1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx
XWi70K
15/15
25
TECHNICAL DATA
FEATURES
DESCRIPTION
Housing
Self-extinguishing PC
Dimensions
8-DIN, 140x176x148
Mounting
DIN rail mounting device
Degree of Protection
NEMA (UL 50e)
Indoor use, Open Type
IP (IEC/EN 60529)
IP00
Power Supply
230Vac
10%, 50/60Hz; 110Vac
10%, 50/60Hz
Overvoltage Category
III
Rated Power
110VAC: 10VA; 230VAC: 10VA
Rated Impulse Voltage
4000V
Display Supported Models
CH620, V620H, T620x and T820x (x=H or T)
Software Class
A
Terminal blocks / Terminal Connections
Plug-in or screw terminal block, wire section between 0,5 and 2,5 mm2
Max tightening force: 0.4 N/m for 5,0mm pitch
Data Storing
Real Time Clock:
Data maintenance up to 6 months with lithium battery.
Other parameters:
internal EEPROM.
Type of Action
1.B
Pollution Degree
2, non-condensing humidity
Ambient Operating Temperature and Humidity
IEC/EN
0T50°C; 20-85 rH% (non-condensing humidity)
UL-CAN/CSA
-10T50°C; 20-85 rH% (non-condensing humidity)
Shipping and storage temperature
-40T85°C; 20-85 rH% (non-condensing humidity)
Resistance to Heat
UL 94 V-0
Measurement range
NTC:
-40T110°C, resolution 0.1°C or 1°C (selectable);
PT1000:
-100T150°C, resolution 0.1°C or 1°C (selectable);
PTC:
-50T150°C, resolution 0.1°C or 1°C (selectable)
Accuracy
±1°C relative to the full scale
Inputs
4 NTC, PTC or PT1000 (configurable); Up to 2 voltage free contacts
I/O port
HOT-KEY: MAX voltage allowed is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY.
Serial Outputs (*)
TTL standard available on 5-pin port (HOT-KEY connector); 2-wire RS485 with termination; 6-wire for VCC; Maximum cable length = 2m
Relay Outputs (standard)
Ref
Nominal
UL
IEC
oA1,
oA4
SPST 20A,
250VAC
Resistive load 14A, 110/230Vac, 30K cycles
Motor load 2HP (12FLA/72LRA), 230Vac, 30K cycles
Motor load 1HP (16FLA/96LRA), 110Vac, 30K cycles
Motor load 4.9FLA/29.4LRA, 110/230Vac, 30K cycles
14(8)A, 230Vac, 30K cycles
oA2
SPST 16A,
250VAC
Resistive load 10A, 230 Vac, 30K cycles
14A (NO), 230Vac, 50K cycles
oA3
SPST 8A,
250VAC
Resistive load 10A, 110/230Vac, 30K cycles
Motor load 1/2HP, 230Vac, 30K cycles
Motor load 4.9FLA/29.4LRA (NO), 110/230Vac, 30K cycles
8(3)A (CO), 230Vac, 100K cycles
oA5
SPDT 7A
250VAC
Resistive load 4A, 250Vac, 100K cycles
4A, 250Vac, 100K cycles
Relay Outputs (optional, on request only)
oA2
SPST 8A,
250VAC
Resistive load 10A, 110/230Vac, 30K cycles
Motor load 1/2HP, 230Vac, 30K cycles
Motor load 4.9FLA/29.4LRA (NO), 110/230Vac, 30K cycles
8(3)A (CO), 230Vac, 100K cycles
oA2,
oA4
SPST 16A inrush,
250VAC
Resistive load 14A, 230Vac, 30K cycles
14A, 230Vac, 50K cycles
oA3
SPST 10A
250VAC
Resistive load 10A, 230Vac, 50K cycles
10A, 230Vac, 25K cycles
oA4
SPST 16A,
250VAC
Resistive load 10A, 230 Vac, 30K cycles
14A (NO), 230Vac, 50K cycles
Maximum ampacity
12A Plug-in terminal block, 14A other types,4A on insulated relay oA5
Analogue Outputs (*)
1Ao
0-10Vdc; Min load = 10k ohm
4-20mA; Max load = 500 ohm
A1+: V+ or I+
A1-: GND or I-
2Ao
0-10Vdc; Min load = 10k ohm
4-20mA; Max load = 500 ohm
A2+: V+ or I+
A2-: GND or I-
Freq
Frequency output; Supply max voltage = 5Vdc; Max supply current = 10mA; Duty
cycle = 50%; Range = 0 to 166 Hz; Maximum cable length = 2m
12: FREQ+
13: GND
Purpose of control
Operating control
Construction of control
Incorporated control, intended to be used in Class I equipment
Approvals
R290/R600a: relays tested according to IEC EN60079:0 and IEC EN60079:15
IEC/EN 60730-1; IEC/EN 60730-2-9
UL 60730-1; UL 60730-2-9
CAN/CSA-E60730-1; CAN/CSA-E60730-2-9
Tested according to the requirements of the relevant subclauses of IEC/EN 60335-2-89 in conjunction with IEC/EN 60335-1
(*) Depending on the specific model, some of these I/O could not be present.