Rate input settings
(continued)
Table 1-2:
Setting
Description
Accuracy
±0.03% of calibrated span ±1 count
Temperature drift
Rate display is not affected by changes in temperature.
Low-flow cutoff
0-99,999 (0 disables cutoff function)
Decimal point
Up to four decimal places or none:
4.4444, 33.333, 222.22, 1111.1, or 00000
Calibration
May be calibrated using K-Factor, scale without signal source, or by ap-
plying an external calibration signal.
K-Factor
Field programmable K-Factor converts input pulses to rate in engineer-
ing units. May be programmed from 0.000001 to 9,999,999 pulses/unit.
Calibration range
Input 1 signal must be ≥ 1 Hz; input 2 signal may be set anywhere above
input 1 setting.
Minimum input span is 1 Hz.
An Error message will appear if the input 1 and input 2 signals are too
close together.
Input contact de-
bounce filter
Programmable contact debounce filter. Input signal frequency speed se-
lections of Hi (no filter), Med (250 Hz max input, 2 ms pulse width), and
Low (100 Hz max input, 5 ms minimum pulse width).
Time base
Second, minute, hour, or day
Gate
Low gate: 1-99 seconds; High gate: 2-9,999 seconds
1.4
Rate/
Internal Display
settings
The settings below are rate/
display
specifications for the Internal Display. Except when
noted, all specifications apply to operation at +25°C (+77°F).
Table 1-3: Rate/
Internal display
settings
Setting
Display
Display assignment
The Top display calculates rate or total. The Bottom displays total; total and
units; total and tag; total, total units, and rate units; grand total; grand to-
tal and grand total units; grand total and tag; grand total, grand total units,
and rate units; rate units; rate; rate and total units; rate and rate units; rate
and tag; rate units; total units; a custom tag; or be off (blank).
Rate display units
Gallons, liters, imperial gallons, cubic meters, barrels, bushels, cubic yards,
cubic feet, cubic inches, liquid barrels, beer barrels, hectoliters, or custom.
Rate display time
base
Display rate may be calculated in terms of units per second, minute, hour,
or day.
Total and grand total
display units
Gallons, liters, imperial gallons, cubic meters, barrels, bushels, cubic yards,
cubic feet, cubic inches, liquid barrels, beer barrels, hectoliters, or custom.
Setting is independent for each.
Introduction
User manual
7
Содержание Daniel 1200 Series
Страница 8: ......
Страница 12: ...Contents iv LTM Internal Display ...
Страница 14: ...Plan 2 LTM Internal Display ...
Страница 33: ...Open collector output connections Figure 3 13 Product connections User manual 21 ...
Страница 34: ...Product connections 22 LTM Internal Display ...
Страница 35: ...Part II Install Install User manual 23 ...
Страница 36: ...Install 24 LTM Internal Display ...
Страница 38: ...Installation requirements and limitations 26 LTM Internal Display ...
Страница 40: ...Operate 28 LTM Internal Display ...
Страница 64: ...Setting the toggle time TIME Figure 5 20 Setup and programming 52 LTM Internal Display ...
Страница 98: ...Product advanced features 86 LTM Internal Display ...
Страница 106: ...Startup procedure 94 LTM Internal Display ...
Страница 107: ...Part IV Maintain Maintain User manual 95 ...
Страница 108: ...Maintain 96 LTM Internal Display ...
Страница 113: ...Maintenance User manual 101 ...