Oct 2019
Diagnostics
105
5.1.2
Problems during Powerup and Reset
Certain conditions can prevent the module from powering up and becoming operational or
entering firmware update mode:
Problem
Indication
Action
Hardware failure
All Indicator LEDs off. Module
unresponsive.
Contact Technical Support to
arrange for repair and
replacement
Invalid bootstrap image
Invalid boot image
No Indicator LEDs turn on and the
module is unresponsive, or
The STATUS LED is solid Green and is
the only LED that is on.
Power-up
diagnostics/hardware
initializations fail that are
considered fatal
LED Fatal Error blink code, as
described in this chapter.
Note the blink code and
contact Customer Service.
Non-Fatal
diagnostic/hardware
initialization faults
The module continues normal
power-up, but an entry is added to
the Local Log table and the RX3i
CPU’
s fault table (if backplane
communications have been
established).
Note the fault and contact
Customer Service.
The module does not
contain hardware identity
information
LED Fatal Error blink pattern, as
described in this chapter.
Note the blink code and
contact Customer Service.
5.1.3
Transitioning to Firmware Update Mode
The module transitions to firmware update mode for any of the following reasons:
1.
Winloader has commanded the module to enter firmware update mode. This is
normal when a firmware update has been initiated from Winloader.
2.
The ECM850 does not have a valid firmware image at power-up. The ECM850
performs checks to determine the firmware image is valid and has not been
corrupted before it begins execution. If the validation fails, firmware update mode
is activated until a valid image has been stored.
For more information about firmware update mode and using Winloader, please see
Chapter 2:, Installation.