4200 Series Transmitters
Instruction Manual
Form 5596
July 2005
4
Table 2. Available Configurations
TYPE
ELECTRICAL
TRAVEL
DUAL
TYPE
NUMBER
TRANSMITTER
ELECTRICAL
POSITION
SWITCHES
Standard Stroke
Up to 105 mm
(Up to 4.125 Inches)
Long Stroke
Up to 610 mm
(Up to 24 Inches)
DUAL
POTENTIOMETER
4210
4211
4212
4215
X
X
− − −
X
X
− − −
X
X
X
X
X
X
− − −
− − −
− − −
− − −
− − −
− − −
− − −
X
4220
4221
4222
X
X
− − −
X
− − −
X
− − −
− − −
− − −
X
X
X
− − −
− − −
− − −
1. See table 3 for zero and span limits.
Table 3. Zero and Span Limits
DEGREES OF
POTENTIOMETER
SLIDING STEM ACTUATOR TRAVEL
TYPE
NUMBER
POTENTIOMETER
ROTATION
CONNECTION
mm
INCHES
TYPE
NUMBER
Zero
Position
Span
CONNECTION
Zero
Position
Span
Zero
Position
Span
Zero
Position
Min.
Max.
Zero
Position
Min.
Max.
Zero
Position
Min.
Max.
4210
4211
0 to 90
15
90
1
0 to 51
8
51
0 to 2
0.315
2
4211
4212
4215
0 to 90
15
90
2
0 to 105
17
105
0 to 4.125
0.670
4.125
4220
4221
0 to 884
150
884
12-Inch Transducer
0 to 305
105
305
0 to 12
4.125
12
4221
4222
0 to 884
150
884
24-Inch Transducer
0 to 610
305
610
0 to 24
12
24
1. Refer to figures 15, 22, and 23 for locations of connections.
2. Zero position is the range of values over which the transmitter zero can be adjusted. Span is the range of shaft rotation or stem travel the transmitter span can be adjusted. For
example, a zero position of 45 degrees and a span of 15 degrees means the transmitter output is 4 mAdc after 45 degrees of shaft rotation. The output then increases from 4 mAdc to
20 mAdc as the shaft rotates from 45 to 60 degrees.
Table 4. Immunity Performance
Port
Phenomenon
Basic Standard
Performance Criteria
(1)
Electrostatic discharge (ESD)
IEC 61000-4-2
A
Enclosure
Radiated EM field
IEC 61000-4-3
A
Enclosure
Rated power frequency magnetic field
IEC 61000-4-8
A
Burst (fast transients)
IEC 61000-4-4
A
I/O signal/control Surge
IEC 61000-4-5
B
I/O signal/control
Conducted RF
IEC 61000-4-6
A
Specification limit =
±
1% of span
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Educational Services
For information on available courses for 4200 Series
electronic position transmitters, as well as a variety
of other products, contact:
Emerson Process Management
Educational Services, Registration
P.O. Box 190; 301 S. 1st Ave.
Marshalltown, IA 50158−2823
Phone: 800−338−8158 or
Phone: 641−754−3771
FAX: 641−754−3431
e-mail: [email protected]