background image

 

Min 

Current minute (0 ÷ 59min) 

dAY  Current day (Sun ÷ SAt) 

Hd1  First weekly holiday (Sun ÷ nu) Set the first day of the week which follows the holiday times. 

Hd2  Second weekly holiday (Sun ÷ nu) Set the second day of the week which follows the holiday 

times. 

N.B.   Hd1,Hd2 can be set also as “nu” value (Not Used).  
TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC) 
ILE 

Energy Saving cycle start during workdays: (0 ÷ 23h 50 min.) During the Energy Saving 

cycle the set point is increased by the value in HES so that the set point is SET + HES.  

dLE  Energy Saving cycle length during workdays: (0 ÷ 24h 00 min.) Sets the duration of the 

Energy Saving cycle on workdays.  

ISE 

Energy Saving cycle start on holidays. (0 ÷ 23h 50 min.) 

dSE  Energy Saving cycle length on holidays (0 ÷ 24h 00 min.) 
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC) 
Ld1÷Ld6 Workday defrost start
 (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles during workdays. Ex. When Ld2 = 12.4 the second defrost starts at 

12.40 during workdays.  

Sd1÷Sd6 Holiday defrost start  (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles on holidays. Ex. When Sd2 = 3.4 the second defrost starts at 3.40 

on holidays.  

N.B. :To disable a defrost cycle set it to “nu”(not used). Ex.  If Ld6=nu ;  the sixth defrost 

cycle is disabled 

OTHER 
Adr   Serial address
  (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc 

NTC probe. 

onF  on/off key enabling: nu = disabled; oFF = enabled; ES = not set it

dP1  Thermostat probe display 

dP2  Evaporator probe display 

dP3  Third probe displayoptional

rSE  Real set point:  it shows the set point used during the energy saving cycle or during the 

continuous cycle. 

rEL  Software release for internal use

Ptb  Parameter table code: readable only

8.

 

DIGITAL INPUT (ENABLED ONLY IF P3P = N) 

8.1

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “did” time delay before signalling the 

EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 

de-activated. 

8.2

 

SERIOUS ALARM MODE (i1F =  bAL) 

When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated. 

8.3

 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “did” parameter, the pressure switch has reached the number of 

activation of  the “nPS” parameter, the “CA” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always 

OFF. If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

8.4

 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the “odc” parameter: no, 

Fan = normal (any change); CPr, F_C = Compressor OFF. 

Since the door is opened, after the delay time set through parameter “did”, the door alarm is enabled, 

the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm stops as 

soon as the external digital input is disabled again. With the door open, the high and low temperature 

alarms are disabled. 

8.5

 

START DEFROST (i1F = dEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 

restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time 

is expired. 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F =Htr)  

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 

(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

HOLIDAY DEFROST (i1F = HDF) –ONLY FOR MODELS WITH RTC 

This function enabled the holiday defrost setting. 

8.9

 

ON OFF FUNCTION (i1F = onF)  

To switch the controller on and off. 

8.10

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “i1P parameter. 

i1P =CL: the input is activated by closing the contact. 

i1P =OP: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector,  allows by means of the external 

TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU 

compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY KEY 
connector. The X-REP output 

EXCLUDES 

 the serial connection.

 

 

To connect the X-REP to the 
instrument the following connectors 
must be used CAB-51F(1m), CAB-
52F(2m), CAB-55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

The controller XW20LS, shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two 

screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). 

The temperature range allowed for correct operation is 0 -  60 °C. Avoid places subject to strong 

vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 

Let the air circulate by the cooling holes. 

 

11.1

 

CUT OUT 

 

11.2

 

STEEL FINISHING MOUNTING  

1

1

2

2

3

3

4

4

RG-LX gascke

(optional)

 

12.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 

2,5 mm

for the digital and analogue inputs. Relays and power supply have a Faston connection 

(6,3mm). Heat-resistant cables have to be used. Before connecting cables make sure the power 

supply complies with the instrument’s requirements. Separate the probe cables from the power supply 

cables, from the outputs and the power connections. Do not exceed the maximum current allowed on 

each relay, in case of heavier loads use a suitable external relay. 

N.B. Maximum current allowed for all the loads is 20A. 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 

infiltration. It is recommended to place the thermostat probe away from air streams to correctly 

measure the average room temperature. Place the defrost termination probe among the evaporator 

fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 

defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “Hot key” and push 

o

 key; the  "uPL" message appears 

followed a by flashing “End” 

3.

 

Push “SET” key and the End will stop flashing. 

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 

NOTE: the “Err” message is displayed for failed programming. In this case push again 

o

 key if you 

want to restart the upload again or remove the “Hot key” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON. 

1592027320 XW20LS RTC GB r1.0 18.03.2015 

XW20LS 

3/5 

Содержание Dixell XW20LS

Страница 1: ...ameter EdF with EdF in the defrost is made every IdF time standard way for controller without RTC with EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld6 on workdays and in Sd1 Sd6 in holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P 4 FRONT PANEL COM...

Страница 2: ... percentage of visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled P4 NOT SET IT SET set point dtr percentage of visualization dLy Display delay 0 20 0m resul 10s when the temperature increases the display is updated of 1 C 1 F after this time dtr Per...

Страница 3: ...strument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F Htr This function allows to invert the regulation of the controller from cooling to heating and viceversa 8 7 ENERGY SAVING i1F ES The Energy Saving function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until the digital input i...

Страница 4: ...Vac connect to terminals 5 6 The X REP output is optional 17 DEFAULT SETTING VALUES Label Name Range C F Level Set Set point LS US 3 0 rtc Real time clock menu Pr1 Hy Differential 0 1 25 5 C 1 255 F 2 0 Pr1 LS Minimum set point 50 C SET 58 F SET 50 0 Pr2 US Maximum set point SET 110 C SET 230 F 110 Pr2 Ot Thermostat probe calibration 12 12 C 120 120 F 0 0 Pr1 P2P Evaporator probe presence n not pr...

Страница 5: ... Sd5 5th holiday defrost start 0 23h 50 min nu 0 0 rtc Sd6 6th holiday defrost start 0 23h 50 min nu 0 0 rtc Adr Serial address 1 247 1 Pr2 PbC Kind of probe Ptc ntc ntc Pr2 onF on off key enabling nu oFF ES oFF Pr2 dP1 Room probe display Pr2 dP2 Evaporator probe display Pr2 dP3 Third probe display Pr2 rSE Real set actual set Pr2 rEL Software release 1 8 Pr2 Ptb Map code Pr2 Only for model with re...

Отзывы: