Emerson Dixell XR40D Скачать руководство пользователя страница 4

 

1592007231 XR40C-D GB r1.0 18.11.2015 

XR40C – XR40D 

4/4 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F) 

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

14.  CONNECTIONS 

14.1  XR40C: 8A COMPRESSOR 

N.C.

1 2 3 4 5

6

7

9 101112

Com

p

Def

Eva

p.

Ro

om

8

Hot Key

8(3)A250V

8(3)A250V

Line

 

 

12Vac/dc supply

: connect to the terminals 7 and 8. 

24Vac/dc supply

: connect to the terminals 7 and 8. 

120Vac supply

: connect to the terminals 7 and 8. 

14.2  XR40C: 20A COMPRESSOR  

 

N.C.

1 2 3 4 5

6

7

9 101112

Com

p

Def

Eva

p.

Ro

om

8

Hot Key

8(3)A250V

20(8)A250V

Line

 

 
12Vac/dc supply

: connect to the terminals 7 and 8. 

24Vac/dc supply

: connect to the terminals 7 and 8. 

120Vac supply

: connect to the terminals 7 and 8. 

14.3  XR40D: 8A COMPRESSOR 

 

Line

   3  4

5  6 

8(3)A/250Vac

8(3)A/250Vac

13  14  15  16  17  18  19 

Comp

n.c.

11  12

n.c.

Power 

Supply

HO

KE

Y

   1  2

 

 

24Vac/dc supply

: connect to the terminals 11 and 12. 

120Vac supply

: connect to the terminals 11 and 12. 

230Vac supply

: connect to the terminals 11 and 12. 

14.4  XR40D: 20A COMPRESSOR 

 

   3  4

5  6 

11  12

Line

8(3)A/250Vac

20(8)A/250Vac

  15  16  17  18 19 

Comp

n.c.

Power 

Supply

HO

T K

EY

   1  2

 

 

24Vac/dc supply

: connect to the terminals 11 and 12. 

120Vac supply

: connect to the terminals 11 and 12. 

230Vac supply

: connect to the terminals 11 and 12. 

 

15.  DEFAULT SETTING VALUES  

Label 

Name 

Range 

°C/°F 

Set 

Set point 

LS÷US 

-5/0 

Hy 

Differential 

0,1

25.5°C/ 1

 255°F 

2/4 

LS 

Minimum set point 

-50°C

SET/-58°F

SET 

-50/-58 

US 

Maximum set point 

SET

110°C/ SET 

 230°F 

110/230 

Ot 

Thermostat probe calibration 

-12

12°C /-120

120°F 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

OE 

Evaporator probe calibration 

-12

12°C /-120

120°F 

OdS 

Outputs delay at start up 

0÷255 min 

AC 

Anti-short cycle delay 

 50 min 

CCt 

Continuos cycle duration 

0.0÷24.0h 

0.0 

COn 

Compressor  ON  time  with  faulty 
probe 

 255 min 

15 

COF 

Compressor OFF time with faulty 
probe 

 255 min 

30 

CF 

Temperature measurement unit 

°C 

 °F 

°C/°F 

rES 

Resolution 

in=integer; dE= dec.point

 

dE/- 

Lod 

Probe displayed 

P1;P2 

P1 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL 

dtE 

Defrost termination temperature 

-50 

 50 °C 

8/46 

IdF 

Interval between defrost cycles 

 120 ore 

MdF 

(Maximum) length for defrost 

 255 min 

30 

dSd 

Start defrost delay 

0÷99min 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Fdt 

Draining time 

0÷120 min 

dPo

 

First defrost after startup 

n=after IdF; y=immed. 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

ALU 

MAXIMUM temperature alarm 

Set

110.0°C; Set÷230°F 

110/230 

ALL 

Minimum temperature alarm 

-50.0°C

Set/ -58°F

Set 

-50/-58 

ALd 

Temperature alarm delay 

 255 min 

15 

dAO 

Delay  of  temperature  alarm  at 
start up 

 

23h e 50’ 

1.30 

i1P 

Digital input polarity 

oP=opening;CL=closing 

CL 

i1F 

Digital input configuration 

EAL=extern. alarm; bAL=lock 

regulation; PAL=press. switch; 
dor=door switch; dEF=defrost; 

LHt=disabled; Htr = Cooling - 

heating 

EAL 

did 

Digital input alarm delay 

0÷255min 

Nps 

Number  of  activation  of  pressure 
switch 

0 ÷15  

15 

odc 

Compressor  status  with  open 
door:   

no, Fan = normal;  

CPr; F_C = Compr. OFF; 

 

no 

PbC 

Kind of probe 

Ptc; ntc 

ntc/Ptc 

dP1 

Room probe display 

-- 

-- 

dP2 

Evaporator probe display 

-- 

-- 

rEL 

Software release 

-- 

4.0 

Ptb 

Map code 

-- 

 

Hidden parameters 

 

 

 

 
 
 
 

Содержание Dixell XR40D

Страница 1: ... defrost termination temperature The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compre...

Страница 2: ...rt up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter AC Anti short cycle delay 0 50 min minimum interval between the compressor stop and the following restart CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays ...

Страница 3: ...rminal block to connect cables with a cross section up to 2 5 mm2 Before connecting cables make sure the power supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay 10 1 PROBE CONNECTION The pro...

Страница 4: ... 50 58 US Maximum set point SET 110 C SET 230 F 110 230 Ot Thermostat probe calibration 12 12 C 120 120 F 0 P2P Evaporator probe presence n not present Y pres y OE Evaporator probe calibration 12 12 C 120 120 F 0 OdS Outputs delay at start up 0 255 min 0 AC Anti short cycle delay 0 50 min 1 CCt Continuos cycle duration 0 0 24 0h 0 0 COn Compressor ON time with faulty probe 0 255 min 15 COF Compres...

Отзывы: