![Emerson FA-700 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/emerson/fa-700/fa-700_installation-and-operation-manual_104229006.webp)
Table 2: LED Operational States
LEDs
Operational States
Power
•
ON green when the FA-700 is plugged into the AC power adapter
•
OFF when operating in battery mode to preserve power
Program
•
FLASHES red with a press of the PROGRAM key
•
ON red
(not flashing)
while programming phone number.
•
OFF in normal operation mode
•
OFF when AC power fails to preserve back-up battery power
Alarm
•
ON red when in alarm mode
•
OFF when in normal operation mode
•
OFF when AC power fails to preserve back-up battery power
Operation
FA-700 normal operation
In normal operations mode, the FA-700:
•
Monitors the ambient temperature thru an on-board temperature sensor.
•
Monitors the AA backup batteries for low power.
How the FA-700 receives power
The FA-700 receives power from a 6-volt AC power adapter (included) and two AA batteries
(not included)
that
supply back-up power during an AC power failure.
Alarm operation
The FA-700 will monitor and send a factory-recorded voice message
to the entered phone
number for the following alarms:
•
If the temperature falls below 45ºF
(7ºC)
or rises above 85ºF
(34ºC
) (DIP switch selectable)
•
If the unit encounters a low battery condition
How the FA-700 handles an alarm condition
Stage
Description
A.
When an alarm occurs, the alarm LED lights up
(if not an AC power failure).
B.
The FA-700 starts calling the programmed phone number attempting to deliver
an in-progress alarm voice message. If it receives a busy signal or no answer after
10 rings
,
it will immediately hang up.
C.
The FA-700 will continue calling the programmed phone number, every 15 or
120 minutes
(DIP switch selectable)
until a called party answers.
D.
When the called party answers
(person or answering machine)
, it will deliver its
factory pre-recorded alarm message, identifying the specific alarm condition(s).
E.
The FA-700 will continue calling until the following action is taken:
•
Locally, press the CANCEL key on the key pad.
•
Remotely, over the phone, press the number “1” key then the “#” key on the
key pad anytime during the alarm message.
F.
Once the alarm call-out is canceled, the FA-700 will do one of two things:
•
If alarm is still active, you may call to hear the current alarm condition.
•
If alarm condition has been corrected, it will not respond to the incoming call.
G.
When you cancel an alarm call-out, and correct the cause of the alarm, the alarm
LED will go out, and the unit will reset to normal operation automatically.
Содержание FA-700
Страница 20: ......