1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15
XRB
13/38
i1F
Digital input 1 configuration:
•
nu
=not used
•
dor
= door switch function
•
dEF
= defrost activation
•
AUS
= auxiliary output
•
ES
= energy saving mode activation
•
EAL
= external warning alarm
•
bAL
= external lock alarm
•
PAL
= external pressure alarm
•
FAn
= evaporator fan control
•
HdF
= holiday defrost
•
onF
= ON/OFF status change
•
LiG
= light output control
•
Lnt
= change configuration (between map LT and map NT)
d1d
Digital inputs 1 alarm delay:
(0 to 255 min) delay between the detection of an external event
and the activation of the relative function.
i2P
Digital input 2 polarity:
(CL; oP)
oP
= activated by closing the contact;
CL
= activated by
opening the contact.
i2F
Digital input 2 configuration:
•
nu
=not used
•
dor
= door switch function
•
dEF
= defrost activation
•
AUS
= auxiliary output
•
ES
= energy saving mode activation
•
EAL
= external warning alarm
•
bAL
= external lock alarm
•
PAL
= external pressure alarm
•
FAn
= evaporator fan control
•
HdF
= holiday defrost
•
onF
= ON/OFF status change
•
LiG
= light output control
•
Lnt
= change configuration (between map LT and map NT)
•
EMt
= Motion sensor
d2d
Digital inputs 2 alarm delay:
(0 to 255 min) delay between the detection of an external event
and the activation of the relative function.
nPS
Number of external pressure switch alarms before stopping the regulation:
(0 to 15) after
reaching nPS events in the digital input alarm delay (par. dxd), the regulation will be stopped and
a manual restart (ON/OFF, power OFF and power ON) will be required.
odC
Compressor and fan status after door opening:
(no; FAn; CPr; F-C):
no
= normal;
FAn
= Fans OFF;
CPr
= Compressor OFF;
F-C
= Compressor and fans OFF.
rrd
Regulation restart after door alarm:
(n; Y)
n
= no regulation if the door is open;
Y
= when the
rrd timer elapses, the regulation restarts even if a door open alarm is ON.
CLi
Light output activation from door input:
(n; Y)
LCi
Time with light output forced ON:
(0 to 255 min) set how much time the light outputs will stay
on after door input activation (
ixF=dor
). 0 = function disabled.
n01
Number of motion detections before activating light output (valid if ixF=EMt):
(0 to 10) set
how many detections from motion sensor will activate light outputs
t01
Time with light output forced ON after motion detection:
(0 to 255 min) set how much time
light outputs will stay on after motion detection activation.
MSF
Function linked with the motion sensor:
(nu; LiG; ES; ALL)
-
nu
= not used
-
LiG
= motion sensor can modify only light outputs
-
ES
= motion sensor can modify only energy saving status
-
ALL
= motion sensor can modify both light outputs and energy saving status
EMF
Motion sensor stop reading interval:
(0 to 255 min) after switching off the light output by button,
serial command or energy saving algorithm the motion sensor will be inhibited for this interval
(valid if
ixF=EMt
)