Emerson Dixell XRi77CX Скачать руководство пользователя страница 2

 

1592020670 XRi77CX-CH GB r1.1 15.10.2019

 

XRi77CX-CH

 

2/9

 

3.4.10

 

REGULATION OUTPUT 

If 

oAx=inV

,  the  related  output  will  work  as  regulation  output  and  will  stay  active  as  soon  as  the 

regulation request is running. 

4.

 

PULL DOWN 

An automatic function named PULL-DOWN is implemented. This function forces the controller to work 
at 

PMA

 until reaching a specific SETPOINT (par. 

CCS

) for a maximum interval of time (par. 

CCt

). The 

PULL-DOWN function is activated: 
At start-up if the temperature measured from the regulation probe is higher than the SETPOINT 
After any defrost 
If the temperature measured from regulation probe go over the 

SET+HY+HY1+oHt

 value. 

If one of the above conditions happens, the controller will maintain the maximum compressor speed 
(

PMA

) until reaching the 

CCS

 setpoint. The maximum interval of time for any PULLDOWN is defined 

from par. 

CCt

5.

 

EVAPORATOR FAN CONTROL 

The evaporator fan control mode is selected by means of the 

FnC

 parameter: 

-

 

FnC = C_n:

 fans will switch ON and OFF with the compressor and

 not run

 during defrost 

-

 

FnC = o_n: 

fans will run even if the compressor is off, and not run during defrost 

 
After defrost, there is a timed fan delay allowing for drip time, set by means of the 

Fnd

 parameter. 

-

 

FnC = C_Y:

  fans will switch ON and OFF with the compressor and 

run

 during defrost 

-

 

FnC = o_Y: 

fans will run continuously also during defrost 

 
The par. 

FAP

 is used to select which temperature probe will be used from the evaporator fan regulator. 

A specific setpoint (par. 

FSt

) provides the temperature value, detected by the evaporator probe, above 

which the fans are always OFF. This is used to make sure circulation of air only if his temperature is 
lower than set in 

FSt-HYF

5.1

 

FORCED ACTIVATION FOR FANS 

This function, managed by the 

FCt

 parameter, is designed to avoid short cycles of fans, that could 

happen when the controller is switched on or after a defrost, when the room air warms the evaporator.  
If the difference between the evaporator temperature and the room temperature is higher than the 

FCt

 

value, the controller will activate the fans. This function is disabled if 

FCt=0

5.2

 

CYCLIC ACTIVATION OF THE FANS WHEN THE COMPRESSOR IS 

SWITCHED OFF 

When 

FnC=C-n

 or 

C-Y

 (fans in parallel to the compressor), the fans will be able to carry out on and 

off cycles even if the compressor is switched off. The on and off interval of time follow the 

Fon

 and 

FoF

 parameters. When the compressor is stopped, the fans will go on working for the 

Fon

 time. On 

the other side, with 

Fon=0

 the fans will stay always off when the compressor is off. 

6.

 

CONDENSER FAN CONTROL 

The condenser fan control mode is selected by means of the 

FCC

 parameter: 

-

 

FCC = C_n:

 fans will switch ON and OFF with the compressor and

 not run

 during defrost 

-

 

FCC = o_n: 

fans will run even if the compressor is off, and not run during defrost 

-

 

FCC = C_Y: 

fans will switch ON and OFF with the compressor and 

run

 during defrost 

-

 

FCC = o_Y: 

fans will run continuously also during defrost 

 
The par. 

FAC

 is used to select which temperature probe will be used from the condenser fan regulator. 

This regulator uses a specific setpoint (par. 

St2

) and differential (par. 

HY2

) to activate and deactivate 

the condenser fans:  

-

 

If 

T>St2+HY2

 the condenser fans are activated 

-

 

If 

T<St2

 the condenser fans are deactivated 

 
The par. 

FCo

 can be used to keep the ventilators active for a period after compressor OFF. 

7.

 

AUXILIARY REGULATOR 

The auxiliary regulator can be be linked to a digital output (relay) for ONOFF regulation. 
The parameters used to configure the auxiliary regulators are the following: 

 

ACH 

Kind of action for auxiliary regulator 

SAA 

Set point for auxiliary regulator 

SHY 

Differential for auxiliary regulator 

ArP 

Probe selection for auxiliary regulator 

Sdd 

Auxiliary regulator disabled during any defrost 

8.

 

DUAL MAP FEATURE 

The controller is programmed with 2 different parameter maps. In this way, it is possible to choose the 
right map to meet both LT and NT applications. There are two different way to do this: 

-

 

If 

i1F=nt

, it will be possible to change the working map by using the digital input. 

-

 

By using the 

DOWN

 button, if it is linked to the map changing function. If so, keep it pressed 3 

sec to activate the relative function. 

9.

 

VARIABLE SPEED COMPRESSOR CONTROL 

9.1

 

FREQUENCY MODE 

The  controller  can  drive  variable  speed  compressors  with  frequency  control  input.  The  frequency 
output port can issue a frequency signal from 30 to 200Hz, duty cycle=50%. A special cable must be 
used in order to connect the frequency output of the controller to the frequency input of the specific 

inverter. 
 

-

 

CAB/EM1: cable 

DD900002 20

 for Embraco VNEK/U models 

-

 

CAB/SE1: cable 

DD900002 22

 for SECOP NLV models 

 

NOTE:

  

-

 

An inverter compressor can be completely controlled from the frequency output only. 

-

 

Only one compressor can be connected when frequency mode is used 

9.2

 

PARAMETERS 

The following parameters are used to set the regulation: 
 

HY1 

Differential for proportional regulation:

 (0.1 to 25.5°C; 1 to 45°F)

 

Fr0 

Frequency output value with compressor stopped:

 (0 to 50Hz) frequency output 

signal when compressor stopped 

PMi 

Minimum compressor speed (in percentage): 

(0 to PMA) 

PMA 

Maximum compressor speed (in percentage):

 (PMi to 100%) 

voS 

Signal output variation (increment) when temperature is increasing:

 if 

vdC=FrE 

then 1 to 100 Hz, otherwise 10 to 1000 rpm 

vo2 

Signal output variation (decrement) when temperature is decreasing:

 if 

vdC=FrE 

then 1 to 100 Hz, otherwise 10 to 1000 rpm 

vo3 

Signal output variation (decrement) after any Pull Down:

 if 

vdC=FrE 

then 1 to 100 

Hz, otherwise 10 to 1000 rpm 

t1F 

Time with compressor at PMI before stopping regulation:

 (0 to 999 min) 

SPi 

Compressor speed (in percentage) in case of any error probe:

 (PMi to PMA) 

CMn 

Continuous mode during Normal Mode:

 (n; Y) 

CME 

Continuous mode during Energy Saving Mode:

 (n; Y)

 

 
The value of the par 

HY1

 can normally be set to the same value of par. 

HY

. In this way, the regulation 

band will be extended from 

SET

 to 

SET+HY+HY1

. The device will activate the regulation when the 

measured  temperature  will  go  over  the 

SET+HY

  value  and  will  stop  the  regulation  when  the 

temperature will reach the 

SET

 value. When the regulation is running, the frequency output, and then 

the  compressor  speed,  will  be  calculated  in  proportional  way  by  using  the 

PM

i…PMA

  band.  After 

reaching the 

SET+HY

 value, the controller  will start increasing the frequency  output,  and  then the 

equivalent compressor speed, by using the par. 

voS

. The speed increasing will be stopped as soon 

as the proportional calculated value (for the compressor speed) hooks the requested value. In case of 
temperature decrement and compressor speed higher than the new requested value, the controller will 
decrease the compressor speed proportionally by using the 

vo2

 value. After any Pull Down, and in 

case of continuous mode regulation (

CMn

 or 

CME=Y

) it is possible to speed up the compressor speed 

decrement by using par. 

vo3

. This helps to avoid subfreezing conditions due to high compressor speed 

after reaching the regulation setpoint. 
After reaching the 

SET

 value it is possible to force the compressor speed to 

Pmi

 for 

t1F

 min. 

In case of any regulation probe error, the compressor speed will be set to the value of par. 

SPi

It is possible to enable a cyclic or a continuous mode operation both during normal mode or energy 
saving mode: 

-

 

CMn, CME = Y

: after reaching the SETPOINT the VSC will keep on running 

-

 

CMn, CME = n

: after reaching the SETPOINT the VSC will be stopped (after 

t1F

9.3

 

TEMPERATURE DEADLOCK CONTROL 

The  controller  can  detect  temperature  deadlocks.  If  the  actual  speed  is  not  able  to  reach  the 
SETPOINT, and if this condition persists for a long interval of time, then the controller will increment 
the actual speed until reaching the SETPOINT. A differential (par. 

th1

) and a speed increment (par. 

oFS

) is used to detect and manage any deadlock condition. 

9.4

 

HOT GAS DEFROST 

In case of using hot-gas defrost, it will be possible to set the compressor speed by using par. 

Aod

9.5

 

PULL DOWN 

An automatic function named PULL DOWN is implemented. This function forces the controller to work 
at 

PMA

 until reaching a specific SETPOINT (par. 

CCS

) for a maximum interval of time (par. 

CCt

). The 

PULL-DOWN function is activated: 

-

 

At  start-up  if  the  temperature  measured  from  the  regulation  probe  is  higher  than  the 

SET+HY+HY1

 

-

 

After any defrost 

-

 

If the temperature measured from regulation probe go over the 

SET+HY+HY1+oHt

 value. 

If one of the above conditions happens, the controller will maintain the maximum compressor speed 
(

PMA

) until reaching the 

CCS

 setpoint. The maximum interval of time for any PULLDOWN is defined 

from par. 

CCt

. At the end of any PULL DOWN it is possible to set an interval of time (par. 

t1F

) with 

predefined compressor speed (

PMi

). 

9.6

 

OIL MIGRATION CONTROL (VALID ONLY FOR VSC) 

To  avoid  oil  migration  during  variable  speed  compressor  operation,  a  lubrication  control  is 
implemented. If the compressor works with a speed lower than the 

MnP

 threshold for 

tMi

 time, then 

the compressor speed will be increased to 

PMA

 for 

tMA

 time. 

NOTES: 

-

 

MnP= PMi to PMA, nu, OFF 

-

 

If 

MnP=nu

, then this function is disabled 

 
If 

MnP=oFF

, then the compressor will be stopped for 

tMA

 if it works continuously for 

tMi 

9.7

 

STEP REGULATION: VSD AND ONOFF COMPRESSOR 

The following parameters are used to set up the step regulation function: 
 

Pon 

Step regulation: inverter compressor speed during ton (in percentage) 

SCd 

Step regulation: deactivation of the ONOFF compressor 

ton 

Step regulation: delay before activation of the second compressor (when T> SET + HY + HY1) 

toF 

Step regulation: delay before deactivation of the second compressor 

don 

Step regulation: minimum operating time of the second compressor 

doF 

Step regulation: minimum stop time of the second compressor 

 
The step regulation is activated when at least one ONOFF compressor is enabled (

oAx=CP1

 or 

CP2

and 

oAn=FrE

The second compressor (the ONOFF one) will be activated when T > SET+HY+HY1. 

The ONOFF compressor deactivation follows par. 

SCd

Содержание Dixell XRi77CX

Страница 1: ...t RTC EdF rtC the defrost is real time controlled depending on the hours set in the parameters Ld1 Ld6 for workdays Other parameters are used to control defrosting cycles the maximum length MdF and defrosting modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PR...

Страница 2: ... to set the regulation HY1 Differential for proportional regulation 0 1 to 25 5 C 1 to 45 F Fr0 Frequency output value with compressor stopped 0 to 50Hz frequency output signal when compressor stopped PMi Minimum compressor speed in percentage 0 to PMA PMA Maximum compressor speed in percentage PMi to 100 voS Signal output variation increment when temperature is increasing if vdC FrE then 1 to 100...

Страница 3: ...g mode by pressing the SET DOWN buttons for 3 sec the C or F LED will start blinking 2 Browse to the required parameter and then press the SET button to display its current value 3 Use UP or DOWN buttons to change its value 4 Press SET button to store the new value and move to the following parameter To exit press SET UP buttons or wait for 15 sec without pressing any key NOTE the set value is sto...

Страница 4: ... idF is expired tdF Defrost type EL in EL electrical heater in hot gas dFP Probe selection for defrost control nP P1 P2 P3 P4 nP no probe P1 thermostat probe P2 evaporator probe P3 configurable probe P4 Probe on Hot Key plug dtE Defrost end temperature 55 to 50 C 67 to 122 F enabled only when EdF Pb sets the temperature measured by the evaporator probe which causes the end of defrost idF Interval ...

Страница 5: ... condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation d2d Digital input 2 alarm delay 0 to 255 min delay between the detection of the external alarm condition and its signalling When i1F PAL it is the interval of time to calculate the number of pressure switch activation nPS Number of pressure alarm events before stopping the re...

Страница 6: ... and then turn the Controller ON 3 The parameter list of the HOT KEY will be automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you wa...

Страница 7: ...ion for defrost control P2 Pr2 dtE Defrost termination temperature 4 0 Pr2 idF Interval between two consecutives defrost cycles 24 Pr2 MdF Maximum length for defrost 45 Pr2 dSd Start defrost delay 0 Pr2 StC Compressor stop time before starting any defrost 5 Pr2 dFd Displaying during defrost it Pr1 dAd Delay for display temperature update after any defrost 20 Pr1 Fdt Draining time 5 Pr2 Hon Drain h...

Страница 8: ...in percentage 100 Pr2 voS_nt Compressor speed variation increment when temperature is increasing 1 Pr2 vo2_nt Compressor speed variation decrement when temperature is decreasing 2 Pr2 vo3_nt Compressor speed variation decrement after any Pull Down 5 Pr2 PdP_nt Compressor speed during any Pull Down 100 Pr2 t1F_nt Time with compressor speed at PMI before stopping the compressor 1 Pr2 SPi_nt Compress...

Страница 9: ...arity CL Pr2 i2F_nt Digital input 2 configuration EAL Pr2 did_nt Digital inputs 1 alarm delay 1 Pr1 d2d_nt Digital inputs 2 alarm delay 1 Pr2 nPS_nt Number of pressure alarm switch before stopping the regulation Lock alarm 15 Pr1 OdC_nt Compressor and fan status after door opening F C Pr1 rrd_nt Regulation restart after open door alarm yes Pr1 HES_nt Differential for energy saving mode 0 Pr1 LdE_n...

Отзывы: