MODBUS Termination Blocks
Default Setting Values • 27
19 Default Setting Values
Label
Name
Range
Value
Level
SEt
Setpoint
LS
to
US
3.0
---
Hy
Differential
0.1 to 25.5°C/ 1 to 255°F
2.0
Pr1
LS
Minimum setpoint
-100°C to
SEt
/-58°F to
SEt
-50.0
Pr2
US
Maximum setpoint
SEt
to 110°C/
SEt
to 230°F
110
Pr2
ot
Thermostat probe calibration
-12 to 12°C /-120 to 120°F
0.0
Pr1
P2P
Evaporator probe presence
n
= not present;
Y
= present
Y
Pr1
oE
Evaporator probe calibration
-12 to 12°C /-120 to 120°F
0.0
Pr2
P3P
Third probe presence
n
= not present;
Y
= present
n
Pr2
o3
Third probe calibration
-12 to 12°C /-120 to 120°F
0
Pr2
P4P
Fourth probe presence
n
= not present;
Y
= present
n
Pr2
o4
Fourth probe calibration
-12 to 12°C /-120 to 120°F
0
Pr2
Ods
Outputs delay at start up
0 to 255 min
0
Pr2
Ac
Anti-short cycle delay
0 to 50 min
1
Pr1
rtr
P1
-
P2
percentage for regulation
0 to 100 (100 =
P1
, 0 =
P2
)
100
Pr2
CCt
Continuous cycle duration
0.0 to 24.0 hr
0.0
Pr2
CCS
Setpoint for continuous cycle
(-100 to 150.0°C) (-67 to 302°F)
3
Pr2
Con
Compressor ON time with faulty probe
0 to 255 min
15
Pr2
CoF
Compressor OFF time with faulty probe
0 to 255 min
30
Pr2
CH
Kind of action
CL
;
Ht
CL
Pr1
CF
Temperature measurement unit
°C to °F
°C
Pr2
rES
Resolution
in
= integer;
dE
= decimal point
dE
Pr1
Lod
Probe displayed
P1
;
P2
P1
Pr2
Red
2
X-REP display
P1
–
P2
–
P3
–
P4
–
SEt
–
dtr
P1
Pr2
dLy
Display temperature delay
0 to 20.0 min (10 sec)
0.0
Pr2
dtr
P1
-
P2
percentage for display
1 to 99
50
Pr2
EdF*
Kind of interval for defrost
rtC
to
in
rtC
Pr2
tdF
Defrost type
EL
= electrical heater;
in
= hot
gas
EL
Pr2
dFP
Probe selection for defrost termination
nP
;
P1
;
P2
;
P3
;
P4
P2
Pr2
dtE
Defrost termination temperature
-50 to 50°C
8.0
Pr1
IdF
Interval between defrost cycles
1 to 120 hr
8
Pr1
MdF
Maximum duration for defrost
0 to 255 min
20
Pr1
dSd
Start defrost delay
0 to 99 min
0
Pr2
dFd
Displaying during defrost
rt
,
it
,
SEt
,
dEF
it
Pr2
dAd
MAX display delay after defrost
0 to 255 min
30
Pr2
Table 19-1
- Default Setting Values (
2
Only for XR35CX with X-REP output)
Содержание Dixell XR35CX - 110VAC
Страница 2: ......
Страница 4: ......
Страница 27: ...Other Messages Connections 21 16 Connections The X REP output is optional Figure 16 1 XR35CX Connections ...
Страница 38: ...32 XR35CX I O Manual 026 1203 Rev 3 03 FEB 2015 Figure A 1 MODBUS Com Wiring Diagram ...
Страница 39: ......