• Do not install the regulator in a location where
there can be excessive water accumulation or
ice formation, such as directly beneath a downspout,
gutter, or roof line of building. Even a protective
hood may not provide adequate protection in
these instances.
• Install the regulator so that any gas discharge
through the vent or vent assembly is over 0,91 m
(3 feet) away from any building opening.
Figure 9.
Type CSB400 “Series Monitor” Regulator Downstream Control Line Installation
WIDE-OPEn MOnITORIng REgULaTOR
PRIMaRY WORKIng REgULaTOR
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
Type CSB400ET with External Pressure Registration and
Token Relief Wide-Open Upstream Monitor Regulator
InLET PRESSURE
OUTLET PRESSURE
UPSTREaM
BLOCK VaLVE
DOWnSTREaM
BLOCK VaLVE
Regulators Subjected to Heavy
Snow Conditions
Some installations, such as in areas with heavy snowfall,
may require a hood or enclosure to protect the regulator
from snow load and vent freeze over.
MInIMUM OF 4 X OUTLET
PIPIng DIaMETER