background image

 

1592009550 XW264K GB r1.0 04.08.2015 

                     XW264K 

2/4 

                          XW264K   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2/4/ 

4.6

 

TO START A MANUAL DEFROST  

 

 
1. 

Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

 
1.  Enter  the  Programming  mode  by  pressing  the  Set  and  DOWN  key  for  few 

seconds (

 and 

 start blinking). 

2. 

The instrument will show the first parameter present in “Pr1” 

 
 
 
 

4.8

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “

Pr2

”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

SET

” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

o

 or 

n

 to input the security code in the flashing digit; confirm the figure by pressing “

SET

”. The 

security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

SET

” on the last digit. 

 
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys 
within 30 seconds. 
 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

“SET”

 + 

n

. When a 

parameter is present in “Pr1” LED 

 is on. 

4.9

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

4.10

 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The  “POF”  message  will  be  displayed  and  the  keyboard  is  locked.  At  this  point  it  is  only 
possible the viewing of the set point or the MAX o Min temperature stored and to switch ON 
and OFF the light and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

4.11

 

ON/OFF FUNCTION 

 

 

By  pushing  the 

ON/OFF

  key,  the  instrument  shows  “OFF”  for  5  sec.  and  the  ON/OFF  LED  is 

switched ON. 
During  the  OFF  status,  all  the  relays  are  switched  OFF  and  the  regulations  are  stopped;  if  a 
monitoring system is connected, it does not record the instrument data and alarms. 

N.B. During the OFF status the Light button is active. 

 

4.12

 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr2

” level. 

2. 

Select “

Prd

” parameter with 

o

 or 

n

3. 

Press the “

SET

” key to display “

Pb1” 

label alternate with Pb1 value. 

4. 

Use 

and 

n

 keys to display the other probe values.  

5. 

Press “

SET

” to move to the following parameter. 

5.

 

PARAMETER LIST 

REGULATION 
Hy  Differential: 

(0,1÷25,5°C;  1÷45°F):  Intervention  differential  for  set  point,  always  positive.  Compressor 

Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set 
point. 

LS  Minimum  set  point  limit: 

(-50,0°C

SET;  -58°F÷SET)  Sets  the  minimum  acceptable  value  for  the  set 

point. 

US  Maximum set point limit: 

(SET

110°C; SET÷230°F) Set the maximum acceptable value for set point. 

OdS  Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up of the 

instrument and inhibits any output activation for the period of time set in the parameter. (Light can work) 

AC  Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following restart. 

CCt  Thermostat override:

 (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used, 

for instance, when the room is filled with new products.

 

Con Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is active in case 

of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is off in case of 

faulty thermostat probe. With COF=0 compressor is always active. 

DISPLAY 
CF  Temperature  measurement  unit:

  °C  =  Celsius;  °F  =  Fahrenheit  .  When  the  measurement  unit  is 

changed the SET point and the values  of the regulation parameters have to be modified

 

rES  Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

de

 = 0,1°C; 

in

 = 1 °C  

Lod  Local display : 

select which probe is displayed by the instrument:

  

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = 2

nd

 evaporator probe 

1r2

 = difference between P1 and P2 (P1-P2) 

Red  Remote display : 

select which probe is displayed by the remote display (

XW-REP

)

  

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = 2

nd

 evaporator probe 

1r2

 = difference between P1 and P2 (P1-P2) 

 
 

DEFROST 
tdF   Defrost type:  

rE

 = electrical heater (Compressor OFF) 

rT

 = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on the 

evaporator temperature and “dtE” value. 

in

 = hot gas (Compressor and defrost relays ON) 

EdF  Defrost mode:

    

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

 = 

Smartfrost mode

. The time IdF (interval between defrosts) is increased only when the compressor 

is running (even non consecutively) and only if the evaporator temperature is less than the value in "

SdF

” 

(set point for SMARTFROST).  

SdF  Set  point  for  SMARTFROST

:  (-30

30  °C/  -22

86  °F)  evaporator  temperature  which  allows  the  IdF 

counting (interval between defrosts) in SMARTFROST mode. 

dtE   Defrost termination temperature 1

st

 evaporator:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when the 

evaporator probe is present) sets the temperature measured by the first evaporator probe which causes 
the end of defrost. 

dtS   Defrost termination temperature 2

nd 

evaporator:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when the 

2

nd

 evaporator probe is present) sets the temperature measured by the 2

nd

 evaporator probe which causes 

the end of defrost. 

idF  Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two defrost 

cycles. 

MdF  (Maximum)  duration  of  first  defrost: 

(0÷255  min)  When 

P2P  =  n

,  no  evaporator  probe,  it  sets  the 

defrost duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length for defrost. 

MdS  (Maximum) duration of second defrost: 

(0÷255 min) When 

P3P = n

, no 2

nd

 evaporator probe, it sets 

the defrost duration, when 

P3P = y

, 2

nd

 defrost end based on temperature, it sets the maximum length for 

2

nd

 defrost. 

dFd   Display during defrost:  
 

rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 

dEG

 = “dEG” label;

 

dAd   Defrost  display  time  out:

  (0

255  min)  Sets  the  maximum  time  between  the  end  of  defrost  and  the 

restarting of the real room temperature display. 

dSd Start defrost delay

: ( 0÷99min) This is useful when different defrost start times are necessary to avoid 

overloading the plant.  

Fdt  Drain  down  time:

  (0÷60  min.)  time  interval  between  reaching  defrost  termination  temperature  and  the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that 
might have formed due to defrost.

 

dPO First defrost after start-up:   
 

= Immediately; 

n

 = after the IdF time 

dAF   Defrost delay after fast freezing: 

(0min÷23h 50min)  after a Fast Freezing cycle, the first defrost will be 

delayed for this time. 

FANS 
FnC  Fan operating mode: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd Fan delay after defrost:

 (0÷255 min)

 

The time interval between the defrost end and evaporator fans start.

 

FSt  Fan stop temperature:

 (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe, 

above which the fan is always OFF. 

ALARMS 
ALC  Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU  High temperature alarm setting:

 ( ALC= rE, 0 

 

50°C or 90°F;   ALC= Ab, ALL 

 110°C or 230°F) 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting: (

  ALC = rE , 0 

 50 °C or 90°F; ALC = Ab , - 50°C or -58°F 

 ALU) 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH  Temperature alarm and fan differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for temperature 

alarm set point and fan regulation set point, always positive.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and the 

corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection of the 

temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm delay at the end of defrost: 

(0

255 min) Time interval between the detection of the temperature 

alarm condition at the end of defrost and the alarm signalling. 

dot   Delay of temperature alarm after closing the door : 

(0

255 min) Time delay to signal the temperature 

alarm condition after closing the door. 

doA   Open door alarm delay:

(0÷254min,nu) delay between the detection of the open door condition and its 

alarm signalling: the flashing message “

dA

” is displayed. If 

doA=nu

 the door alarm will be not signalled. 

nPS   Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

did

” interval, 

before signalling the alarm event (I2F= PAL). 

ANALOGUE OUTPUT 4÷20 mA (OPTIONAL) 
AOS  Analogue output start point: 

(-50÷110°C or -58°÷230°F). Sets the temperature at which the analogue 

output begins. 

APB  Analogue output band width

:

 

(-50÷110°C or -58°÷230°F) sets the width of the regulation band for the 

analogue  output.  If  APb  is 

positive

  then  it  is  above  the  start  point  and  the  kind  of  action  is  direct 

(condenser application). If APb is 

negative

 then it is below the start point and the kind of action is inverse 

(evaporator application).  

CAO  Input type for the analogue output: 

four input types can be selected: 

P1

 = room probe temperature; 

P2

 = evaporator probe temperature; 

P3

 = temperature of the third probe 

1r2

= temperature difference between the room probe and the evaporator probe 

 

PROBE INPUTS 
Ot  Thermostat  probe  calibration: 

(-12.0

12.0°C/  -21

21°F)  allows  to  adjust  possible  offset  of  the 

thermostat probe. 

OE    1

st

  Evaporator  probe  calibration: 

(-12.0

12.0°C/  -21

21°F)  allows  to  adjust  possible  offsets  of  the 

evaporator probe. 

O3  2

nd

 Evaporator probe calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offsets of the 2

nd

 

evaporator probe. 

P2P  1

st

 Evaporator probe presence:  

n

= not present: the defrost stops only by time; 

y=

 present: the defrost stops by temperature and time. 

P3P  2

nd

 Evaporator probe presence: n

= not present; 

y=

 present. 

HES  Temperature  increase  during  the  Energy  Saving  cycle  :

  (-30,0°C 

  30,0°C  /  -22÷86°F)  sets  the 

increasing value of the set point during the Energy Saving cycle.  

 
 
 

 

 

 

Содержание Dixell WING XW264K

Страница 1: ...EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temperature is bigger than SdF parameter At the end of defrost the drip time is controlled through the Fdt parameter This instrument can menage a defrost on two different evaporators It waits the defrost end on both evaporators before starting normal regulation 3 4 CONTROL OF EVAP...

Страница 2: ... mode dtE Defrost termination temperature 1st evaporator 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the first evaporator probe which causes the end of defrost dtS Defrost termination temperature 2nd evaporator 50 0 110 0 C 58 230 F Enabled only when the 2nd evaporator probe is present sets the temperature measured by the 2nd evaporator ...

Страница 3: ...unction is enabled until the digital input is activated 6 7 CONFIGURABLE INPUT REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 6 8 DIGITAL INPUTS POLARITY The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING Keyboard T620 ...

Страница 4: ... digits red LED 14 2 mm high Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A compressor relay SPST 8 3 A 250Vac light relay SPST 16 3 A 250Vac or optional relay SPST 16 3 A special for fluorescent lights fans relay SPST 8 3 A 250Vac 1st defrost relay SPDT 8 3 A 250Vac 2nd defrost relay SPDT 8 3 A 250Vac ON OFF SPST relay 16 3 A 250Vac Other output Ala...

Отзывы: