Hall Sensor— when selected indicates if the Hall Sensor readings are out of range.
Temperature Limit
D
Instrument Temperature High— when selected indicates if the device has exceeded the Instrument Temperature
High Limit.
D
Instrument Temperature Low— when selected indicates if the device has exceeded the Instrument Temperature
Low Limit.
Input Compensation Error
D
Temperature Input Error— when selected indicates if the AO temperature status or RTD status has become “Bad" or
“Uncertain" or the device is not set up correctly to receive AO temperature.
D
Upper Fluid Input Error— when selected indicates if the Upper Fluid AO status has become “Bad" or “Uncertain" or
the device is not setup correctly to receive AO density for the Upper Fluid.
D
Lower Fluid Input Error— when selected indicates if the Lower Fluid AO status has become “Bad" or “Uncertain" or
the device is not setup correctly to receive AO density for the Lower Fluid.
D
Fluid Values Crossed— when selected indicates if the process fluid density values have crossed; the Upper Fluid
density is too close to (0.1 SG), or has become greater than, the Lower Fluid density.
D
Invalid Custom Table— when selected indicates if the custom process fluid density table or torque tube table being
used for temperature compensation is invalid.
D
Temperature Out of Compensation Range—when selected indicates if the Compensation Temperature has
exceeded the compensation limits.
Calibrate
Guided Calibrations
AMS Device Manager
Configure > Calibrate > Guided Calibrations
Device Communicator
Configure > Calibrate > Full Calibration (Bench) or Full Calibration (Field)
Calibration in Use
Name
—indicates the calibration in use.
Date
—indicates when the calibration was performed.
Calibrator
—indicates who performed the calibration.
Calibration Method
—indicates the method of calibration.