Instruction Manual Supplement
D103266X012
DVC5000 Digital Valve Controller
May 2018
14
Command 35: Write Primary Variable Range Values
In the DVC5000, the Primary Variable is defined to be the measured Valve Travel.
This command is used to write the ranging values reported in Command 15. It sets the engineering units to be
reported with 0% and 100% of calibrated travel.
This command will only be accepted when the DVC5000’s Instrument Mode is in the “Out of Service” condition and
will be rejected if Write Protection is in effect.
Byte
Format
Description
Allowable choices
Request
Data Bytes
0
UINT8
Upper and Lower Range Values Unit Code
57(%)
1 4
Float
Primary Variable Upper Range Value
5 8
Float
Primary Variable Lower Range Value
Response
Data Bytes
0
UINT8
Upper and Lower Range Values Unit Code
57(%)
1 4
Float
Primary Variable Upper Range Value
5 8
Float
Primary Variable Lower Range Value
Code
Class
Description
Command
Specific
Response
Codes
2
Invalid selection Units code did not match configured units
7
In Write Protect Mode
16
Access Restricted Instrument Mode is not in “Out of Service” condition
32
Busy
Command 38: Reset Configuration Change Flag
Resets the configuration changed flag in the DVC5000.
This command is only accepted from the primary HART Master. Any write to the DVC5000 other than digital setpoint
values and write protect status will cause the configuration change flag to be set.
Byte
Format
Description
Request
Data Bytes
none
Response
Data Bytes
none
Code
Class
Description
Command
Specific
Response
Codes
16
Access Restricted (If command is issued from a Secondary master)