1592034020 XR77CHC EN r1.0 2019.01.31 

                           XR77CHC 

3/7 

 

11.3

 

START A MANUAL DEFROST 

Push the 

DEFROST

 button for more than 3 sec to start a manual defrost. 

12

 

PARAMETER MENU 

The device has a parameter menu available from keyboard and where it is possible to modify some specific 
parameters. A couple of parameter levels are present: 

-

 

PR1: user menu, standard parameters are placed into this menu 

-

 

PR2:  protected  menu,  application  specific  parameters  are  placed  here.  A  password  can  be 
used to protect these values from unauthorized modification. 

12.1

 

MENU NAVIGATION 

A tree-structured menu is implemented to simplify the parameter browsing and modification. Follow the button 
functions (valid both in PR1 and PR2): 

-

 

SET

: used to enter a submenu or a stored value 

-

 

UP

 and 

DOWN

: used to scroll the menu labels, the parameters into a submenu and to modify a 

parameter value 

-

 

AUX/DEF

:  used  to  go  back  to  the  upper  menu  level  (for  example,  from  a  submenu  list  of 

parameters to the main menu labels) 

12.2

 

CHANGE A PARAMETER VALUE 

To change a parameter value, operate as follows:  
1.

 

Enter  the  Programming  mode  by  pressing  the 

SET+DOWN

  buttons  for  3  sec 

(“

°C

 

LED  starts 

blinking). 

2.

 

Select the required parameter. Press the 

SET

 button to display its value 

3.

 

Use 

UP

 or 

DOWN 

buttons to change its value. 

4.

 

Press 

SET

 to store the new value and move to the following parameter. 

 

To exit:

 Press 

SET+UP 

buttons or waits for 15 sec without pressing any button. 

 

NOTE:

 The modified value will be stored even if the programming mode ends by timeout. 

12.3

 

PROTECTED LEVEL 

The Protected Level has all the parameters of the instrument. This level is password protected. The 

default password is: “000”. It is strongly recommend

ed to change the standard password after ending 

the installing operations. 

12.3.1

 

ENTER THE PROTECTED LEVEL 

1.

 

Enter  the  Programming  mode  by  pressing 

SET+DOWN

  buttons  for  3  sec  (

°C 

or 

°F

  LED  starts 

blinking) 

2.

 

Released the buttons and then search for submenu 

Pr2

 

3.

 

Per SET button and then insert the password value 

4.

 

Confirm  with  SET.  If  the  password  is  correct,  the 

label  “Pr2”  will  blink  for  some  time  and  then

 

protected parameter menu will be enabled. 

12.3.2

 

PROTECTED MENU 

1.

 

Select the parameter to modify 

5.

 

Press the 

SET

 key to display its current value 

6.

 

Use 

UP

 or 

DOWN

 to change its value 

7.

 

Press 

SET

 to store the new value and move to the following parameter 

 

To exit

: Press 

SET+

UP

 or wait for 15 sec without pressing any button. 

 

NOTE:  

1.

 

If there are no parameters into the User Level, after 3 sec 

the “nP” 

label will be displayed. Go to 

submenu Pr2 and follow the previous procedure. 

2.

 

The modified value will be stored even if the programming mode ends by timeout. 

3.

 

Modify the par. 

PSU

 (when into Protected Level) to change the current password 

12.3.3

 

MOVE PARAMETERS THROUGH LEVELS 

Each parameter present into the Protected Level can be moved into the User Level by pressing both 

SET+DOWN 

buttons. If a parameter is into the User Level, when visualized into the Protected Level it 

will have also the decimal point. 

12.4

 

KEYBOARD MANAGEMENT 

12.4.1

 

TEMPORARY LOCK 

1.

 

Keep both 

UP 

and 

DOWN 

buttons pressed for more than 3 sec. 

2.

 

The “

oFF

” label

 will be displayed and the keyboard will be locked. If any button is pressed more 

than 3 sec, 

the “

oFF

” message will be displayed.

 

12.4.2

 

TEMPORARY UNLOCK 

Keep both 

UP 

and 

DOWN 

buttons pressed together for more than 3 sec till the 

“on”

 

message will be 

displayed. 

12.4.3

 

ADVANCED LOCK FUNCTION 

It is possible to selectively lock the keyboard by using the following parameters: 
1.

 

brd

: select the kind of lock: 

a.

 

UnL

: all buttons unlocked 

b.

 

SEL

: buttons 

UP

DOWN

 and 

DEFROST

 are locked 

c.

 

ALL

: all keyboard is locked 

2.

 

tLC

: delay after power-on before activating the advanced lock function 

 

NOTE

: when advanced lock function is active, temporary lock and unlock functions are disabled. 

12.5

 

THE ON/OFF FUNCTION 

 

 

If 

onF = oFF

, the instrument will be switched off by pushing the 

ON/OFF

 button. The 

OFF

 

message  will  appear  on  the  display.  In  this  configuration  the  regulation  is 

disabled. To switch the instrument on, push again the 

ON/OFF

 button. 

