background image

 

1592007231 XR40C-D GB r1.0 18.11.2015 

XR40C – XR40D 

3/4 

with

 

i1F= dor: door open signalling delay 

with  i1F  =  PAL:  time  for  pressure  switch  function: 

time  interval  to 

calculate the number of the pressure switch activation. 

nPS  Pressure  switch  number:

  (0 

15)  Number  of  activation  of  the  pressure 

switch, during the “

did

” interval, before signalling the alarm event (I2F= PAL).  

If  the  nPS  activation  in  the  did  time  is  reached,  switch  off  and  on  the 
instrument to restart normal regulation. 

 

odc 

Compressor status when open door:

  

no,

 

Fan

 = normal; 

CPr, F_C

 = 

Compressor OFF  

OTHER 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 

= PBC probe, 

ntC = 

NTC probe. 

 

dP1  First probe display 

 

dP2  Second probe display 

 

rEL 

Software release 

for internal use. 

 

Ptb 

Parameter table code:

 readable only. 

8.  DIGITAL INPUT (IF AVAILABLE) 

The free contact digital input is programmable in five different configurations by 
the “

i1F

” parameter. 

8.1  DOOR SWITCH INPUT  (i1F = dor) 

It  signals  the  door  status  and  the  corresponding  relay  output  status  through  the 

odc

” parameter: 

no,

 

Fan

 = normal (any change); 

CPr, F_C

 = Compressor OFF; 

Since  the  door  is  ope

ned,  after  the  delay  time  set  through  parameter  “

did

”,  the 

door  alarm  is  enabled,  the  display  shows  the  message  “

dA

”  and 

the  regulation 

restarts

.  The  alarm  stops  as  soon  as  the external digital input is disabled again. 

With the door open, the high and low temperature alarms are disabled. 

8.2  GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before 

signalling the “

EAL

” alarm message. The outputs status don’t change. The alarm 

stops just after the digital input is de-activated. 

8.3  SERIOUS ALARM MODE (i1F = bAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  “

did

”  delay  before 

signalling  the  “

CA

”  alarm  message.  The  relay  outputs  are  switched  OFF.  The 

alarm will stop as soon as the digital input is de-activated. 

8.4  PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached 

the  number  of  activation  of    the  “

nPS

”  parameter,  the  “

CA

”  pressure  alarm 

message will be displayed. The compressor and the regulation are stopped. When 
the digital input is ON the compressor is always OFF. 

If  the  nPS  activation  in  the  did  time  is  reached,  switch  off  and  on  the 
instrument to restart normal regulation. 

8.5  START DEFROST (i1F = dFr) 

It starts a defrost if there are the right conditions. After the defrost is finished, the 
normal  regulation  will  restart  only  if  the  digital  input  is  disabled  otherwise  the 
instrument will wait until the “MdF” safety time is expired. 

8.6  INVERSION OF  THE KIND OF ACTION: HEATING-
COOLING (i1F = Htr) 

This  function  allows  to  invert  the  regulation  of  the  controller:  from  cooling  to 
heating and viceversa. 

8.7  DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

 

9.  INSTALLATION AND MOUNTING 

Instrument 

XR40C

  shall  be  mounted  on  vertical  panel, 

in a 29x71 mm hole, and fixed using the special bracket 
supplied.  
To obtain an IP65 protection grade use the front panel 
rubber gasket (mod. RG-C) as shown in figure.  

 

Instrument 

XR40D

 shall be mounted on an omega DIN rail  

The  temperature  range  allowed  for  correct  operation  is  0

60  °C.  Avoid  places 

subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same 
recommendations apply to probes. Let air circulate by the cooling holes. 

10.  ELECTRICAL CONNECTIONS 

The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a 
cross  section  up  to  2,5  mm

2

.  Before  connecting  cables  make  sure  the  power 

supply  complies  with  the  instrument’s  requirements.  Separate  the  probe  cables 
from the power supply cables, from the outputs and the power connections. Do not 
exceed the maximum current allowed on each relay, in case of heavier loads use 
a suitable external relay. 

10.1  PROBE CONNECTION 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to 
casual  liquid  infiltration.  It  is  recommended  to  place  the  thermostat  probe  away 
from  air  streams  to  correctly  measure  the  average  room  temperature.  Place  the 
defrost  termination  probe  among  the  evaporator  fins  in  the  coldest  place,  where 
most ice is formed, far from heaters or from the warmest place during defrost, to 
prevent premature defrost termination. 

11.  HOW TO USE THE HOT KEY  

11.1  HOW TO PROGRAM A HOT KEY FROM THE 
INSTRUMENT (UPLOAD) 

1. 

Program one controller with the front keypad. 

2. 

When the controller is ON

, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message appears followed a by flashing 

“End”

 

3. 

Push “

SET”

 key and the 

End

 will stop flashing. 

4. 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

:  the “

Err

” message is displayed for failed programming. In this case push 

again 

o

 

key  if  you  want  to  restart  the  upload  again  or  remove  the  “

Hot  key

”  to 

abort the operation. 

11.2  HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 
(DOWNLOAD) 

1. 

Turn OFF the instrument. 

2. 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn 

the Controller ON. 

3. 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the 

Controller  me

mory,  the  “

doL

”  message  is  blinking  followed  a  by  flashing 

“End”.

 

4. 

After  10  seconds  the  instrument  will  restart  working  with  the  new 
parameters.  

5. 

Remove the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the 

unit 

off and then on if you want to restart the download again or remove the “

Hot 

key

” to abort the operation. 

12.  ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 
 

Room probe  failure 

Compressor output according 
to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

“dA” 

Door open 

Regulation restarts  

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious external alarm (i1F=bAL) 

All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL) 

All outputs OFF 

12.1  ALARM RECOVERY  

Probe alarms “

P1

” and “

P2

” start some seconds after the fault in the related probe; 

they  automatically  stop  some  seconds  after  the  probe  restarts  normal  operation. 
Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat 

temperature returns to normal values and when defrost starts. 
Alarms 

“EA”

  and 

“CA” 

(with  i1F=bAL)

 

recover  as  soon  as  the  digital  input  is 

disabled. 
Alarm 

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

13.  TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XR40C 

frontal 32x74 mm; depth 60mm; 

XR40D 

4 DIN modules 70x85 mm; depth 61mm

 

Mounting: XR40C 

panel mounting in a 71x29mm panel cut-out 

 

XR40D

 DIN RAIL mounted in a omega (3) din rail 

Protection: 

IP20.

 

Frontal protection: XR40C 

IP65 with frontal gasket RG-C (optional). 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power  supply: 

according  to  the  model:  12Vac/dc,  ±10%;  24Vac/dc,  ±10%;  

230Vac 

10%, 50/60Hz, 110Vac 

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high.  

Inputs

: 2 NTC or PTC probes. 

Digital input: 

free contact 

Relay outputs

 

 

compressor: 

SPDT relay 8(3) A, 250Vac or  

 

SPST relay 20(8)A; 250Vac

 

 

defrost: 

SPDT relay 8(3) A, 250Vac 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

normal; 

Software class: 

A.

 

Содержание Dixell XR40D

Страница 1: ... defrost termination temperature The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compre...

Страница 2: ...rt up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter AC Anti short cycle delay 0 50 min minimum interval between the compressor stop and the following restart CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays ...

Страница 3: ...rminal block to connect cables with a cross section up to 2 5 mm2 Before connecting cables make sure the power supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay 10 1 PROBE CONNECTION The pro...

Страница 4: ... 50 58 US Maximum set point SET 110 C SET 230 F 110 230 Ot Thermostat probe calibration 12 12 C 120 120 F 0 P2P Evaporator probe presence n not present Y pres y OE Evaporator probe calibration 12 12 C 120 120 F 0 OdS Outputs delay at start up 0 255 min 0 AC Anti short cycle delay 0 50 min 1 CCt Continuos cycle duration 0 0 24 0h 0 0 COn Compressor ON time with faulty probe 0 255 min 15 COF Compres...

Отзывы: