background image

 

1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx 

XWi70K

 

5/15 

 

LS 

Minimum Set Point:

 (-100.0°C to SET; -148°F to SET) fix the minimum value for the 

set point. 

US 

Maximum Set Point:

 (SET to 150.0°C; SET to 302°F) fix the maximum value for the 

set point. 

HY 

Compressor regulation differential in normal mode:

 (0.1 to 25.0°C; 1 to 45°F) set 

point  differential.  Compressor  Cut-IN  is 

T  >  SET  +  HY

.  Compressor  Cut-OUT  is 

T<=SET

HY1 

Proportional  band in normal mode:

 (0.1 to  25.5°C;  1 to 45°F) define  a second 

regulation  band  which  is  used  when  double  ONOFF  compressor  regulation  or  a 
variable speed compressor is configured.

 

odS 

Output activation delay at start-up:

 (0 to 255 min) this function is enabled after the 

instrument power-on and delays the output activations. 

AC 

Anti-short cycle delay:

 (0 to 999 sec) minimum interval between a compressor stop 

and the following restart. 

AC1 

Anti-short cycle delay (2nd compressor):

 (0 to 999 sec) delay before activating 

second compressor, depending on regulation mode selected by par. 

2CC

 

2CC 

Activation mode for 2nd compressor (valid if oAx=CP1 and oAy=CP2):

 (FUL; 

HAF) 

FUL

=second  compressor  will  be  activated  after 

AC1

  delay. 

HAF

=second 

compressor will be activated with step logic. 

rCC 

Enable compressor rotation: 

(n;Y) 

n

 = CP1 is always the first compressor activated. 

Y

 = CP1 and CP2 activation is alternated 

MCo 

Maximum time with compressor ON: 

(0 to 255min) maximum time with ONOFF 

compressor active. With 

MCo=0

 this function is disabled. 

rtr 

Regulation percentage=F(P1; P2) (100=P1; 0=P2): 

100=P1 only; 0=P2 only

 

CCt 

Maximum duration for Pull Down:

 (0.0 to 99h50min, res. 10min) after elapsing this 

time interval, the super cooling function is immediately stopped. 

CCS 

Pull Down phase differential (SET+CCS or SET+HES+CCS):

  

(-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the regulation 
SETPOINT is moved to 

SET+CCS 

(in normal mode) or to 

SET+HES+CCS

 (in 

energy saving mode)

 

oHt 

Threshold  for  automatic  activation  of  Pull  Down  in  normal  mode 
(SET+HY+oHt): 

(0.0 to 25.5°C; 0 to 45°F) this is the upper limit used to activate the 

super cooling function. 

Con 

Compressor  ON  time  with  faulty  probe:

  (0  to  255  min)  time  during  which  the 

compressor is active in case of faulty thermostat probe. With 

Con=0

 compressor is 

always OFF. 

CoF 

Compressor  OFF  time  with  faulty  probe:

  (0  to  255  min)  time  during  which  the 

compressor is OFF in case of faulty thermostat probe.  With 

CoF=0

 compressor is 

always active. 

PROBE MENU 

 Prb 

PbC 

Probe selection: 

(ntC; Pt1) 

ntC

=NTC type; 

Pt1

=PT1000 type 

ot 

Probe P1 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible 

offset of the first probe. 

P2P 

Probe P2 presence:

 

n

 = not present; 

Y

 = present. 

oE 

Probe P2  calibration:

 -12.0 to 12.0°C; -21  to 21°F)  allows to  adjust  any  possible 

offset of the second probe. 

P3P 

Probe P3 presence:

 

n

 = not present; 

Y

 = the defrost is present. 

o3 

Probe P3 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible 

offset of the third probe. 

P4P 

Probe P4 presence:

 

n

 = not present; 

Y

 = present.

 

o4 

Probe P4 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible 

offset of the fourth probe. 

VARIABLE SPEED DRIVE MENU 

 vSC 

FMi 

Minimum  value  for  Variable  Speed  Compressor  (RPM  *  10):

  (0  to  FMA)  select 

according to the VSC in use

 

FMA 

Maximum value for Variable Speed Compressor (RPM * 10):

 (FMi to 500) select 

according to the VSC in use 

EMi 

Minimum  value  for  Variable  Speed  Compressor  (RPM  *  10)  in  Energy  Saving 
Mode:

 (0 to EMA) select according to the VSC in use

 

EMA 

Maximum  value for Variable Speed  Compressor (RPM * 10)  in Energy Saving 
Mode:

 (EMi to 500) select according to the VSC in use

 

Fr0 

Value when Variable Speed Compressor is shut down (RPM * 10):

 (0 to 200) select 

according to the VSC in use 

tSt 

PI regulator, temperature sampling time:

 (00:00 to 42min:30sec) 

 

iSt 

PI regulator, integral sampling time:

 (00:00 to 42min:30sec)

 

vdC 

Type of Variable Speed Compressor:

 (nu; FrE) 

nu

 = no VSC in use; 

FrE

 = VSC with 

frequency control mode is used; 

VC1

 = Embraco with serial control; 

VC2

 = SECOP 

with serial control.

 

voS 

Signal output variation for Variable Speed Compressor: 

(0 to 100 Hz or RPM*10) 

VSC variation when 

SET-

HY ≤ T ≤ SET+HY

 

vo2 

Signal output variation for Variable Speed Compressor: 

(0 to 100 Hz or RPM*10; 

nu)) VSC variation when

 SET-HY-

HY1≤T<SET

-

HY and SET+HY<T≤SET+HY+HY1

 

vo3 

Signal output variation for Variable Speed Compressor: 

(0 to 100 Hz or RPM*10; 

nu)) VSC variation when

 SET-HY-HY1<T and T>SET+HY+HY1 

PdP 

Variable Speed Compressor (in %) during any Pull Down: 

(0 to 100%) this value 

is always calculated using FMi and FMA limits. 0=function disabled.

 

SPi 

Compressor speed (in %) in case of any probe error during Con interval:

 (0 to 

100%) this value is always calculated using FMi and FMA limits.

 

Aod 

Compressor speed (in %) during any defrost cycle (valid if tdf=in):

 (0 to 100%) 

this value is always calculated using FMi and FMA limits.

 

AoF 

Compressor speed (in%) during a pre-defrost phase (valid if tdf=in):

 (0 to 100%) 

this value is always calculated using FMi and FMA limits.

 

tHv 

PI regulator, max interval for output variation:

 (tLv to 255 sec)

 

tLv 

PI regulator, min interval for output variation:

 (1 sec to tHv) 

rSr 

PI regulator, range for output value calculation (RPM * 10):

 (0=disabled; 1 to 255 

RPM*10) 

Str 

PI regulator, delay before range drift: 

(0 to 255 sec) 

dPt 

PI regulator, divisor for PI response time reduction (acts on both par. tSt and 
iSt):

 (1 to 10) 

CMn 

Continuous control ON in normal mode: 

(n; Y) 

Y

 = VSC is never stopped during 

regulation.

 

CME 

Continuous control ON in energy saving mode:

 (n; Y) 

Y

 = VSC is never stopped 

during regulation.

 

MnP 

Compressor  speed  threshold  to  activate  lubrication  (valid  for  variable  speed 

compressors only, 0=disabled):

 (nu; 1 to 100%; OFF) nu = not used; 1 to 100% = 

select the  percentage to  activate function; OFF = compressor is stopped  when the 
condition is reached 

 

tMi 

Time  range  with  compressor  speed  below  MnP  to  activate  lubrication  cycle: 

(00:00 to 24h00min) time before activating the lubrication function

 

tMA 

Time range with compressor speed at 100% to activate lubrication cycle:

 (0 to 

255 min) VSC will be forced to 100%, for 

tMA

, after activating the lubrication function. 

NOTE: if 

MnP=OFF

, VSC will be stopped for 

tMA 

A00 

Number of serial controlled VSC:

 (1 to 2) number of VSC connected

 

A01 

Serial address for compressor 1:

 (1 to 247)

 

A02 

Serial address for compressor 2:

 (1 to 247)

 

VARIABE SPEED FAN (MODBUS) - vSF 

S00 

Number  of  serial  condenser  fans  (0=disabled): 

(0  to  4)  number  of  variable 

speed condenser fans controlled via Modbus. Only EMB ventilators are supported. 

C01…C04

 

Serial addresses for condenser fans:

 (1 to 247) up to 4 condenser fan can be 

controlled in parallel (all of them will use the same speed value).

 

F12 

Serial  baudrate  for  condenser  fan  (kbaud):  4.8

=4800baud;

  9.6

=9600baud; 

19.2

=19200baud 

SFr 

Direction of rotation for condenser fan:

 (Lt; rt) 

Lt 

= left rotation; 

rt 

= right rotation 

tCC 

Time with condenser efficiency function activated:

 (0 to 255 sec) interval for 

condenser fans cleaning function. 

CdF 

Default configuration sent to condenser fan (at power on):

 (n; Y)

 

DISPLAY MENU - diS 

CF 

Temperature measurement unit: 

(°C; °F) 

°C 

= Celsius; 

°F

 = Fahrenheit. 

rES 

Temperature resolution:

 (dE; in) 

dE

 = decimal; 

in

 = integer. 

rEd 

Remote  keyboard visualization: 

(P1; P2; P3; P4; Set; dtr) 

Px

=probe “x”; 

Set

=set 

point; 

dtr

=percentage calculated from P1 and P2 and using par. 

dtr

.

 

dLY 

Temperature display delay:

 (0.0 to 20min00sec, res. 10 sec) when the temperature 

increases, the display is updated of 1°C or 1°F after this time. 

dtr 

Probe visualization percentage, F(P1; P2): 

(1 to 99)

 

with 

dtr=1

 the display will show 

this value 

VALUE=0.01*P1+0.99*P2 

DEFROST MENU - dEF 

EdF 

Defrost mode:

 

in

=fixed intervals; 

rtC

=following real time clock

 

tdF 

Defrost type: EL

=electrical heaters; 

in

=hot gas

 

dFP 

Probe selection for defrost control:

 (nP; P1; P2; P3; P4) 

nP

=no probe; 

Px

=probe 

“x”.

 

dSP 

Probe  selection  for  2

nd

  defrost  control:

  (nP;  P1;  P2;  P3;  P4) 

nP

=no  probe; 

Px

=probe “x”.

 

dtE 

End defrost temperature:

 (-55 to 50°C; -67 to 122°F) sets the temperature measured 

by the evaporator probe (

dFP

), which causes the end of defrost cycle.

 

dtS 

End  2

nd

  defrost  temperature:

  (-55  to  50°C;  -67  to  122°F)  sets  the  temperature 

measured by the evaporator probe (

dFP

), which causes the end of defrost cycle.

 

idF 

Interval between two successive defrost cycles:

 (0 to 120 hours) determines the 

time interval between the beginning of two defrosting cycles. 

MdF 

Maximum length of defrost cycle:

 (0 to 255 min; 0 means no defrost) when 

P2P=n

 

(no evaporator probe presence) it sets the defrost duration, when 

P2P=Y

 (defrost end 

based on evaporator temperature) it sets the maximum length for the defrost cycle. 

MdS 

Maximum  length  of  2

nd

  defrost  cycle:

  (0  to  255  min;  0  means  no  defrost)  when 

P2P=n

  (no  evaporator  probe  presence)  it  sets  the  defrost  duration,  when 

P2P=Y

 

(defrost  end  based on  evaporator temperature) it sets the maximum length for the 
defrost cycle.

 

dSd 

Start defrost delay: 

(0 to 255 sec) delay in defrost activation.

 

StC 

Compressor  off-cycle  before  starting  any  defrost: 

(0  to  255  sec)  interval  with 

compressor OFF before activating hot gas cycle

 

dFd 

Displaying during  defrost:

  (rt;  it;  SEt;  dEF;  Coo) 

rt

  =  real  temperature; 

it

  =  start 

defrost temperature; 

SEt

 = set point; 

dEF

 

= label “

dEF

”; 

Coo 

= when a defrost ends, 

it shows the label “Coo” until the regulation temperature is above 

SET+HY+HY1

 

dAd 

Temperature  display delay  after any defrost cycle: 

(0  to  255 min)  delay  before 

updating the temperature on the display after the end of any defrost. 

Fdt 

Draining time: 

(0 to 120 min) regulation delay after finishing a defrost phase

 

Hon 

Drain heater enabled after draining time (par. Fdt):

 (0 to 255 min) the relative output 

will stay on after draining time.

 

SAt 

Sampling time to calculate the average compressor speed before any desfrost 
cycle: 

(0 to 255 min) the average compressor speed is used only with VSC. 

dPo 

Defrost cycle enebled at stat-up: 

(n; Y) enables defrost at power on.

 

dAF 

Pre-defrost time:

 (0 to 255 min) enable a lower setpoint (SET-1°C or SET-2°F) before 

activating the defrost phase.

 

od1 

Automatic defrost (at the beginning of any energy saving mode): 

(n; Y) 

n

=function 

disabled; 

Y

=function enabled 

od2 

Optimized defrost: 

(n;Y) 

n

 = function disabled; 

Y

 = the controller needs a temperature 

probe  placed  on  the  evaporator  surface  to  monitor  the  presence  of  ice  during  any 
defrost phase. 

Syd 

Type  of  synchronized  defrost: 

(n;  SYn;  nSY;  rnd) 

n

  =  function  disabled; 

SYn

  = 

synchronized, all devices connected will start a defrost phase at the same time. 

nSY

 

= de-synchronized, all devices connected will delay the beginning of the same defrost 
phase; 

rnd 

= random defrost function.

 

dt1 

Differential temperature for latent heating control 

(0.1 to 1.0 °C) to catch the latent 

heating phase during any defrost

 

ndE 

Number  of  connected  controllers  for  special  defrost  operations  (valid  if 
Syd=SYn, nSY or rnd): 

(1 to 20) number of devices connected to the same network 

for syncro, desyncro or random defrost.

 

FAN MENU - FAn 

FAP 

Probe selection for evaporator fan: 

(nP; P1; P2; P3; P4) 

nP

=no probe; 

Px

=probe “x”.

 

Содержание Dixell XWi70K

Страница 1: ... delay AC1 is always respected The second compressor is deactivated when T SET HY With parameter rCC it is possible to enable the compressor rotation function the activation of the first and the second compressor will be alternated to equalize the number of working hours of both of them In case of hot gas defrost operation it is possible to select if one or both compressors will be used 3 2 PULL D...

Страница 2: ... for auxiliary regulator 2 Sd2 Auxiliary regulator 2 disabled during any defrost 9 ANALOGUE OUTPUTS The controller is equipped with 2 configurable analogue outputs type 4 20mA or 0 10Vdc both selectable It is possible to use them for proportional regulation of Evaporator fan speed Condenser fan speed Or as proportional output linked to the Auxiliary regulator 1 linked only to analogue output 1 Aux...

Страница 3: ... manually by the user 11 7 DEAD BAND oAx db By setting oAx db the controller will perform a dead band regulation The heating element has to be connected to the correspondent relay If the temperature increases and reaches set point plus differential HY the compressor is started and then turned off when the temperature reaches the set point value again If the temperature decreases and reaches the se...

Страница 4: ...accessible parameters under a specific menu operate as follows 1 Enter the Programming mode by pressing the SET DOWN key for 3 seconds 2 The display will show the first menu available under Pr1 level 14 4 HOW TO ENTER PARAMETER PROGRAMMING MENU PR2 In the PR2 level there are all the parameters of the instrument 14 4 1 ENTERING THE PARAMETER PROGRAMMING MENU PR2 1 Enter the Programming mode by pres...

Страница 5: ... control ON in normal mode n Y Y VSC is never stopped during regulation CME Continuous control ON in energy saving mode n Y Y VSC is never stopped during regulation MnP Compressor speed threshold to activate lubrication valid for variable speed compressors only 0 disabled nu 1 to 100 OFF nu not used 1 to 100 select the percentage to activate function OFF compressor is stopped when the condition is...

Страница 6: ...tput value at the end of the scale 2At Interval of time with analogue output 2 maximum value 0 to 255 sec analogue output is forced at 100 after any activation for 2At seconds ALARM MENU ALr ALP Probe selection for temperature alarms nP P1 P2 P3 P4 nP no probe Px probe x Note P4 Probe on Hot Key plug ALC Temperature alarm configuration Ab rE Ab absolute rE relative ALU High temperature alarm when ...

Страница 7: ...mable defrost cycles during any ddx day Example when Ld2 12 4 the second defrost starts at 12 40 am during working days N B To disable a defrost cycle set it to nu not used Ex if Ld6 nu the sixth defrost cycle will be disabled SERIAL COMMUNICATION CoM Adr Serial address 1 to 247 device address for Modbus communication bAU Baudrate 9 6 19 2 select the correct baudrate for serial communication USER ...

Страница 8: ...automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation...

Страница 9: ...t Maximum duration for Pull Down 04 00 Pr1 hour CCS Pull Down phase differential SET CCS or SET HES CCS 1 Pr1 F oHt Threshold for automatic activation of Pull Down in normal mode SET HY oHt 10 Pr1 F Con Compressor ON time with faulty probe 30 Pr1 min CoF Compressor OFF time with faulty probe 10 Pr1 min PbC Probe selection ntC Pr2 ot Probe P1 calibration 0 Pr1 F P2P Probe P2 presence yes Pr1 oE Pro...

Страница 10: ...r2 C ndE Number of connected controllers for random refrost Syd rnd 1 Pr2 FAP Probe selection for evaporator fan P3 Pr1 FSt Evaporator fan stop temperature 50 Pr1 F HyF Evaporator fan regulator differential 2 Pr1 F FnC Evaporator fan operating mode O_n Pr1 Fnd Evaporator fan delay after defrost cycle 4 Pr1 min FCt Differential temperature for cyclic activation of evaporator fans 0 disabled 0 Pr1 F...

Страница 11: ...ential in energy saving 1 Pr1 F ESt Energy saving timeout 24 Pr1 hour LdE Energy saving controls the lights lights OFF when energy saving goes active no Pr1 LHt Maximum duration for light output on 0 Pr1 min HUr Hours Pr1 Min Minutes Pr1 dAy Day of the week Pr1 dyM Day of the month Pr1 Mon Month Pr1 yAr Year Pr1 Hd1 First day of weekend nu Pr1 Hd2 2nd day of weekend nu Pr1 iLE Energy saving cycle ...

Страница 12: ...r max interval for output variation 30 Pr2 sec tLv_nt PI regulator min interval for output variation 10 Pr2 sec rSr_nt PI regulator range for output value calculation RPM 10 90 Pr2 RPM 10 Str_nt PI regulator delay before range drift 60 Pr2 sec dPt_nt PI regulator divisor for PI response time reduction acts on both par tSt and iSt 1 Pr2 CMn_nt Continuous control ON in normal mode yes Pr2 CME_nt Con...

Страница 13: ...Interval of time with analogue output 1 maximum value 5 Pr1 sec 2An_nt Type of analogue output 2 Vlt Pr1 2oL_nt Minimum value for analogue output 2 5 Pr1 2oH_nt Maximum value for analogue output 2 100 Pr1 2At_nt Interval of time with analogue output 2 maximum value 5 Pr1 sec ALP_nt Probe selection for temperature alarms nP Pr1 ALC_nt Temperature alarms configuration relative absolute Ab Pr1 ALU_nt...

Страница 14: ...no Pr1 dd7_nt Saturday defrost no Pr1 Ld1_nt 1st defrost starting time nu Pr1 hour Ld2_nt 2nd defrost starting time nu Pr1 hour Ld3_nt 3rd defrost starting time nu Pr1 hour Ld4_nt 4th defrost starting time nu Pr1 hour Ld5_nt 5th defrost starting time nu Pr1 hour Ld6_nt 6th defrost starting time 12 00 Pr1 hour Adr_nt Serial address 1 Pr1 bAU_nt Baudrate 9 6 Pr1 brd_nt Type of keyboard lock UnL Pr2 ...

Страница 15: ...ac 30K cycles Motor load 2HP 12FLA 72LRA 230Vac 30K cycles Motor load 1HP 16FLA 96LRA 110Vac 30K cycles Motor load 4 9FLA 29 4LRA 110 230Vac 30K cycles 14 8 A 230Vac 30K cycles oA2 SPST 16A 250VAC Resistive load 10A 230 Vac 30K cycles 14A NO 230Vac 50K cycles oA3 SPST 8A 250VAC Resistive load 10A 110 230Vac 30K cycles Motor load 1 2HP 230Vac 30K cycles Motor load 4 9FLA 29 4LRA NO 110 230Vac 30K c...

Отзывы: