The instrument will show the first parameter present in “Pr1” 

 
 
 
 

4.8

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “

Pr2

”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

SET

” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

or 

n

 to input the security code in the flashing digit; confirm the figure by pressing “

SET

”. The 

security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

SET

” on the last digit. 

 
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys 
within 30 seconds. 
 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

“SET”

 + 

n

. When a 

parameter is present in “Pr1” LED 

 is on. 

4.9

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

or 

n

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

or 

n

 to change its value. 

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

4.10

 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

or 

n

 keys pressed together for more than 3 s the 

and 

n

 keys. 

2.  

The “POF” message will be displayed and the keyboard is locked. At this point it is only 
possible the viewing of the set point or the MAX o Min temperature stored and to switch 
ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

and 

n

 keys pressed together for more than 3s. 

 

4.11

 

ON/OFF FUNCTION 

 

 

By pushing the 

ON/OFF

 key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is 

switched ON. 
During  the  OFF  status,  all  the  relays  are  switched  OFF  and  the  regulations  are stopped;  if a 
monitoring system is connected, it does not record the instrument data and alarms. 

N.B. During the OFF status the Light button is active. 

 

4.12

 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr2

” level. 

2. 

Select “

Prd

” parameter with 

or 

n

3. 

Press the “

SET

” key to display “

Pb1” 

label alternate with Pb1 value. 

4. 

Use 

and 

n

 keys to display the other probe values.  

5. 

Press “

SET

” to move to the following parameter. 

5.

 

PARAMETER LIST 

REGULATION 
Hy  Differential: 

(0,1÷25,5°C;  1÷45°F):  Intervention  differential  for  set  point,  always  positive.  Compressor 

Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set 
point. 

LS  Minimum  set  point  limit: 

(-50,0°C

SET;  -58°F÷SET)  Sets  the  minimum  acceptable  value  for  the  set 

point. 

US  Maximum set point limit: 

(SET

110°C; SET÷230°F) Set the maximum acceptable value for set point. 

OdS  Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up of the 

instrument and inhibits any output activation for the period of time set in the parameter. (Light can work) 

AC  Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following restart. 

CCt  Thermostat override:

 (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used, 

for instance, when the room is filled with new products.

 

Con Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is active in case 

of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is off in case of 

faulty thermostat probe. With COF=0 compressor is always active. 

 
DISPLAY 
CF  Temperature  measurement  unit:

  °C  =  Celsius;  °F  =  Fahrenheit.  When  the  measurement  unit  is 

changed the SET point and the values  of some parameters have to be modified. 

rES  Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

de

 = 0,1°C 

in

 = 1 °C  

Lod  Local display : 

select which probe is displayed by the instrument:

  

P1

 = Thermostat probe 

P2

 = Evaporator probe 

P3

 = not used 

1r2

 = difference between P1 and P2 (P1-P2) 

 

DEFROST 
tdF   Defrost type:  

rE

 = electrical heater (Compressor OFF) 

rT

 = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on the 

evaporator temperature and “dtE” value. 

in

 = hot gas (Compressor and defrost relays ON) 

EdF  Defrost mode:

    

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

 = 

Smartfrost mode

. The time IdF (interval between defrosts) is increased only when the compressor 

is running (even non consecutively) and only if the evaporator temperature is less than the value in "

SdF

” 

(set point for SMARTFROST).  

SdF  Set  point  for  SMARTFROST

:  (-30

30  °C/  -22

86  °F)  evaporator  temperature  which  allows  the  IdF 

counting (interval between defrosts) in SMARTFROST mode. 

 dtE   Defrost  termination  temperature:

  (-50,0÷110,0°C;  -58÷230°F)  (Enabled  only  when  the  evaporator 

probe  is  present)  sets  the  temperature  measured  by  the  evaporator  probe  which  causes  the  end  of 
defrost. 

IdF  Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two defrost 

cycles. 

MdF  (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the defrost 

duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length for defrost. 

dFd   Display during defrost:  
 

rt

 = real temperature;  

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 

dEG

 = “dEG” label;

 

dAd   Defrost  display  time  out:

  (0

255  min)  Sets  the  maximum  time  between  the  end  of  defrost  and  the 

restarting of the real room temperature display. 

Fdt  Drain  down  time:

  (0÷60  min.)  time  interval  between  reaching  defrost  termination  temperature  and  the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that 
might have formed due to defrost.

 

dPO First defrost after start-up:   
 

= Immediately;  

n

 = after the IdF time 

dAF   Defrost delay after fast freezing: 

(0min÷23h 50min)  after a Fast Freezing cycle, the first defrost will be 

delayed for this time. 

 

FANS 
FnC  Fan operating mode: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd  Fan delay after defrost:

 (0÷255 min)

 

The time interval between the defrost end and evaporator fans start.

 

FSt  Fan stop temperature:

 (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe, 

above which the fan is always OFF. 

 

ALARMS 
ALC  Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU  High temperature alarm setting:

  

 

ALC= rE, 0 

 

50°C or 90°F 

 

ALC= Ab, ALL 

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting:

 

 

ALC = rE , 0 

 50 °C or 90°F 

 

ALC = Ab , - 50°C or -58°F 

 ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH  Temperature alarm and fan differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for temperature 

alarm set point and fan regulation set point, always positive.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and the 

corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection of the 

temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm delay at the end of defrost: 

(0

255 min) Time interval between the detection of the temperature 

alarm condition at the end of defrost and the alarm signalling. 

dot   Delay of temperature alarm after closing the door : 

(0

255 min) Time delay to signal the temperature 

alarm condition after closing the door. 

doA   Open door alarm delay:

(0÷254min,nu) delay between the detection of the open door condition and its 

alarm signalling: the flashing message “

dA

” is displayed. If 

doA=nu

 the door alarm will be not signalled. 

nPS   Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

did

” interval, 

before signalling the alarm event (I2F= PAL). 

 

 

PROBE INPUTS 
Ot  Thermostat  probe  calibration: 

(-12.0

12.0°C/  -21

21°F)  allows  to  adjust  possible  offset  of  the 

thermostat probe. 

OE    Evaporator  probe  calibration: 

(-12.0

12.0°C/  -21

21°F)  allows  to  adjust  possible  offsets  of  the 

evaporator probe. 

P2P  Evaporator probe presence:  

n

= not present: the defrost stops only by time; 

y=

 present: the defrost stops by temperature and time. 

HES  Temperature  increase  during  the  Energy  Saving  cycle:

  (-30,0°C 

  30,0°C  /  -22÷86°F)  sets  the 

increasing value of the set point during the Energy Saving cycle.  

 

DIGITAL INPUTS 
odc  Compressor and fan status when open door:

  

no

 = normal; 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

 

F_C

 = Compressor and fan OFF.  

I1P  Door switch input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact. 

I2P  Configurable digital input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact 

 

 

 

I2F  Digital input operating mode:

 configure the digital input function: 

 

EAL 

= generic alarm;

 

 

bAL 

= serious alarm mode;

 

 

PAL 

= Pressure switch;

 

   

dFr 

= Start defrost; 

 

AUS 

= Not used; 

Содержание Dixell Wing XW263L

Страница 1: ...ature is bigger than SdF parameter At the end of defrost the drip time is controlled through the Fdt parameter 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C n fans will switch ON and OFF with the compressor and not run during defrost FnC C y fans will run continuously but not during defrost After defrost there is a timed fan delay allowing for ...

Страница 2: ...s less than the value in SdF set point for SMARTFROST SdF Set point for SMARTFROST 30 30 C 22 86 F evaporator temperature which allows the IdF counting interval between defrosts in SMARTFROST mode dtE Defrost termination temperature 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the evaporator probe which causes the end of defrost IdF Inter...

Страница 3: ...ntil the digital input is activated 6 7 CONFIGURABLE INPUT REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 6 8 DIGITAL INPUTS POLARITY The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING Instruments XW263L shall be mounte...

Страница 4: ...rescent lights fans relay SPST 8 3 A 250Vac defrost relay SPDT 16 3 A 250Vac Other output alarm buzzer Hot Key output Serial output RS485 standard Communication protocol Modbus RTU Data storing on the non volatile memory EEPROM Kind of action 1B Pollution grade normal Software class A Operating temperature 0 60 C Storage temperature 25 60 C Relative humidity 20 85 no condensing Measuring and regul...

Отзывы: