Emerson Dixell XRi77CX Скачать руководство пользователя страница 6

 

1592020670 XRi77CX-CH GB r1.1 15.10.2019

 

XRi77CX-CH

 

6/9

 

14.5

 

SWITCH THE AUXILIARY RELAY (IXF = AUS) 

With 

oAx=AUS

 the digital input switched the status of the auxiliary relay. 

14.6

 

INVERSION OF THE KIND OF ACTION: HEATING-COOLING (IXF = HTR)  

This function allows inverting the regulation of the controller: from cooling to heating and viceversa. 

14.7

 

ENERGY SAVING (IXF = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the 

[SET+HES]

 

(parameter) sum. This function is enabled until the digital input is activated. 

14.8

 

ON OFF FUNCTION (IXF = ONF)  

To switch the controller on and off. 

14.9

 

CHANGE PARAMETER MAP (IXF = NT) 

To move from LT to NT parameter map. 

14.10

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the 

i1P

 and 

i2P 

parameters. 

 

i1P or i2P=CL

, the input is activated by closing the contact.

 

 

i1P or i2P=OP

, the input is activated by opening the contact. 

15.

 

RS485 SERIAL LINE 

 FOR MONITORING SYSTEMS 

The  RS485  serial  line  allows  connecting  the  instrument  to  a  monitoring  system  (

ModBUS-RTU

 

compatible). 

16.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XRi77CX-CH

 shall be mounted on vertical panel, in a 

29x71 mm hole, and fixed using the special bracket supplied. 
The temperature range allowed for correct operation is 0 to 60°C. 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive dirt or humidity. The same recommendations apply to 
probes. Let air circulate by the cooling holes. 

 

 

 

17.

 

ELECTRICAL CONNECTIONS 

The instrument is  provided  with screw terminal block  to connect cables  with a cross section  up to 

2.5mm2.  Before  connecting  cables  make  sure  the 

power  supply  complies  with  the  instrument’s

 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 

power connections. Do not exceed the maximum current allowed on each relay, in case of heavier 

loads use a suitable external relay. 

17.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. 
It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly  measure  the 
average  room  temperature.  Place  the  defrost  termination  probe  among  the  evaporator  fins  in  the 
coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to 
prevent premature defrost termination. 

18.

 

HOW TO USE THE HOT KEY 

To enable the HOT-KEY port (5-pin connector), set the par. 

oAn=n

.  

18.1

 

PROGRAM A HOT KEY FROM AN INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the 

HOT-KEY

  and push 

UP 

button; the 

uPL

 

message 

appears followed a by a flashing 

End

 label. 

3.

 

Push 

SET 

button and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument, remove the 

HOT-KEY

 and

 

then turn it ON again. 

 

NOTE

: the “

Err

” message 

appears in case of a failed programming operation. In this case push again 

button if you want to restart the upload again or remove the 

HOT-KEY

 to abort the operation. 

18.2

 

PROGRAM AN INSTRUMENT BY USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a 

pre-programmed 

HOT-KEY

 into the 5-PIN receptacle 

and then turn the Controller 

ON. 

3.

 

The  parameter  list  of  the 

HOT-KEY

  will  be  automatically  downloaded  into  the  Controller 

memory. T

he “

doL

” message 

will blink followed a by a flashing 

End

 label. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

HOT-KEY

 

NOTE: 

the message “Err” is displayed for failed programming. In this case turn the unit off and then 

on if you want to restart the download again or remove the 

HOT-KEY

 to abort the operation. 

19.

 

ALARM SIGNALS 

Message 

Cause 

Outputs 

P1 

Room probe failure 

Compressor output works with Con and CoF 

P2 

Evaporator probe failure 

Defrost end is timed 

P3 

Third probe failure 

Outputs unchanged 

P4 

Fourth probe failure 

Outputs unchanged 

HA 

Maximum temperature alarm 

Outputs unchanged 

LA 

Minimum temperature alarm 

Outputs unchanged 

HA2 

Condenser high temperature 

It depends on the AC2 parameter 

Message 

Cause 

Outputs 

LA2 

Condenser low temperature 

It depends on the bLL parameter 

dA 

Door open 

Compressor restarts  

EA 

External alarm 

Output unchanged 

CA 

Serious external alarm (ixF=bAL) 

All outputs OFF 

rtC 

Real time clock parameter error 

Output unchanged, defrost follows idF, need to 
set RTC parameters 

rtF 

Real time clock malfunctioning 

Output unchanged, defrost follows idF 

19.1

 

BUZZER MUTING OR ALARM RELAY OUTPUT DEACTIVATION 

If 

tbA=Y

, the buzzer and the relay are silenced by pressing any key.  

If 

tbA=n

, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers. 

19.2

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P2

”, “

P3

” and “

P4

” 

start some seconds after the fault in the related probe; they 

automatically stop some seconds after the probe restarts normal operation. Check connections before 
replacing the probe. 

Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the temperature returns to normal 

values. 
Alarms 

EA

 and 

CA

 

(with 

i1F=bAL

)

 

recover as soon as the digital input is disabled. 

19.3

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode: no parameter in Pr1. 
On the display or in dP2, dP3, dP4: the selected probe is not enabled. 

20.

 

TECHNICAL DATA 

Housing: 

self-extinguishing ABS

 

Case: 

frontal 32x74mm; depth 60mm 

Mounting: 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20 

Frontal protection: 

IP65 

Connections: 

Screw terminal block 

 2.5 mm

2

 wiring 

Power supply:

 (according to the model) 230Vac 

10%, 50/60Hz; 110Vac 

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display:

  

-

 

3 digits, red LEDs, 14.2 mm high (CX format) 

-

 

3 digits, red LEDs, 19 mm high (CH format) 

Inputs:

 Up to 4 NTC, PTC or PT1000 probes

 

Digital inputs: 

 free voltage contact 

Frequency output:

 30 to 200 Hz, 14Vdc MAX, duty cycle=50% 

Relay outputs (nominal ratings):  

-

 

oA1: 

SPST 16(5)A 250Vac

 

-

 

oA2: 

SPDT 8(3)A, 250Vac 

-

 

oA3: 

SPST 5(2)A, 250Vac 

-

 

oA4: 

SPST 8(3)A 250Vac 

Data storing:

 on the non-volatile memory (EEPROM) 

Internal clock back-up:

 24 hours 

Kind of action: 

1B 

Pollution degree: 

2  

Software class: 

Rated impulsive voltage:

 2500V; 

Overvoltage Category:

 II 

Operating temperature: 

0 to 55°C (32 to 131°F) 

Storage temperature: 

-30 to 85°C (-22 to 185°F) 

Relative humidity:

 20 to 85% (no condensing) 

Measuring and regulation range: 

-

 

NTC probe: 

-40 to 110°C (-40 to 230°F) 

-

 

PTC probe:

 -50 to 150°C (-55 to 302°F) 

-

 

PT1000 probe:

 -100 to 150°C (-148 to 392°F) 

Resolution: 

0.1°C or 1°C or 1°F (selectable) 

Accuracy (ambient temp. 25°C):

  ±0.7°C ±1 digit 

21.

 

WIRINGS 

 

 

Содержание Dixell XRi77CX

Страница 1: ...t RTC EdF rtC the defrost is real time controlled depending on the hours set in the parameters Ld1 Ld6 for workdays Other parameters are used to control defrosting cycles the maximum length MdF and defrosting modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PR...

Страница 2: ... to set the regulation HY1 Differential for proportional regulation 0 1 to 25 5 C 1 to 45 F Fr0 Frequency output value with compressor stopped 0 to 50Hz frequency output signal when compressor stopped PMi Minimum compressor speed in percentage 0 to PMA PMA Maximum compressor speed in percentage PMi to 100 voS Signal output variation increment when temperature is increasing if vdC FrE then 1 to 100...

Страница 3: ...g mode by pressing the SET DOWN buttons for 3 sec the C or F LED will start blinking 2 Browse to the required parameter and then press the SET button to display its current value 3 Use UP or DOWN buttons to change its value 4 Press SET button to store the new value and move to the following parameter To exit press SET UP buttons or wait for 15 sec without pressing any key NOTE the set value is sto...

Страница 4: ... idF is expired tdF Defrost type EL in EL electrical heater in hot gas dFP Probe selection for defrost control nP P1 P2 P3 P4 nP no probe P1 thermostat probe P2 evaporator probe P3 configurable probe P4 Probe on Hot Key plug dtE Defrost end temperature 55 to 50 C 67 to 122 F enabled only when EdF Pb sets the temperature measured by the evaporator probe which causes the end of defrost idF Interval ...

Страница 5: ... condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation d2d Digital input 2 alarm delay 0 to 255 min delay between the detection of the external alarm condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation nPS Number of pressure alarm events before stopping the re...

Страница 6: ... and then turn the Controller ON 3 The parameter list of the HOT KEY will be automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you wa...

Страница 7: ...ion for defrost control P2 Pr2 dtE Defrost termination temperature 4 0 Pr2 idF Interval between two consecutives defrost cycles 24 Pr2 MdF Maximum length for defrost 45 Pr2 dSd Start defrost delay 0 Pr2 StC Compressor stop time before starting any defrost 5 Pr2 dFd Displaying during defrost it Pr1 dAd Delay for display temperature update after any defrost 20 Pr1 Fdt Draining time 5 Pr2 Hon Drain h...

Страница 8: ...in percentage 100 Pr2 voS_nt Compressor speed variation increment when temperature is increasing 1 Pr2 vo2_nt Compressor speed variation decrement when temperature is decreasing 2 Pr2 vo3_nt Compressor speed variation decrement after any Pull Down 5 Pr2 PdP_nt Compressor speed during any Pull Down 100 Pr2 t1F_nt Time with compressor speed at PMI before stopping the compressor 1 Pr2 SPi_nt Compress...

Страница 9: ...arity CL Pr2 i2F_nt Digital input 2 configuration EAL Pr2 did_nt Digital inputs 1 alarm delay 1 Pr1 d2d_nt Digital inputs 2 alarm delay 1 Pr2 nPS_nt Number of pressure alarm switch before stopping the regulation Lock alarm 15 Pr1 OdC_nt Compressor and fan status after door opening F C Pr1 rrd_nt Regulation restart after open door alarm yes Pr1 HES_nt Differential for energy saving mode 0 Pr1 LdE_n...

Отзывы: