Emerson DIXELL XR30CHC Скачать руководство пользователя страница 3

 

1592034030 XR30CHC EN r1.0 2019.01.31 

                           XR30CHC 

3/6 

 

LS 

Minimum Set Point:

 (-100.0°C to SET; -148°F to SET) sets the minimum value for the  set 

point. 

US 

Maximum Set Point:

 (SET to 200.0°C; SET to 392°F) set the maximum value for set point. 

HY 

Differential in normal mode:

 (0.1 to 25.0°C; 1 to 45°F) differential for set point. Compressor 

Cut-IN is 

T > SET + HY

. Compressor Cut-OUT is 

T<=SET

HYE 

Differential  in  energy  saving  mode:

  (0.1  to  25.0°C;  1  to  45°F)  differential  for  set  point. 

Compressor Cut-IN is 

T > SET + HES + HYE

. Compressor Cut-OUT is 

T<= SET + HES

odS 

Outputs  delay  activation  after  power  on:

 (0  to  255  min)  this  function  is  enabled  after  the 

power-on of the instrument and delays output activations. 

AC 

Anti-short cycle delay:

 (0 to 50 min) minimum interval between a compressor stop and the 

following restart. 

rtr 

Percentage for regulation: 

100=P1 only; 0=P2 only

 

CCt 

Maximum duration for pull down:

 (0.0 to 23h50min, res. 10min) after elapsing this interval of 

time the super cooling function is immediately stopped 

CCS 

Differential for pull down:

 (-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the 

regulation  SETPOINT  is  moved  to 

SET+CCS 

(in  normal  mode)  or  to 

SET+HES+CCS

  (in 

energy saving mode)

 

oHt 

Overheating  before  activating  the  pull-down  function  (when  in  normal  mode): 

(1.0  to 

12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function. 

oHE 

Overheating before activating the pull-down function (when in energy saving mode): 

(1.0 

to  12.0°C;  1  to  21°F)  this  is  the  upper  threshold  limit  used  to  activate  the  super  cooling 
function. 

Con 

Compressor ON time with faulty probe:

 (0 to 255 min) time during which the compressor is 

active in case of faulty thermostat probe. With 

CY=0

 compressor is always OFF. 

CoF 

Compressor OFF time with faulty probe:

 (0 to 255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With 

Cn=0

 compressor is always active. 

PROBE SETUP - Prb 

PbC 

Probe selection:

 ntC; PtC; Pt1000 

ot 

Probe P1 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the 

first probe. 

P2P 

Evaporator probe presence:

 

n

 = not present; 

Y

 = the defrost stops by temperature. 

oE 

Evaporator  probe  calibration:

  -12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust  any  possible 

offset of the third probe. 

P3P 

Third probe presence:

 

n

 = not present; 

Y

 = the defrost stops by temperature. 

o3 

Third probe calibration:

 -12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of 

the third probe. 

DISPLAY - diS 

iCo 

Enabling icon visualisation:

 (n; Y) the icons can be hidden during normal functioning

 

CF 

Temperature measurement unit: 

(°C; °F) 

°C 

= Celsius; 

°F

 = Fahrenheit. 

rES 

Resolution (only for °C):

 (dE; in) 

dE

 = decimal; 

in

 = integer. 

Lod 

Probe displayed: 

(

P1; P2; P3; P4; SEt; dtr; USr

Px

=probe “x”; 

SEt

=set point; 

dtr

=do not 

use it; 

USr

=do not use it. 

dLY 

Temperature  visualization  delay:

  (0.0  to  20min00sec,  res.  10  sec)  when  the  temperature 

increases, the display is updated of 1°C or 1°F after this time. 

dtr 

Visualization percentage = F(P1;P2): 

(0 to 100)

 

with 

dtr=1

 the display will show this value 

VALUE=0.01*P1+0.99*P2 

DEFROST - dEF 

idF 

Interval  between  two  consecutive  defrost  cycles:

  (0  to  255  hours)  determines  the  time 

interval between the beginnings of two defrosting cycles. 

MdF 

Maximum length for defrost:

 (0 to 255 min; 0 means no defrost) when 

P2P=n

 (no evaporator 

probe presence) it sets the defrost duration, when 

P2P=Y

 (defrost end based on  evaporator 

temperature) it sets the maximum length for defrost. 

dSd 

Start defrost delay: 

(0 to 255 min) delay in defrost activation.

 

dFd 

Display during defrost:

 (rt; it; SP; dF) 

rt

 = real temperature; 

it

 = start defrost temperature;  

SP

 = SET-POINT; 

dF

 

= label “

dF

”.

 

dAd 

Max delay for updating display after any defrost: 

(0 to 255 min) delay before updating the 

temperature on the display after finishing any defrost. 

Fdt 

Draining time: 

(0 to 255 min) 

 

dPo 

First defrost after start-up: 

(n; Y) to enable defrost at power on.

 

dAF 

Defrost delay after freezing: 

(0.0 to 24h00min, res. 10 min) delay before activating a defrost. 

od1 

Automatic  defrost  (at  the  beginning  of  any  energy  saving  mode): 

(n;  Y) 

n

=function 

disabled; 

Y

=function enabled 

FAN - FAn 

FAC 

Probe selection for  condenser fan management:  nP

=no probe; 

P1

=probe Pb1; 

P2

=probe 

Pb2; 

P3

=probe Pb3; 

P4

=probe Pb4 on Hot Key plug.

 

St2

 

Condenser  fan  stop  temperature: 

(-55  to  50°C;  -67  to  122°F)  setting  of  temperature, 

detected by evaporator probe. Over this value of temperature fans are always OFF. 

HY2 

Differential for condenser fan:

 (0.1 to 25.5°C; 1 to 45°F) differential for evaporator ventilator 

regulator 

FCC

 

Condenser fan mode operation: 

(Cn; on; CY; oY)  

 

Cn 

= runs with the compressor and OFF during defrost  

 

on 

= continuous mode, OFF during defrost 

 

CY 

= runs with the compressor and ON during defrost 

 

oY 

= continuous mode, ON during defrost 

ALARMS - ALr

 

ALP 

Temperature alarms probe selection: 

(P1, P2, P3, P4) 

ALC 

Temperature alarms configuration: 

(Ab, rE) 

Ab

 = absolute; 

rE

 = relative. 

ALU

 

Maximum temperature alarm:

 when this temperature is reached, the alarm is enabled after 

the 

Ad

 delay time. 

 

If 

ALC=Ab

 

 ALL to 150.0°C or ALL to 302°F. 

 

If 

ALC=rE

 

 0.0 to 50.0°C or 0 to 90°F. 

ALL

 

Minimum temperature alarm:

 when this temperature is reached, the alarm is enabled after the 

Ad

 delay time. 

 

If 

ALC=Ab

 

 -55.0°C to ALU or -67°F to ALU. 

 

If 

ALC=rE

 

 0.0 to 50.0°C or 0 to 90°F. 

AFH 

Differential for temperature alarm recovery:

 (0.1 to 25.0°C; 1 to 45°F) differential for alarms.

 

ALd

 

Temperature  alarm  delay:

  (0  to  255  min)  delay  time  between  the  detection  of  an  alarm 

condition and the relative alarm signalling. 

dot

 

Delay  of  temperature  alarm  with  door  open: 

(0.0  to  24h00min,  res.  10  min)  delay  time 

between the detection of a temperature alarm condition and the relative alarm signalling, after 
powering on the instrument. 

dAo

 

Delay of temperature alarm at start up: 

(0.0 to 24h00min, res. 10 min) delay time between 

the detection of a temperature alarm condition and the relative alarm signalling, after powering 
on the instrument. 

CONDENSER TEMPERATURE ALARM - ALr 

AP2 

Probe  selection  for  second  temperature  alarms: 

(nP;  P1;  P2;  P3;  P4) 

nP

=no  probe; 

P1

=thermostat probe; 

P2

=evaporator probe; 

P3

=do not use it; 

P4

=Probe on Hot Key plug 

AU1 

Second high temperature pre-alarm:

 (-55.0 to 150.0°C; -67 to 302°F)

 

AH1 

Differential for second temperature pre-alarm recovery: 

(0.1 to 25.0°C; 1 to 45°F)

 

Ad1 

Second temperature pre-alarm delay: 

(0 to 255 min; 255 = not used) delay time between the 

detection of a condenser pre-alarm condition and the relative alarm signaling.

 

AL2 

Second low temperature alarm:

 (-55.0 to 150.0°C; -67 to 302°F)

 

AU2 

Second high temperature alarm: 

(-55.0 to 150.0°C; -67 to 302°F)

 

AH2 

Differential for second temperature alarm recovery: 

(0.1 to 25.0°C; 1 to 45°F)

 

Ad2 

Second  temperature  alarm  delay: 

(0  to  255  min;  255  =  not  used)  delay  time  between  the 

detection of a condenser alarm condition and the relative alarm signaling.

 

dA2 

Delay for second temperature alarm at start up: 

(0.0 to 24h00min, res. 10 min)

 

bLL 

Compressor  off  because  of  second  low  temperature  alarm: 

(n;  Y)

  n 

=  no,

 

compressor 

keeps on working

; Y 

= yes,

 

compressor is  switched off  till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

AC2 

Compressor  off  because  of  second  high  temperature  alarm: 

(n;  Y)

  n 

=  no,

 

compressor 

keeps on working

; Y 

= yes,

 

compressor is  switched off  till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

SAF 

Differential for anti freezing control: 

(-12.0 to 12.0°C; -21.0 to 21.0°F) regulation sopped if 

T<SET+SAF

 

DIGITAL OUTPUT MANAGEMENT - oUt 

tbA 

Alarm muting: 

(n; Y) to disable the (optional) buzzer and the output configured as alarm. 

oAx 

(x=1,2) 

Output  configuration: 

(nu;  CP1;  dEF;  FAn;  ALr;  LiG;  AUS;  db;  onF;  HES;  Cnd) 

nu

=not 

used; 

CP1

=compressor; 

dEF

=defrost; 

FAn

=ventilators; 

ALr

=alarm; 

LiG

=light; 

AUS

=Auxiliary relay; 

onF

=always on with instrument on; 

db

=neutral zone; 

HES

=night blinds; 

Cnd

=Condenser  fan; 

CP2

=second  compressor; 

dF2

=second  defrost; 

HEt

=heater  control; 

inV

=do not use it. 

AoP 

Alarm  relay  polarity: 

(oP;  CL) 

oP 

=  alarm  activated  by  closing  the  contact; 

CL 

=  alarm 

activated by opening the contact

 

DIGITAL INPUT - inP 

ibt

 

Base time for digital inputs:

 (SEC; Min) 

SEC 

= seconds; 

Min 

= minutes. Delay for activating 

the function linked to the digital inputs. 

i1P

 

Digital  input  1  polarity:

  (oP;  CL) 

oP 

=  activated  by  closing  the  contact; 

CL 

=  activated  by 

opening the contact. 

i1F

 

Digital input 1 configuration:

 (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; 

CC; EMt)  

 

nu

=not used 

 

dor

 = door switch function 

 

dEF

 = defrost activation  

 

AUS

 = auxiliary output 

 

ES 

= energy saving mode activation 

 

EAL

 = external warning alarm 

 

bAL 

= external lock alarm 

 

PAL 

= external pressure alarm 

 

FAn 

= evaporator fan control 

 

HdF

 = holiday defrost 

 

onF 

= ON/OFF status change 

 

LiG 

= light output control 

 

CC

 = change configuration (between C1 and C2) 

 

EMt

 = do not use it  

did

 

Digital inputs 1 alarm delay:

 (0 to 255) it is the delay between the detection of an  external 

event and the activation of the relative function. 

i2P

 

Digital input 2 polarity (if d.i.2 present):

 (oP; CL) 

oP 

= activated by closing the contact; 

CL 

activated by opening the contact. 

i2F

 

Digital input 2 configuration:

 (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; 

CC; EMt)  

 

nu

=not used 

 

dor

 = door switch function 

 

dEF

 = defrost activation  

 

AUS

 = auxiliary output 

 

ES 

= energy saving mode activation 

 

EAL

 = external warning alarm 

 

bAL 

= external lock alarm 

 

PAL 

= external pressure alarm 

 

FAn 

= evaporator fan control 

 

HdF

 = holiday defrost 

 

onF 

= ON/OFF status change 

 

LiG 

= light output control 

 

CC

 = change configuration (between C1 and C2) 

 

EMt

 = Motion detector 

d2d 

Digital inputs 2 alarm delay:

 (0 to 255) it is the delay between the detection of an  external 

event and the activation of the relative function. 

nPS 

Number  of  external  pressure  alarms  before  stopping  the  regulation: 

(0  to  15)  after 

reaching 

nPS

 events in the digital input alarm delay (par. 

dxd

) the regulation will be stopped 

and a manual restart (ON/OFF, power OFF and power ON) will be required 

odC

 

Compressor and fan status after door opening:

 (no; FAn; CPr; F-C): 

no

 = normal;  

FAn

 = Fans OFF; 

CPr

 = Compressor OFF; 

F-C

 = Compressor and fans OFF. 

rrd

 

Regulation restart after door open alarm:

 (n; Y) 

n

 = no regulation if door is opened; 

Y

 = when 

did

 is elapsed, regulation restarts even if a door open alarm is present. 

LCi 

Light output controlled by digital input: 

(0 to 255 min) a digital input event will activate the 

light output and the output will stay ON for this interval 

ENERGY SAVING - ES 

HES

 

Differential  for  energy  saving  mode:

  (-30.0  to  30.0°C;  -54  to  54°F)  it  sets  the  increasing 

value of the set point during the Energy Saving cycle. 

Содержание DIXELL XR30CHC

Страница 1: ...lways saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to normal mode HES differential for SETPOINT when energy sa...

Страница 2: ...fter ending the installing operations 10 3 1 ENTER THE PROTECTED LEVEL 1 Enter the Programming mode by pressing SET DOWN buttons for 3 sec C or F LED starts blinking 2 Released the buttons and then search for submenu Pr2 3 Per SET button and then insert the password value 4 Confirm with SET If the password is correct the label Pr2 will blink for some time and then protected parameter menu will be ...

Страница 3: ...he alarm is enabled after the Ad delay time If ALC Ab 55 0 C to ALU or 67 F to ALU If ALC rE 0 0 to 50 0 C or 0 to 90 F AFH Differential for temperature alarm recovery 0 1 to 25 0 C 1 to 45 F differential for alarms ALd Temperature alarm delay 0 to 255 min delay time between the detection of an alarm condition and the relative alarm signalling dot Delay of temperature alarm with door open 0 0 to 2...

Страница 4: ...value visualization ES change working mode from normal to energy saving mode and vice versa LG2 Light button timed 3sec configuration left upper side nu not used LiG light output control AUS auxiliary output control dEF defrost control CC change configuration between NT and LT map ES change working mode from normal to energy saving mode and vice versa UP2 Up button timed 3sec configuration nu not ...

Страница 5: ...ousing self extinguishing ABS Case frontal 32x74 mm depth 60mm Mounting panel mounting in a 71x29mm panel cut out Body Protection IP20 Frontal protection IP65 Terminal blocks Screw terminal block 2 5 mm2 wiring Power supply according to the model 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3 5VA max Display 3 digit LED H 14 2 mm Inputs up to 4 NTC PTC or PT1000 probes Digital input up to ...

Страница 6: ...roller via Bluetooth Extend rights of access to a specific appliance also to other users A Cloud portal will be used for Extend rights of access to a specific appliance also to other users Select the permission level for any new user The link for opening the Cloud webpage is on the left side menu of the mobile APP slide right the screen of the APP when on the Device List page and follow the Cloud ...

Отзывы: