Instruction Manual Supplement
D103266X012
DVC5000 Digital Valve Controller
May 2018
11
Command 3: Read Dynamic Variables and Loop Current
This command is used to read the value of Loop Current and the four Dynamic Variables.
The default Dynamic Variable assignment and the Variable Units Codes are shown on page 6.
Byte
Format
Description
Request
Data Bytes
none
Response
Data Bytes
03
Float
Loop Current (implied units of “mA”)
4
Byte, hex
Primary Variable (PV) units code
58
Float
Primary Variable (PV) value
9
Byte, hex
Secondary Variable (SV) units code
1013
Float
Secondary Variable (SV) value
14
Byte, hex
Tertiary Variable (TV) units code
1518
Float
Tertiary Variable (TV) value
19
Byte, hex
Fourth Variable (FV or QV) units code
2023
Float
Fourth Variable (FV or QV) value
Code
Class
Description
Command
Specific
Response
Codes
8
Warning – Value read invalid (one of the variables is out of range)
Command 14: Read Primary Variable Transducer Information
Note
The Transducer Serial Number is not applicable to the DVC5000 and is set to “0”.
Byte
Format
Description
Returned Value
Device Revision 2
Device Revision 3
Request
Data bytes
None
Response
Data
Bytes
02
UINT24
Transducer Serial Number
000000
000000
3
Enum
Transducer Limits and
Minimum Span Units
Code
39 (mA)
250 (Not Used)
47
Float
Upper Transducer Limit
41C00000
7FA00000 (Not A Number NAN)
811
Float
Lower Transducer Limit
00000000
7FA00000 (Not A Number NAN)
1215
Float
Minimum Span
40800000
7FA00000 (Not A Number NAN)
Code
Class
Description
Response
Codes
None