 19 2 Remove t...

Страница 8: ...ap screws key 24 and hex nuts key 23 to 98 to 126 in lbs 11 1 to 14 2 N m of torque Adjust the control pressure to the desired pressure setting refer to the Adjustment section 12 For Type T208M connect the control line Refer to the Startup section before putting the regulator back in operation To Convert Constructions From Type T208 to Type T208M A control line is needed New parts required keys 30...

Страница 9: ...Closing Cap Plastic standard T11069X0012 Steel 1E422724092 Stainless steel 1E422735072 Carbon steel 1 ERSA01809A0 23 Hex Nut 8 required For Gray cast iron or WCC Carbon steel casing 1A345724122 For LCC Carbon steel or CF8M CF3M Stainless steel casing 1A3457K0012 24 Cap Screw 8 required For Gray cast iron or WCC Carbon steel casing 1A579724052 For LCC Carbon steel or CF8M CF3M Stainless steel 1A579...

Страница 10: ...END CONNECTION STYLE 1 PART NUMBER 3 4 In DN 20 Body 1 In DN 25 Body Gray cast iron NPT ERSA03695A0 ERSA03697A0 WCC Carbon steel NPT ERSA00231A1 ERSA00764A1 CL150 RF ERSA01470A0 ERSA01470A1 CL300 RF ERSA01470A2 ERSA01470A3 PN 16 25 40 RF ERSA01470A4 ERSA01470A5 CF8M CF3M Stainless steel 3 NPT 2 ERSA00231A0 ERSA00764A0 CL150 RF ERSA01470A6 ERSA01470A7 CL300 RF ERSA01470A8 ERSA01470A9 PN 16 25 40 RF...

Страница 11: ... 60 TO 72 IN LBS 6 8 TO 8 1 N m Table 4 Type T208 Trim Option Code TRIM OPTION CODE DIAPHRAGM MATERIAL DISK AND O RING MATERIAL OPERATING TEMPERATURE RANGES Standard Nitrile NBR Nitrile NBR 40 to 180 F 40 to 82 C VV Fluorocarbon FKM Fluorocarbon FKM 40 to 300 F 4 to 149 C TN Fluorinated Ethylene Propylene FEP Nitrile NBR 20 to 180 F 29 to 82 C TV Fluorinated Ethylene Propylene FEP Fluorocarbon FKM...

Страница 12: ...sponsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Process Management Regulator Technologies Inc product remains solely with the purchaser TORQUE 98 TO 126 IN LBS 11 1 TO 14 2 N m TORQUE 340 TO 470 IN LBS 38 5 TO 53 1 N m TORQUE 90 TO 126 IN LBS 10 2 TO 14 2 N m EXTERNAL SQUARE HEAD ADJUSTING SCREW ASSEMBLY OPTION...

Отзывы: