Product data sheet
FieldQ
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America’s:
+1 281 477 4100
Europe:
+36 22 53 0950
Asia/Pacific:
+65 67 77 8211
1.604.12 Rev. 3 Page 13 of 13
November 2018
Namur NE-107 Alarms
This section describes the parameter interaction to implement a
FieldQ™ QC54 Control module to the NAMUR NE-107 require-
ments as a parameter group in the Resource Block. There are
four alarm categories defined as per the NE-107 specification,
Failed, Off Specification, Maintenance, and Check function.
Maintenance
Although the output signal is valid, the wear
reserve is nearly exhausted or a functions will soon be restricted
due to operational conditions e.g. build-up of deposits
Off Specification
Off-spec means that the device is operating
outside its specified range or an internal diagnostic indicates
deviations from measured or set values due to internal
problems in the device or process characteristics (e.g. bubble
formation in flow metering or valve sticking).
Check Function
Output signal temporarily invalid (e.g. frozen)
due to on-going work on the device.
Failed
Output signal invalid due to malfunction in the field
device or its peripherals.
Each of these categories share 32 conditions that can be defined
by the device manufacturer. Each condition may be mapped or
not mapped for each category. If a condition is mapped then it
is indicated in the* ACTIVE parameter. If the condition in the *
ACTIVE parameter is not masked by the
corresponding bit in the *_MASK parameter then the condition
will be queued for broadcast using the corresponding *ALM
parameter at the associated priority indicated by *PRI
parameter. The 4 categories are defined below.
The conditions are not expected to identify explicitly the root
cause of the condition, but rather to identify it in terms of:
• Replace the device
• Replace a part of the device
• Correct a configuration problem
• Fix something outside of the device
The above list is all that the operator needs to know to restore
his process functionality and if there are more than 31 device
conditions they should be grouped by definition into these bit
Parameter
Mnemonic
Obj
Type
Data Type/
Structure
Use/Model
Store
Size
Valid
Range
Initial
Value
Permission
Other
Range
Check
FD_CHECK_ACTIVE
S
Bit String
C/FD Active
D
4
Read only
FD_CHECK_ALM
R
DS-87
C/Alarm
D
15
FD_CHECK_MAP
S
Bit String
C/Contained
S
4
ALARM
FD_CHECK_MASK
S
Bit String
C/Contained
S
4
ALARM
FD_CHECK_PRI
S
Unsigned8
C/Alert Priority
S
1
0 - 15
0
ALARM
Yes
FD_EXTENDED_ACTIVE_n
S
Bit String
C/Contained
D
4
Read only
FD_EXTENDED_MAP_n
S
Bit String
C/Contained
S
4
FD_FAIL_ACTIVE
S
Bit String
C/FD Active
D
4
Read only
FD_FAIL_ALM
R
DS-87
C/Alarm
D
15
FD_FAIL_MAP
S
Bit String
C/Contained
S
4
ALARM
FD_FAIL_MASK
S
Bit String
C/Contained
S
4
ALARM
FD_FAIL_PRI
S
Unsigned8
C/Alert Priority
S
1
0 - 15
0
ALARM
Yes
FD_MAINT_ACTIVE
S
Bit String
C/FD Active
D
4
Read only
FD_MAINT_ALM
R
DS-87
C/Alarm
D
15
FD_MAINT_MAP
S
Bit String
C/Contained
S
4
ALARM
FD_MAINT_MASK
S
Bit String
C/Contained
S
4
ALARM
FD_MAINT_PRI
S
Unsigned8
C/Alert Priority
S
1
0 - 15
0
ALARM
Yes
FD_OFFSPEC_ACTIVE
S
Bit String
C/FD Active
D
4
Read only
FD_OFFSPEC_ALM
R
DS-87
C/Alarm
D
15
FD_OFFSPEC_MAP
S
Bit String
C/Contained
S
4
ALARM
FD_OFFSPEC_MASK
S
Bit String
C/Contained
S
4
ALARM
FD_OFFSPEC_PRI
S
Unsigned8
C/Alert Priority
S
1
0 - 15
0
ALARM
Yes
FD_RECOMMEN_ACT
S
Unsigned16
C/Contained
D
2
1 – manf
spec
0
Read only
FD_SIMULATE
R
DS-89
C/FD Simulate
D
9
disabled
FD_VER
S
Unsigned16
C/Contained
S
2
Read only