Emerson Copeland ZR16 Скачать руководство пользователя страница 8

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

compressor.  This  results  in  pressures  equalizing  through  
the  compressor  which  can  cause  the  compressor  to  
slowly  rotate  backwards  until  the  pressures  equalize.  
This  condition  does  not  affect  compressor  durability  
but  can  cause  unexpected  sound  after  the  compressor  
is turned off. 

Low Ambient Cut-Out 

A  low  ambient  cut-out  is  not  required  to  limit  air-to  air 
heat  pump  operation.  Air-to-water  heat  pumps  must 
be  reviewed  since  this  configuration  could  possibly  run 
outside  of  the  approved  operating  envelope  (Figure  7) 
causing overheating or excessive wear. 

Oil Type 

Mineral oil is used in the ZR*K5 compressors. Sonneborn 
Suniso  3GS  or  Chevron  Texaco  Capella  WF32  should 
be used if additional oil is needed in the field. 

Polyolester  (POE)oil  isused  in  theZR*K5E  compressors.  
See  the  compressor  nameplate  for  the  original  oil  
charge.  A  complete  recharge  should  be  approximately  
four fluid  ounces (118 ml) less than the  nameplate  value.  
Copeland

™  Ultra  32-3MAF,  available  from  Emerson  

Wholesalers,  should  be  used  if  additional  oil  is  needed  
in  the  field.  Mobil  Arctic  EAL22CC,  Emkarate  RL22,  
Emkarate  32CF  and  Emkarate  3MAF  are  acceptable  
alternatives. 

CAUTION! POE must be handled carefully and  the  
proper  protective  equipment (gloves,  eye protection, 
etc.) must be used when handling POE  lubricant.  POE 
must not come into contact with any surface  or material 
that  might  be  harmed  by  POE,  and  spills  should  be 
cleaned up quickly with paper towels, soap and water. 

Contaminant Control 

Copeland Scroll

 

compressors leave the factory with  a 

miniscule  amount  of  contaminants.  Manufacturing 
processes  have  been  designed  to  minimize  the 
introduction  of  solid    or  liquid  contaminants.  Dehydration 
and purge processes ensure minimal moisture levels in 
the  compressor  and  continuous  auditing  of  lubricant 
moisture  levels  ensure  that  moisture  isn

’t  inadvertently 

introduced into the compressor. 

It  is  generally  accepted  that  system  moisture  levels  
should  be  maintained  below  50  ppm.  A  filter-drier  is  
required  on  all  R-407C  and  POE  lubricant  systems  
to    prevent    solid    particulate    contamination,    oil  
dielectric  strength  degradation,  ice  formation,  and  
oil  hydrolysis,  and  metal  corrosion.  It  is  the  system  
designer

’s  responsibility  to  make  sure  the  filter-drier  is  

adequately sized to accommodate the contaminants 

 

 

 

©  2013  Emerson  Climate  Technologies,  Inc. 
Printed in the U.S.A. 

 

from    system    manufacturing    processes    that    leave  
solid  or  liquid  contaminants  in  the  evaporator  coil,  
condenser  coil,  and  interconnecting  tubing  plus  any  
contaminants  introduced  during  the  field  installation  
process.  Molecular  sieve  and  activated  alumina  are  
two  filter-drier  materials  designed  to  remove  moisture  
and  mitigate  acid  formation.  A  100%  molecular  sieve  
filter  can  be  used  for  maximum  moisture  capacity.  A  
more  conservative  mix,  such  as  75%  molecular  sieve  
and 25%  activated  alumina, should be used for service  
applications. 

Long Line Sets/High Refrigerant Charge 

Some  system  configurations  may  contain  higher-than- 
normal  refrigerant  charges  either  because  of  large  
internal coil volumes or long line sets. If such a system  
also  contains  an  accumulator  then  the  permanent  
loss  of  oil  from  the  compressor  may  become  critical.  
If  the  system  contains  more  than  20  pounds  (9  kg)  
of  refrigerant,  it  is  our  recommendation  to  add  one  
fluid  ounce  of  oil  for  every  5  pounds  (15  ml/kg)  of  
refrigerant  over  this  amount.  If  the  system  contains  
an  accumulator  the  manufacturer  of  the  accumulator  
should be consulted for a pre-charge recommendation. 

Other  system  components  such  as  shell  and  tube  
evaporators  can  trap  significant  quantities  of  oil  and  
should  be  considered  in  overall  oil  requirements.  
Reheat coils  and  circuits  that  are  inactive  during  part  
of  the  normal  cycle  can  trap  significant  quantities  of  
oil if system piping allows the oil to fall out of the  
refrigerant flow  into  an  inactive circuit. The  oil  level must  
be  carefully  monitored  during  system  development,  
and corrective action should be taken if compressor oil  
level  falls  below  the  top  of  the  lower  bearing  bracket  
for  more  than  two  minutes.  The  lower  bearing  bracket  
weld points on the compressor shell can be used as a  
low-oil-level marker. 

Discharge Mufflers 

Flow  through  Copeland  Scroll  compressors  is  semi- 
continuous    with   relatively  low    pulsation.   External  
mufflers,  where  they  are  normally  applied  to  piston  
compressors  today,  may  not  be  required  for  Copeland  
Scroll  compressors.  Because  of  variability  between  
systems,  however,  individual  system  tests  should  be  
performed  to  verify  acceptability  of  sound  performance.  
Whenno  testing  isperformed,mufflersare  recommended  
in  heat  pumps.  A  hollow  shell  muffler  such  as  the  
Emerson  Flow  Controls  APD-1  or  APD-054  will  work  
quite well. The mufflers should be located a minimum of  
six inches (15 cm) to a maximum of 18 inches (46 cm)  
from  the  compressor  for  most  effective  operation.  The  
farther the muffler is placed from the compressor within  
these ranges the more effective it may be. If adequate 

 
 

8  

Содержание Copeland ZR16

Страница 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Страница 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Страница 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Страница 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Страница 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Страница 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Страница 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Страница 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Страница 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Страница 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Страница 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Страница 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Страница 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Страница 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Страница 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Страница 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Страница 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Страница 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Страница 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Страница 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Страница 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Страница 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Отзывы: