1592028300 Quick reference guide ICX200D EVO rel. 1.0
15/20
5.3.5
Analog output for relay connection (12Vdc coil)
Maximum current to drive the coil of the relay is 40mA.
6 LAN CONNECTION
Through the I/O expansion is possible to increase the number of probes, digital inputs, relay and
analog outputs.
The I/O expansion does not regulate independently but is only an actuator; the configuration of the
inputs and outputs must be made through EI parameters in the IC200 EVO.
The connection to the Ichill is done via LAN.
To configure the expansion is necessary to:
• enable expansion presence via parameter CF78 "Presence expansion card I / O"
• configure the address of communication with the iCHILL with parameter EI01
• configure expansion ICX207D the communication address via dip-switch, which must match the
address set in parameter EI01 of the Ichill
• configure the inputs and outputs using the parameters EI02...EI43 of the Ichill
• connect the iCHILL and expansion according to the diagram showed below
In case of lack or loss of LAN communication, adjustment dell'Ichill is immediately blocked.
The maximum length of the LAN connection is 30 mt.
The address of LAN communication with the controller iCHILL EVO series must be set via dip-switch.