 
WARNING: any load connected to the normally closed contacts of the relays is always supplied 
from the main voltage, even if the instrument is in standby mode.

 

13

 

PARAMETERS 

MENU LIST 

rEG 

Regulation: it includes all parameters related to main temperature regulation 

Prb 

Probe setup: it includes all parameters related to probe configuration 

diS 

Display: it includes all parameters related to the user interface 

dEF 

Defrost: it includes all parameters to control any defrost operation 

FAn 

Ventilators: it includes all parameters to control the ventilators 

AUS 

Auxiliary: it includes all parameters for auxiliary regulators 

ALr 

Alarms: it includes all parameters to set up the alarm conditions 

oUt 

Outputs: it includes all parameters to set up the digital outputs 

inP 

Inputs: it includes all parameters to set up the digital inputs 

ES 

Energy Saving: it includes all parameters to define the energy saving mode 

Cnt 

Counters: to see the counters values 

rtC 

Real Time Clock: it includes all parameters to set up the internal clock 

bLE 

Bluetooth: it includes all parameters to set up the Bluetooth communication 

E2 

EEPROM: it includes all parameters to set up the datalogger 

oth 

Other: it includes all parameters to set up the serial communication and the keyboard  

viS 

Visualization: it includes the read only parameters (probe values and FW info) 

REGULATION - rEG 

SEt 

Regulation Set Point: 

range from LS to US 

LS 

Minimum Set Point:

 (-100.0°C to SET; -148°F to SET) sets the minimum value for  the  set 

point. 

US 

Maximum Set Point:

 (SET to 200.0°C; SET to 392°F) set the maximum value for set point. 

HY 

Differential in normal mode:

 (0.1 to 25.0°C; 1 to 45°F) differential for set point. Compressor 

Cut-IN is 

T > SET + HY

. Compressor Cut-OUT is 

T<=SET

HYE 

Differential  in  energy  saving  mode:

  (0.1  to  25.0°C;  1  to  45°F)  differential  for  set  point. 

Compressor Cut-IN is 

T > SET + HES + HYE

. Compressor Cut-OUT is 

T<= SET + HES

odS 

Outputs  delay  activation  after  power  on:

 (0  to  255  min)  this  function  is  enabled  after  the 

power-on of the instrument and delays output activations. 

AC 

Anti-short cycle delay:

 (0 to 50 min) minimum interval between a compressor stop and the 

following restart. 

AC1 

Second compressor anti-short-cycle delay:

 (0 to 255 sec) delay  before activating second 

compressor, depending on regulation mode selected by par. 

2CC

 

2CC 

Activation  mode  for  second  compressor  (valid  if  oAx=CP1  and  oAy=CP2):

  (FUL;  HAF) 

FUL

=second compressor activated in parallel with first one. 

HAF

=second compressor activated 

with step logic. 

rCC 

Compressors rotation enabled: 

(n;Y) 

n

 = CP1 is always the first compressor activated. 

Y

 = 

CP1 and CP2 activation is alternated 

MCo 

Maximum  time  with  compressor  active: 

(0  to  255min)  maximum  time  with  ONOFF 

compressor active. With 

MCo=0

 this function is disabled. 

rtr 

Percentage for regulation: 

100=P1 only; 0=P2 only

 

CCt 

Maximum duration for pull down:

 (0.0 to 23h50min, res. 10min) after elapsing this interval of 

time the super cooling function is immediately stopped 

CCS 

Differential for pull down:

 (-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the 

regulation  SETPOINT  is  moved  to 

SET+CCS 

(in  normal  mode)  or  to 

SET+HES+CCS

  (in 

energy saving mode)

 

oHt 

Overheating  before  activating  the  pull-down  function  (when  in  normal  mode): 

(1.0  to 

12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function. 

oHE 

Overheating before activating the pull-down function (when in energy saving mode): 

(1.0 

to  12.0°C;  1  to  21°F)  this  is  the  upper  threshold  limit  used  to  activate  the  super  cooling 
function. 

Con 

Compressor ON time with faulty probe:

 (0 to 255 min) time during which the compressor is 

active in case of faulty thermostat probe. With 

CY=0

 compressor is always OFF. 

CoF 

Compressor OFF time with faulty probe:

 (0 to 255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With 

Cn=0

 compressor is always active. 

HY1 

Differential for proportional regulation: 

(0.1 to 25.5°C; 1 to 45°F) differential for proportional 

regulation band. It is used when 

 

PROBE SETUP - Prb 

PbC 

Probe selection:

 ntC; PtC; Pt1000 

ot 

Probe P1 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the 

first probe. 

P2P 

Evaporator probe presence:

 

n

 = not present; 

Y

 = the defrost stops by temperature. 

oE 

Evaporator  probe  calibration:

  -12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust  any  possible 

offset of the third probe. 

P3P 

Third probe presence:

 

n

 = not present; 

Y

 = the defrost stops by temperature. 

o3 

Third probe calibration:

 -12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of 

the third probe. 

P4P 

Fourth probe presence:

 

n

 = not present; 

Y

 = the condenser temperature alarm is managed. 

o4 

Fourth probe calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of 

the condenser probe. 

DISPLAY - diS 

iCo 

Enabling icon visualisation:

 (n; Y) the icons can be hidden during normal functioning

 

CF 

Temperature measurement unit: 

(°C; °F) 

°C 

= Celsius; 

°F

 = Fahrenheit. 

rES 

Resolution (only for °C):

 (dE; in) 

dE

 = decimal; 

in

 = integer. 

Lod 

Probe displayed: 

(

P1; P2; P3; P4; SEt; dtr; USr

Px

=probe “x”; 

SEt

=set point; 

dtr

=do not 

use it; 

USr

=do not use it. 

dLY 

Temperature  visualization  delay:

  (0.0  to  20min00sec,  res.  10  sec)  when  the  temperature 

increases, the display is updated of 1°C or 1°F after this time. 

dtr 

Visualization percentage = F(P1;P2): 

(0 to 100)

 

with 

dtr=1

 the display will show this value 

VALUE=0.01*P1+0.99*P2 

DEFROST - dEF 

EdF 

Defrost mode:

 

in

=fixed intervals; 

rtC

=following real time clock 

 

tdF 

Defrost type: EL

=electrical heaters; 

in

=hot gas; 

ALt

=uses only for compressor stop defrost. 

dFP 

Probe  selection  for  defrost  control:

 

nP

=no  probe; 

P1

=thermostat  probe; 

P2

=evaporator 

probe; 

P3

=third probe (do not use it); 

P4

=Probe on Hot Key plug. 

dtE 

Defrost termination temperature for defrost control:

 (-55 to 50°C; -67 to 122°F) it sets the 

temperature measured by the evaporator probe (

dFP

), which causes the end of defrost.

 

idF 

Interval  between  two  consecutives  defrost  cycles:

  (0  to  255  hours)  determines  the  time 

interval between the beginnings of two defrosting cycles. 

MdF 

Maximum length for defrost:

 (0 to 255 min; 0 means no defrost) when 

P2P=n

 (no evaporator 

probe presence) it sets the defrost duration, when 

P2P=Y

 (defrost end based on  evaporator 

temperature) it sets the maximum length for defrost. 

dSd 

Start defrost delay: 

(0 to 255 min) delay in defrost activation.

 

Содержание DIXELL XR77CHC

Страница 1: ... is possible to enable the compressor rotation function the activation of the first and the second compressor will be alternated to equalize the number of working hours of both In case of hot gas defrost operation it is possible to select if one or both compressors will be used 5 ENERGY SAVING ALGORITHM 5 1 DESCRIPTION The device permits to set different temperature to be used during normal and re...

Страница 2: ... CONFIGURABLE OUTPUT 10 1 1 LIGHT OUTPUT With oAx LiG the relay operates as light output 10 1 2 DIGITAL OUTPUT ACTIVATION The auxiliary output can be managed by digital inputs oAx AUS i1F or i2F AUS with oAx AUS and i1F i2F AUS the output is switched on and off following the linked digital input status 10 1 3 AUXILIARY THERMOSTAT The auxiliary regulator can be used to manage the auxiliary output H...

Страница 3: ... to set up the internal clock bLE Bluetooth it includes all parameters to set up the Bluetooth communication E2 EEPROM it includes all parameters to set up the datalogger oth Other it includes all parameters to set up the serial communication and the keyboard viS Visualization it includes the read only parameters probe values and FW info REGULATION rEG SEt Regulation Set Point range from LS to US ...

Страница 4: ...temperature alarm recovery 0 1 to 25 0 C 1 to 45 F differential for alarms ALd Temperature alarm delay 0 to 255 min delay time between the detection of an alarm condition and the relative alarm signalling Dot Delay of temperature alarm with door open 0 0 to 24h00min res 10 min delay time between the detection of a temperature alarm condition and the relative alarm signalling after powering on the ...

Страница 5: ...audrate for serial communication brd Keyboard lock type nu SEL ALL UnL keyboard unlocked SEL only SET and DEF AUX button enabled when locked ALL keyboard unlocked after tLC tLC Keyboard lock timeout 0 to 255 sec timeout after power on and before activating the keyboard lock LGC Light button configuration left upper side nu not used LiG light output control AUS auxiliary output control dEF defrost ...

Страница 6: ...e alarms EA CA and dA will automatically stop as soon as the digital input is disabled The internal buzzer can be muted by pressing any key if parameter tbA Y 21 TECHNICAL DATA Housing self extinguishing ABS Case frontal 32x74 mm depth 60mm Mounting panel mounting in a 71x29mm panel cut out Body Protection IP20 Frontal protection IP65 Terminal blocks plug in terminal blocks 2 5 mm2 wiring Power su...

Страница 7: ...roller via Bluetooth Extend rights of access to a specific appliance also to other users A Cloud portal will be used for Extend rights of access to a specific appliance also to other users Select the permission level for any new user The link for opening the Cloud webpage is on the left side menu of the mobile APP slide right the screen of the APP when on the Device List page and follow the Cloud ...

Отзывы: