![Emerson ECM850 Скачать руководство пользователя страница 64](http://html.mh-extra.com/html/emerson/ecm850/ecm850_user-manual_101596064.webp)
User Manual
Chapter 3
GFK-2849A
Oct 2019
Configuration
57
11.
In the dialogue box <server name> RCB Assignment, click OK to close. On closure of
the IEC 61850 Configurator, all required PPVs are generated automatically in the
project. This is shown in the screenshot below, where report-related parameters are
shown as variables. It also includes the normal DO/DA variables, which are part of
the report.
Figure 56
12.
In the dialogue box <server name> RCB Assignment, click OK to close. The
configuration can be downloaded to the RX3i Controller and the controller can be
put in RUN mode. Reports get enabled (see RptEna_RP = 1), if the configuration is
valid. The DO/DA data in the report gets updated based don the trigger options as
set in the client configuration.
Figure 57