4.1
Power terminal connections
Figure 4-1 Power terminal connections
* When using a 200 V drive on a single phase supply, the live and neutral conductors can be connected to any of the AC connections on the drive.
** This is not required if the optional internal braking resistor is used.
L1
*
L2
*
L2
L1
L3/N
U
V
W
Optional EMC
filter
Optional
line reactor
Fuses
L3
*
Mains
supply
Supply
ground
AC
connections
_
+
DC
DC
High current
-DC connections
+
_
Low voltage
DC (48V)
DST12XX = 200 to 240V 10%
DST14XX = 380 to 480V 10%
±
±
Connectors specification:
Maximum size of power cable
= 4.0mm (10AWG)
Torque setting = 1 N m
2
PE
It is essential that the braking
resistor be protected against
overload caused by a failure
of the brake control. Unless
the resistor has in-built
protection, a circuit like those
shown in Figure 4-1 should
be used, where the thermal
protection device
disconnects the AC supply to
the drive. Do not use AC
relay contacts directly in
series with the braking
resistor circuit, because it
carries DC.
WARNING
Terminals
Torque setting
Power terminals
1.0 N m
(12.1 lb in)
Control terminals
0.2 N m
(1.7 lb in)
Status relay
terminals
0.5 N m
(4.5 lb in)
Ground terminal
screws
4 N m
(35 lb in)
Small ground
terminal screws
2 Nm
(17.7 Ib in)
* *Torque tolerance = 10%
NOTE