                           XR30CHC 

1/6 

 

DIGITAL CONTROLLER WITH  

BLUETOOTH CONNECTIVITY 

XR30CHC 

82 rel. 1.0.1 

 
1

 

GENERAL WARNINGS ................................................................................................................................... 1

 

2

 

GENERAL DESCRIPTION .............................................................................................................................. 1

 

3

 

REGULATION .................................................................................................................................................. 1

 

4

 

ENERGY SAVING ALGORITHM .................................................................................................................... 1

 

5

 

PULL DOWN FUNCTION ................................................................................................................................ 1

 

6

 

CONDENSER FAN .......................................................................................................................................... 1

 

7

 

DEFROST ........................................................................................................................................................ 1

 

8

 

DIGITAL OUTPUT CONFIGURATION ........................................................................................................... 1

 

9

 

FRONT PANEL COMMANDS ......................................................................................................................... 2

 

10

 

PARAMETER MENU ....................................................................................................................................... 2

 

11

 

PARAMETERS ................................................................................................................................................ 2

 

12

 

DIGITAL INPUTS ............................................................................................................................................. 4

 

13

 

INSTALLATION AND MOUNTING .................................................................................................................. 4

 

14

 

OPTIONAL FEATURES .................................................................................................................................. 4

 

15

 

ELECTRICAL CONNECTIONS ....................................................................................................................... 4

 

16

 

USE THE HOT-KEY ........................................................................................................................................ 5

 

17

 

INTERNAL MEMORY ...................................................................................................................................... 5

 

18

 

ALARM SIGNALLING ...................................................................................................................................... 5

 

19

 

TECHNICAL DATA .......................................................................................................................................... 5

 

20

 

WIRINGS .......................................................................................................................................................... 5

 

21

 

BLUETOOTH COMMUNICATION .................................................................................................................. 6

 

 

1

 

GENERAL WARNINGS 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 
the same and unchanged functionality. 

1.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.

r.l

.” (see 

address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of  mains filters (our mod. FT1) in parallel 
with inductive loads could be useful. 

2

 

GENERAL DESCRIPTION 

The 

XR30CHC

32x74x60mm format

, is a microprocessor-based controller suitable  for  applications 

on  medium  or  low  temperature  ventilated  refrigeration  units.  It  has  2  relay  outputs  to  control 
compressor and fans, light or defrost. The device is also provided with up to 3 NTC, PTC or PT1000 
probe inputs to control temperature, to manage the condenser and for visualization purpose. There are 

also two configurable digital inputs. By using the 

HOT-KEY

 it is possible to program the instrument in a 

quick and easy way. 
The controller has Bluetooth 4.2 connectivity.  

3

 

REGULATION 

The  regulation  is  performed  according  to 
the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature  increases  and  reaches  set 
point  plus  differential,  the  compressor  will 
start.  The  compressor  will  stop  when  the 
temperature  reaches  the  set  point  value 
again. 

 

In  case  of  fault  because  of  the  thermostat  probe,  the  start  and  stop  of  the  compressor  are  timed 
through parameters 

CoF

 and 

Con

4

 

ENERGY SAVING ALGORITHM

 

4.1

 

DESCRIPTION 

The device permits to set different temperature to be used during normal and reduced power use. The 
standard SET-POINT (

SET

) is used to maintain the temperature at a certain value when the energy 

saving status (ES) is not active. On the other side, when the ES status is active a different SET-POINT 
(

SET_ES

),  higher  than  the  standard  one,  will  be  used.  The  parameter 

HES

  will  have  to  be  set  to 

change the regulation temperature according to the following formula: 

SET_ES = SET + HES 

There are also two different differential values for 

SET

 and 

SET_ES

, which are used for compressor 

cut-in  and  cut-out:  when  ES  status  is  active  the 

HYE

  parameter  will  be  used  instead  of  the 

HY

 

parameter. 

4.2

 

BASIC ENERGY SAVING ALGORITHM 

The energy saving status will be always saved in the internal memory to resume previous operation if 
a power failure occurs. It needs the presence of a door switch to work (for example: 

i1F=dor

). 

4.2.1

 

PARAMETER INVOLVED 

 

i1F or i2F:

 set as door input to monitor the appliance usage

 

 

StE:

 interval to change from normal to energy saving mode

 

 

EtS:

 interval to change from energy saving to normal mode

 

 

HES:

 differential for SETPOINT when energy saving mode active

 

 

HYE:

 differential for regulation when energy saving mode is active

 

 

dS:

 interval for door opening detection

 

 

LdE:

 light output controlled (OFF when energy saving mode is active)

 

 

FROM 

TO 

CHANGED BY 

Normal 

mode

 

Energy 
Saving

 

- Pushing the 

DOWN

 button for 3 sec (if enabled). 

- Door continuously closed for the 

StE

 time.

 

Energy 
Saving

 

Normal 

mode 

- Pushing the 

DOWN

 button for 3 sec (if enabled).  

- Controller in ES mode for the 

EtS

 time. 

- If the controller is in ES mode, it returns in Standard mode 
(normal set-point) after opening the door more than 

dS

 time.

 

  

NOTE: 

the  cycling  mode  (ES  -  Normal  mode  -  ES  -  etc.)  works  if 

i1F=dor

  and 

EtS

  and 

StE

  are 

different from zero. If 

EtS=0 

or

 StE=0, 

the controller will not change the operating mode,

 

and it will be 

possible to change from the normal mode to the energy saving mode by using ES button or by setting 

i1F=ES

. See the below diagrams where the status changing is described: 

5

 

PULL DOWN FUNCTION 

The Pull Down is automatically activated: 

 

After any defrost 

 

After power-on if 

T>SET+CCS

 

 

When the regulation probe temperature 

is:  

 

T>SET+HY+oHt

 value in normal mode 

 

T>SET+HES+HYE+oHE

 value in energy saving mode  

In this case, a different set-point value (

SET+CCS

) will be enabled. As soon as the room temperature reaches 

the 

SET+CCS

 value, the compressor will be stopped and the normal regulation will restart. 

NOTE:

 Pull Down 

function is disabled when 

CCS=0

 or 

CCt=0

The 

CCt

 parameter sets the maximum activation time for any pull down. When 

CCt

 expires, the Pull Down will 

be immediately stopped and the standard SET-POINT will be restored. 

6

 

CONDENSER FAN 

6.1

 

GENERAL DESCRIPTION 

The condenser fan is can be managed by dedicated control. To enable it, a condenser probe must be 
selected by using par. 

FAC

. Here follows the description of all the related parameters: 

 

FAC

: to select the condenser fan probe 

 

St2

: to select the condenser fan deactivation setpoint 

 

HY2

: differential for condenser fan activation 

 

FCC

 parameter it can be selected the condenser fan working mode: 

o

 

FCC=C-n:

 condenser fan will switch ON and OFF with the compressor and

 

will 

not run during defrost 

o

 

FCC =o-n:

 condenser fan will run even if the compressor is off, and will not run 

during defrost 

o

 

FCC =C-Y: 

condenser fan will switch ON and OFF with the compressor and will 

run during defrost 

o

 

FCC =o-Y: 

condenser fan will run continuously, also during defrost. 

7

 

DEFROST 

7.1

 

DEFROST MODE 

Any defrost operation can be controlled in the following way: 

 

EdF=rtC

: by using an internal real-time clock (only for models equipped with RTC) 

 

EdF=in

: timed defrost, in this case a new defrost will start as soon as the 

idF

 timer expires 

7.2

 

TIMED MODE 

Defrost control is timed only. A couple of parameters is used to control the interval between defrost 
cycles  (

idF

)  and  its  maximum  length  (

MdF

).  During  the  defrost  cycle  is  possible  to  select  some 

different display indications by using the 

dFd 

parameter. 

8

 

DIGITAL OUTPUT CONFIGURATION 

Depending on the model, one or more  digital outputs (relays) can be configurated with one of the following 
functionalities. 

8.1

 

ON/OFF OUTPUT (OAX = ONF) 

When 

oAx=onF

, the output is activated when the controller is turned on and de-activated when the 

controller is turned off. 

8.2

 

DEAD BAND REGULATION 

With 

oAx=db

 the output can be used to control, for example, a heater element. It is used to implement 

a dead band regulation. If so: 

 

oAx=db

 cut in is 

SET-HY

 

 

oA1=db

 cut out is 

SET

  

8.3

 

ALARM OUTPUT 

With 

oAx=ALr 

the output operates as alarm output. It is activated every time an alarm happens. Its 

status depends on the 

tbA 

parameter: if 

tbA=Y

, the output is deactivated by pressing any key.  

If 

tbA=n

, the alarm output stays on until the alarm condition recovers. 

Содержание DIXELL XR30CHC

Страница 1: ...lways saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to normal mode HES differential for SETPOINT when energy sa...

Страница 2: ...fter ending the installing operations 10 3 1 ENTER THE PROTECTED LEVEL 1 Enter the Programming mode by pressing SET DOWN buttons for 3 sec C or F LED starts blinking 2 Released the buttons and then search for submenu Pr2 3 Per SET button and then insert the password value 4 Confirm with SET If the password is correct the label Pr2 will blink for some time and then protected parameter menu will be ...

Страница 3: ...he alarm is enabled after the Ad delay time If ALC Ab 55 0 C to ALU or 67 F to ALU If ALC rE 0 0 to 50 0 C or 0 to 90 F AFH Differential for temperature alarm recovery 0 1 to 25 0 C 1 to 45 F differential for alarms ALd Temperature alarm delay 0 to 255 min delay time between the detection of an alarm condition and the relative alarm signalling dot Delay of temperature alarm with door open 0 0 to 2...

Страница 4: ...value visualization ES change working mode from normal to energy saving mode and vice versa LG2 Light button timed 3sec configuration left upper side nu not used LiG light output control AUS auxiliary output control dEF defrost control CC change configuration between NT and LT map ES change working mode from normal to energy saving mode and vice versa UP2 Up button timed 3sec configuration nu not ...

Страница 5: ...ousing self extinguishing ABS Case frontal 32x74 mm depth 60mm Mounting panel mounting in a 71x29mm panel cut out Body Protection IP20 Frontal protection IP65 Terminal blocks Screw terminal block 2 5 mm2 wiring Power supply according to the model 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3 5VA max Display 3 digit LED H 14 2 mm Inputs up to 4 NTC PTC or PT1000 probes Digital input up to ...

Страница 6: ...roller via Bluetooth Extend rights of access to a specific appliance also to other users A Cloud portal will be used for Extend rights of access to a specific appliance also to other users Select the permission level for any new user The link for opening the Cloud webpage is on the left side menu of the mobile APP slide right the screen of the APP when on the Device List page and follow the Cloud ...

Отзывы: