1592009550 XW264K GB r1.0 04.08.2015 

                     XW264K 

3/4 

                          XW264K   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4/ 

DIGITAL INPUTS 
odc  Compressor and fan status when open door:

  

no

 = normal; 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF.  

I1P  Door switch input polarity: CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact. 

I2P  Configurable digital input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact 

I2F  Digital input operating mode:

 configure the digital input function: 

 

EAL 

= generic alarm; 

bAL 

= serious alarm mode; 

PAL 

= Pressure switch; 

dFr 

= Start defrost; 

 

AUS 

= Not used; 

Es 

= Energy Saving; 

onF 

= remote On/OFF. 

 

did   Time  interval/delay  for  digital  input  alarm:

(0

255  min.) Time interval to calculate the number of  the 

pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines 
the time delay between the detection and the successive signalling of the alarm. 

OTHER 
Adr   RS485  serial  address 

(1÷247)

Identifies  the  instrument  address  when  connected  to  a  ModBUS 

compatible monitoring system. 

rEL   Release software:

 (read only) Software version of the microprocessor. 

Ptb   Parameter table:

 (read only) it shows the original code of the Dixell parameter map. 

Prd    Probes display: 

(read only) display the temperature values of the evaporator probes Pb2 and Pb3. 

Pr2   Access to the protected parameter list 

(read only). 

6.

 

DIGITAL INPUTS 

The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the 
second is programmable in seven different configurations by the “

I2F

” parameter. 

6.1

 

DOOR SWITCH INPUT  

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

dOA

”, the alarm output is enabled and the 

display shows the message “

dA

”. The alarm stops as soon as the external digital input is disabled again. During 

this time and then for the delay “

dot

” after closing the door, the high and low temperature alarms are disabled. 

6.2

 

CONFIGURABLE INPUT - GENERIC ALARM (EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the “

EAL

” alarm 

message. The outputs status don’t change. The alarm stops just after the digital input is de-activated. 

6.3

 

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

BAL

” alarm message. 

The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. 

6.4

 

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of activation of  

the “

nPS

” parameter, the “

PAL

” pressure alarm message will be displayed. The compressor and the regulation 

are stopped. When the digital input is ON the compressor is always OFF. 

6.5

 

CONFIGURABLE INPUT - START DEFROST (DFR) 

It  executes  a  defrost  if  there  are  the  right  conditions.  After  the  defrost  is  finished,  the  normal  regulation  will 
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired. 

6.6

 

CONFIGURABLE INPUT - ENERGY SAVING (ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES (parameter) 
sum. This function is enabled until the digital input is activated. 

6.7

 

CONFIGURABLE INPUT -  REMOTE ON/OFF (ONF) 

This function allows to switch ON and OFF the instrument. 

6.8

 

DIGITAL INPUTS POLARITY  

The digital inputs polarity depends on “

I1P

” and “

I2P

” parameters. 

 

CL

 : the digital input is activated by closing the contact.

 

 

OP

 : the digital input is activated by opening the contact 

7.

 

INSTALLATION AND MOUNTING 

Keyboard 

T620 

shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 

 3 x 

2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L).  
Keyboard 

V620 

shall be mounted on vertical panel, in a 72x56 mm hole, and fixed using screws 

 3 x 2mm. To 

obtain an IP65 protection grade use the front panel rubber gasket (mod. RGW-V).  
Instrument 

XW264K

  shall  be  mounted  in  a  panel  with  two  or  more  screws  and  it  must  be  connected  to  the 

keyboard by means of a two-wire cable (

 1mm).  The temperature range allowed for correct operation is 0 - 60 

°C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases,  excessive  dirt  or  humidity.  The  same 
recommendations apply to probes. Let the air circulate by the cooling holes. 

 

7.1

 

T620 CUT OUT 

 

165

150

31

+0.5

-0

+0

.5

-0

+1

-1

Ø3 x2

 

 
 
 
 
 
 
 
 
 

7.2

 

V620: CUT OUT  

 

56

72

40

83

,5

 

 

7.3

 

MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD 

 

CLICK!

1

2

2

3

3

1

1

 

7.4

 

MOUNTING WITH KEYBOARD COVER OPENING UPWARD 

 

CLICK!

1

2

2

2

3

3

1

1

 

8.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm

for 

the digital and analogue inputs.  Relays and power supply have a Faston connection (6,3mm). Heat-resistant 
cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s 
requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the  power 
connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable 
external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

8.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is 
recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly  measure  the  average  room 
temperature. Place the defrost termination probes among the evaporators fins in the coldest places, where most 
ice  is  formed,  far  from  heaters  or  from  the  warmest  place  during  defrost,  to  prevent  premature  defrost 
termination. 

9.

 

TTL SERIAL LINE 

The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network line 

ModBUS-RTU

 compatible as the Dixell

 

monitoring system XJ500 (Version 3.0). 

The  same  TTL  connector  is  used  to  upload  and  download  the  parameter  list  of  the  “

HOT  KEY

“.  These 

instruments can be ordered with direct serial output 

RS485

 (Optional). 

 

10.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the 

“Hot 

Key” 

and vice-versa. 

10.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert 
the 

“Hot Key” 

and then turn the Wing ON. 

2.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Wing  memory,  the  “

DoL

” 

message is blinking. After 10 seconds the instrument will restart working with the new parameters. 

3.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. The instrument starts regularly with the new programming. 

Содержание Dixell WING XW264K

Страница 1: ...EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temperature is bigger than SdF parameter At the end of defrost the drip time is controlled through the Fdt parameter This instrument can menage a defrost on two different evaporators It waits the defrost end on both evaporators before starting normal regulation 3 4 CONTROL OF EVAP...

Страница 2: ... mode dtE Defrost termination temperature 1st evaporator 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the first evaporator probe which causes the end of defrost dtS Defrost termination temperature 2nd evaporator 50 0 110 0 C 58 230 F Enabled only when the 2nd evaporator probe is present sets the temperature measured by the 2nd evaporator ...

Страница 3: ...unction is enabled until the digital input is activated 6 7 CONFIGURABLE INPUT REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 6 8 DIGITAL INPUTS POLARITY The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING Keyboard T620 ...

Страница 4: ... digits red LED 14 2 mm high Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A compressor relay SPST 8 3 A 250Vac light relay SPST 16 3 A 250Vac or optional relay SPST 16 3 A special for fluorescent lights fans relay SPST 8 3 A 250Vac 1st defrost relay SPDT 8 3 A 250Vac 2nd defrost relay SPDT 8 3 A 250Vac ON OFF SPST relay 16 3 A 250Vac Other output Ala...

Отзывы: