Product data sheet
FieldQ
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America’s:
+1 281 477 4100
Europe:
+36 22 53 0950
Asia/Pacific:
+65 67 77 8211
1.604.12 Rev. 3 Page 3 of 13
November 2018
General specifications:
Material housing:
Aluminium alloy
Operating media:
Air or inert gasses, filtered at 5µm
Pneumatic entry:
Metric units: G1/4"
Imperial units: 1/4”NPT
Electrical connections : Internal 3 pole terminal strip for bus
signal
Internal and external earth
connection
Optional quick connectors: 7/8" or
M12 connector (see page 9)
Cable entries:
Metric units: 2x M20x1.5
Imperial units: 1/2” and 3/4"NPT
Enclosure:
Rated IP66 - NEMA4X
Switch points:
Factory set at 15° before each end of
travel (open and closed position).
Adjustable range:
Between -3° to 15° and +75° to +93°
of the end position.
Finish:
Chromated with polyurethane
based coating.
Temperature range:
-20°C to +50°C (-4°F to +122°F)
Dimensions:
Metric:
See data sheet 1.603.08
Imperial/UNC:
See data sheet 1.603.09
DIN 3337:
See data sheet 1.603.10
Electrical safety requirements:
Use:
In and outdoor.
Altitude:
Operating full power available up to
2000 meter (6000 feet).
Maximum relative:
80% for temperatures up to 31°C
humidity
(87.8°F) decreasing linearly to 50%
relative humidity at 40°C (104°F).
Mains supply:
Up to ±10% of nominal voltage
fluctuation
Over voltage category: II
Pollution degree:
2 (3 when the cover remains closed)
Communication Protocol:
Protocol :
F
OUNDATION
™-Fieldbus
Transmission :
H1, IEC 61158-2
Maximum current :
18mA from bus
Required external :
Restrict the power supply
protection current
to <600mA.
Function blocks
The Control Module provides the following function blocks:
- Resource Block (RB)
- Transducer Block (TB)
- Analog Input (AI) Function Block
- Discrete Output (DO) Function Block
- 2x Discrete Input (DI) Function Block
- PID Function Block
Diagnostics and Alerts
Standard FOUNDATION™- Fieldbus diagnostics and alerts
provided meets Emerson PlantWeb Alerts standard.
Applicable diagnostics include:
-
Travel times for the Open stroke, Close stroke and
Average travel times.
-
Cycle Counters for Control Module, Pneumatic Module,
Actuator and Valve
-
Time in Position
-
Various internal electronic health tests.
-
Instrument temperature.
For more detailed information on diagnostics see page 10
and 11.