208/240V - 3 Phase - 50/60 Hz

PRESSURE

SWITCH

TIMERRELA

Y

MANUAL

RESET

Timer Checkout

1)  De-energize compressor/control circuit. Insert small

 

screwdriver to hold bellows lever tab down (no pressure

 

position), see figure 3.

2)  Re-energize compressor/control circuit – timer should then

 

be energized and stop the compressor in the preset time

 

period. After checkout, the FD113 timer must be reset.

Pressure Checkout

1)  To accurately check the operating pressure of the FD113,

 

the compressor must be de-pressurized, the FD113 “Oil”

 

and “Low” pressure lines disconnected and a check

 

performed as outlined in “pressure check” under the 

 

checking and adjusting procedure.

CONTROL CHECKOUT

FIGURE 2—FD113 MOUNTING DIMENSIONS

Contacts below are shown in normal run condition with oil pressure.

Typical Old Copeland 3-Wire Oil Pressure Safety Control Wiring

Manual reset timer contacts. Terminal 21 to 22 closed 

during normal run and during time-out – open on time-out. 

Terminals 21/24 (signal) closed after time-out.

Power to Timer thru pressure switch contacts. During normal run, 

11/14 closed for “safe light” circuit. On loss of pressure, 11/14 open 

and timer is energized for time delay period until trip-out.

FIGURE 4

FIGURE 3

Optional Current Sensing Relay

 in Series with N/T1 line

  for compressors with internal line break motor protectors.

  (Prevents oil pressure safety control from tripping when internal

  line-break motor protector trips.)

FIGURE 5

TIMER

RESET

BUTTON

Содержание FD113

Страница 1: ...ing Mount the control in a protected area on the mounting bracket or a flat surface with screws provided CAUTION If other screws are used use 8 32 screws that do not penetrate into the control more than 1 8 Oil Pressure Safety Controls should always be mounted above the oil level in the compressor crankcase The capillary tubes or pressure connections should be routed to allow them to be free drain...

Страница 2: ...mately 10 PSIG factory 6 Slowly re pressurize Continuity light should re energize approximately 5 PSI above de energize pressure Pressure Adjustment 1 To change pressure adjustment from factory setting remove control cover Rotate notched pressure setting disc in the control right to increase left to decrease settings see figure 1 Repeat steps 4 6 to determine settings Adjust Repeat as necessary to...

Страница 3: ... checking and adjusting procedure CONTROL CHECKOUT FIGURE 2 FD113 MOUNTING DIMENSIONS Contacts below are shown in normal run condition with oil pressure Typical Old Copeland 3 Wire Oil Pressure Safety Control Wiring Manual reset timer contacts Terminal 21 to 22 closed during normal run and during time out open on time out Terminals 21 24 signal closed after time out Power to Timer thru pressure sw...

Страница 4: ... voltage leakage paths from the compressors connections winding to ground Optional Current Sensing Relay in Series with N L1 line for compressors with internal line break motor protectors Prevents oil pressure safety control from tripping when internal line break motor protector trips FIGURE 6 Typical 3 Wire Separate Power Source NOTE Contactor Coil Alarm and Normal Light must be same voltage as t...

Отзывы: