Emerson Copeland ZR16 Скачать руководство пользователя страница 9

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

attenuation  is  not  achieved,  use  a  muffler  with  a  larger  
cross-sectional  area  to  inlet-area  ratio.  The  ratio  should  
be  a  minimum  of  20:1  with  a  30:1  ratio  recommended.  
The  muffler  should  be  from four  to six  inches  (10  -15  
cm) long. 

Air  Conditioning  System  Suction  Line  Noise  and 
Vibration 

Copeland  Scroll  compressors  inherently  have  low  sound  
and  vibration  characteristics.  However,  the  sound  and  
vibration  characteristics  differ  in  some  respects  from  
those  of  reciprocating  compressors.  In  rare  instances,  
these could result in unexpected sound complaints. 

One  difference  is  that  the  vibration  characteristics  of  the  
scroll  compressor,  although  low,  include  two  very  close  
frequencies,  one  of  which  is  normally  isolated  from  the  
shell  by  the  suspension  of  an  internally  suspended  
compressor.  These  frequencies,  which  are  present  in  all  
compressors, may result  in  a  low  level 

“beat” frequency  

that may be detected as noise coming along the suction  
line  into  a  house  under  some  conditions.  Elimination  
of  the 

“beat”  can  be  achieved  by  attenuating  either  

of  the  contributing  frequencies.  The  most  important  
frequencies to avoid are 50 and 60 Hz power supply line  
and  twice-line  frequencies  for  single-phase  compressors  
and  line  frequency  for  three  phase  compressors. This  is  
easily  done  by  using  one  of  the  common  combinations  
of  design  configuration  described  in  Table  2.  The  scroll  
compressor  makes  both  a  rocking  and  torsional  motion,  
and  enough  flexibility  must  be  provided  in  the  line  to  
prevent  vibration  transmission  into  any  lines  attached  to  
the unit. In a split system the most important goal is to  
ensure  minimal  vibration  in  all  directions  at  the  service  
valve  to  avoid  transmitting  vibrations  to  the  structure  to  
which the lines are fastened. 

A second difference  of  the  Copeland  Scroll compressor  
is  that  under  some  conditions  the  normal  rotational  
starting  motion  of  the  compressor  can  transmit  an  

“impact”  noise  along  the  suction  line.  This  may  be  
particularly  pronounced  in  three-phase  models  due  to  
their  inherently  higher  starting  torque.This  phenomenon,  
like  the  one  described  previously,  also  results  from  the  
lack  of  internal  suspension,  and  can  be  easily  avoided  
by  using  standard  suction  line  isolation  techniques  as  
described in Table 2. 

The sound phenomena described above are not usually 
associated  with  heat  pump  systems  because  of  the 
isolation  and  attenuation  provided  by  the  reversing 
valve and tubing bends. 

 

 

 

 

 

 

 

 

©  2013  Emerson  Climate  Technologies,  Inc. 
Printed in the U.S.A. 

 

Mounting Parts 

Table 3  lists  the  mounting parts to  be used  with  
these  compressors.  Many  OEM  customers  buy  the  
mounting parts directly from the supplier, but Emerson

’s  

grommet    design    and    durometer    recommendation  
should  be  followed  for  best  vibration  reduction  through  
the  mounting  feet.  Please  see  AE4-1111  for  grommet  
mounting suggestions and supplier addresses. 

Single Phase Starting Characteristics 

Start  assist  devices  are  usually  not  required,  even  if  
a  system  utilizes  non-bleed  expansion  valves.  Due  to  
the  inherent  design of  the  Copeland  Scroll compressor,  
the  internal  compression  components  always  start  
unloaded even  if system pressures are not balanced. In  
addition,  since  internal  compressor  pressures  are  always  
balanced  at  startup,  low  voltage  starting  characteristics  
are  excellent  for  Copeland  Scroll  compressors.  The  
starting  Locked  Rotor  Amperage  (LRA),  also  referred  
to  as  inrush  current,  is  normally  six  or  more  times  higher  
than  the  rated  running  amperage  of  the  compressor  
and  lasts  from  100  to  300  milliseconds  until  the  rotor  
starts  turning. This  high  starting  current  may  result  in  
significant 

“sag” in voltage where a poor power supply  

is encountered. Low starting voltage reduces the starting  
torque  of  the  compressor  and  subsequently  increases  
the  time  the  compressor  is  in  a  locked  rotor  condition.  
This  could  cause  light  dimming  or  a  buzzing  noise  
where  wire  is  pulled  through conduit.  Start  components  
will  substantially  reduce  start  time  and  consequently  
the  magnitude  and  duration  of  both  light  dimming  and  
conduit  buzzing.  Specified  starting  components  can  be  
found  in  the  Online  Product  Information  section  of  www.  
emersonclimate.com. 

PTC Start Components 

For less severe voltage drops or as a start boost, solid 
state  Positive  Temperature  Coefficient  (PTC)  devices 
rated  from  10  to  25  ohms  may  be  used  to  facilitate 
starting for any of these compressors. 

Electrical Connections 

WARNING 

Molded electrical plug (Emerson p/n 529-0060- 
04  or  OEM  equivalent)  must  be  used  in  all 
applications. 

The  orientation  of  the  electrical  connections  on  the  
Copeland  Scroll  compressors  is  shown  in  Figure  4.  
ZR*K5  compressors  have  one  electrical  connection  
option,  the  one  piece  push-on  molded  electrical  plug.  
ZR*K5 compressors are not available with traditional 

 
 
 
 

9  

Содержание Copeland ZR16

Страница 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Страница 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Страница 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Страница 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Страница 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Страница 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Страница 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Страница 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Страница 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Страница 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Страница 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Страница 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Страница 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Страница 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Страница 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Страница 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Страница 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Страница 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Страница 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Страница 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Страница 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Страница 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Отзывы: