Complete Resource Block Parameter Listing (cont’d)
SHED REMOTE OUT
Time duration at which to give up on computer writes to function block Rout locations. Shed from
Rout shall never happen when SHED REMOTE OUT = 0.
FAULT_STATE
Condition set by loss of communication to an output block, fault promoted to an output block or a
physical contact. When Fault State condition is set, then output function blocks will perform their
FSTATE actions.
SET FAULT STATE
Allows the Fault State condition to be manually initiated by selecting Set.
CLEAR FAULT STATE
Writing a Clear to this parameter will clear the device fault state if the field condition, if any, has
cleared.
MAXIMUM NOTIFY
Maximum number of unconfirmed alert notify message possible.
LIMIT NOTIFY
Maximum number of unconfirmed alert notify messages allowed.
CONFIRM_TIME
The time the resource will wait for confirmation of receipt of a report before trying again. Retry shall
not happen when CONFIRM_TIME = 0.
WRITE_LOCK
If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block inputs will
continue to be updated.
UPDATE_EVT
This alert is generated by any change to the static data.
BLOCK_ALM
The block alarm is used for all configuration, hardware, connection failure or system problems in
the block. The cause of the alert is entered in the subcode field. The first alert to become active will
set the Active status in the Status attribute. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported without clearing the Active status, if the
subcode has changed.
ALARM SUMMARY
The current alert status, unacknowledged states, unreported states, and disabled states of the
alarms associated with the function block.
ACKNOWLEDGE OPTION
Selection of whether alarms associated with the block will be automatically acknowledged.
WRITE PRIORITY
Priority of the alarm generated by clearing the write lock.
WR_ALM
This alert is generated if the write lock parameter is cleared.
ITK_VER
Major revision number of the interoperability test case used in certifying this device as
interoperable. The format and range of the version number is defined and controlled by the
Fieldbus Foundation. Note: The value of this parameter will be zero (0) if the device has not been
registered as interoperable by the FF.
DETAILED BLOCK ERRORS
Provides list of all active block alarms in the block.
SUPPORTED_MODES
The modes supported by this particular block.
IKEY
TopWorx revision control.
REVISION_ID
TopWorx revision control.
REVISION_DATE
TopWorx revision control.
DEVICE REVISION
Manufacturer revision number associated with the resource. Used by an interface device to locate
the DD file for the resource.
CHARACTERISTICS: BLOCK_TAG
Defined to be unique throughout the control system at one plant site. The Tag may be changed
using the FB_TAG service.
MEMORY SIZE
Available configuration memory in the emptry resource. To be checked before attempting
download.
NONVOLATILE CYCLE TIME
Interval between writing copies of NV parameters to non-volatile memory. Zero means never.
Содержание DXP-FF
Страница 11: ...www topworx com 11 TM DO DO DO DO DO DO DO ...
Страница 12: ...D Series with FF Option Installation Operation Maintenance 502 969 8000 12 ...
Страница 25: ...www topworx com 25 TM Complete Transducer Parameter Listing cont ...
Страница 37: ...www topworx com 37 TM Warranty ...
Страница 38: ...D Series with FF Option Installation Operation Maintenance 502 969 8000 38 NOTES ...
Страница 39: ...www topworx com 39 TM NOTES ...