READ CAREFULLY
PRINCIPLE OF OPERATION
Easy Heat TSR is a self-regulating heating cable that automatically
varies its heat output with changes in surrounding temperature.
Since this cable regulates its heat output with temperature,
a thermostat may not be necessary for some applications.
Easy Heat TSR cable can be used for pipe freeze protection or
temperature maintenance applications, in either ordinary or
hazardous (CID2) locations. TSR cable is also available with fluor
-
opolymer overjacket for use in areas requiring enhanced chemi-
cal resistance. TSR cable with fluoropolymer overjacket is suitable
for maintaining grease and fuel lines at temperatures required for
flow conditions.
The TSR cable is available with power densities of 3, 5, 8 and 10
Watts per foot. This power is specified at a surrounding tempera
-
ture of 50
o
F. At other temperatures, of course, the cable power
output will be considerably different. (See chart).
Nominal Power Output on
Metal Pipe
25
50
75
100
125
150
Pipe Temperature
o
F
WATTS/FT
8
w
/
ft
5
w
/
ft
3
w
/
ft
10
8
6
4
2
0
10
w
/
ft
CONSTRUCTION DETAILS
tinned copper
GroUnd
BrAid
BUS
WireS
FLAMe retArdAnt
tpe oUter JAcKet
poLyoLeFin
oVer
JAcKet
tpe inner
JAcKet
irrAdiAted SeLF-reGULAtinG
HeAtinG core MAteriAL
16 AWG
tinned
copper
Note: All above cables are also available with fluoropolymer over jacket (for enhanced
chemical resistance, change suffix J to F). *Lengths good for 208 & 277 VAC
Performance and Rating Data
Power Rating
Catalog
Service
Watts/ft
Maximum
Number
Voltage
@ 50
o
F (10
o
C)
Single Run Length
TSR31J
120
3
325' (99
m)
TSR32J
240
3
650' (198M)*
TSR51J
120
5
270' (82M)
TSR52J
240
5
540' (165M)*
TSR81J
120
8
210' (64M)
TSR82J
240
8
420' (128M)*
TSR101J
120
10
180' (55M)
TSR102J
240
10
360' (110M)*
TSR SPECIFICATIONS/APPLICATION INFORMATION
Note:
1) Maximum maintenance temperature of all cables is 150
o
F (66
o
C) with
185
o
F (85
o
C) maximum intermittent exposure temperatures.
2) For applications in hazardous (classified) locations, all cables have a
T5 surface temperature identification number.
Voltage Adjustment Table
Power Rating multiplier
Cable
208
220
277
(Suffix J/F)
VAC
VAC
VAC
TSR32
0.85
0.91
1.13
TSR52
0.87
0.92
1.09
TSR82
0.88
0.93
1.08
TSR102
0.89
0.94
1.05
TSR
Self-Regulating Pipe Tracing Heating Cable
Specification/Application Guide
©2008 Easy Heat
www.easyheat.com
40252-001 Rev. 5
Because of the self-regulating feature of this cable, it can be
wrapped over itself (overlapped), if necessary, when installed on
pipes, valves or flanges.