Page 14
Product Information / Produktinformation
A6151
Shaft Vibration Monitor
Signal conditioning
Sensor signal outputs
Front sockets SMB and/or z14 / z16*, uncoupled,
open circuit and short circuit proof, non reactive.
Channel 1
−
SENS 1
SMB K1
Channel 2
−
SENS 2
SMB K2
Signal output
−
1 ...
−
24 V; signal 1:1 to sensor input signal
Precision
±
1
%
of f.s.d.
Frequency range
0.2 ... 200 Hz (
−
3 dB)
±
20 %
Per. load resistance
> 100 k
Ω
Internal resistance
1 k
Ω
*Depends on the jumper setting J2.
Dynamic outputs
The AC portion of the sensor signal is output as scaled value.
Channel 1
−
AC1 / Channel 2
−
AC2 z14 / z16* open
−
circuit and short
−
circuit proof, non
−
reactive
Nominal range
0...20 Vpp
Measuring range
Corresponds to the measuring range configured for
the characteristic value, min. 400 mVpp,
max. 8000 mVpp
Precision
±
1
%
of f.s.d.
Frequency range
0.2 Hz ... 200 Hz (
−
3 dB)
±
20 %
Per. load resistance
> 10 k
Ω
Source impedance
10 k
Ω
Internal resistance
Approximately 20
Ω
*Depends on the jumper setting J2.
Scaled d.c. Outputs
The DC portion of the sensor signal (proportional to the static distance sensor / measurement
object) is output as standardized DC voltage NGL
.
Channel 1
−
NGL1 / channel 2
−
NGL2 z12 / d12 open circuit and short circuit proof, non
reactive
Nominal range
0 ... +10 V DC
Measuring range
According to the configured operating range of the
sensor
0 V corresponds to the lower value of the work range
+10 V corresponds to the upper value of the work
range
Precision
/ resolution
±
1
%
of f.s.d. / 12 Bit
Per. load resistance
> 10 k
Ω
Internal resistance
Approximately 50
Ω