© 2017 Emerson Climate Technologies, Inc.

 

AE4-1372 R4 

structure. 

The use of standard soft grommets is not 

recommended

 
Refer 

Figure 2

 for details.  

 

Safety Relief Valves 

 

In a closed system filled with CO

2

 the pressure can rise 

above  725  PSIG  (50  Bar)  under  some  ambient 
conditions.  The  system  must  be  equipped  with  safety 
relief  valves  to 

ensure  that  the  compressor’s  low  side 

and high side pressures are not exceeded (see below). 
If the unit is shut down for service or other reasons, the 
pressure  will  rise  due  to  ambient  heat.  To  prevent  the 
loss of charge at shut down through the relief valves, it 
is  recommended  to  provide  additional  cooling  to  keep 
the pressure below the maximum standstill pressure of 
the  suction  side.  This  can  be  achieved  using  a  small 
auxiliary 

condensing 

unit 

connected 

to 

an 

uninterruptable  power  supply,  that  removes  heat  from 
the R744 liquid receiver. The auxiliary condensing unit 
will  not  be  sufficient  to  maintain  the  low-stage  system 
below  the  Maximum  Allowable  Operation  Pressure  if 
there is a load from the evaporators.  

Refer  to  ANSI/ASHRAE  Standard  15-2016,  Section 
9.7.5 and ANSI/ASHRAE 15 appendix C-2016. 
 
  ZO Maximum Operating pressures 

 Suction side    

400 PSIG (27.6 Bar) 

 Discharge side  

625 PSIG (43.1 Bar) 

 
The requirements for Copeland Scroll compressors with 
CO

2

  per  Underwriters  Laboratory  (UL)  state  that  a 

system with a CO

2

 compressor must be installed with an 

approved  suction  pressure  relief  valve.  ASME  high-
pressure  relief  valves  are  the  only  valves  currently 
approved for use with the Copeland Scroll CO

2

 models. 

The  installation  of  the  above  valve  must  meet  the 
following criteria: 

1.  There  must  be  an  open  flow  path  from  the 

compressor suction sump to the relief valve.  This 
is accomplished by connecting the relief valve to 
the  correct  port  on  the  suction  Rotalock  valve. 
This  port  is  open  to  the  compressor  sump  no 
matter  what  position  the  valve  stem  is  located.  
The relief valve itself can be remotely located as 
long  as  the  path  from  compressor suction  sump 
and the valve is always open. 

2.  This flow path cannot be shut off in any way by a 

valve. 

Figure

 

4

 represents the correct (a) and incorrect (b) way 

to  apply  the  pressure  relief  valve.  Failure  to  apply  the 
high-pressure  relief  valve  correctly  will  void  any  UL 
approval of the system.    
 
The  high-pressure  relief  valve  should  be  located  such 
that the path between the valve and the low side of the 
compressor  is  always  open  and  cannot  be  shut  off  in 
any  way  by  a  valve. 

Note  that  the  valve  opens  only 

once and must be replaced if it opens. 

 
A 500 PSIG (34.5 Bar) high-pressure relief valve kit is 
shipped  with  the  compressor.  Contact  Application 
Engineering for alternative pressure relief valves. 
 
ZO compressors have Rotalock valve fittings. Rotalock 
shut-off valves are available  for  the suction  as well as 
discharge side. Using either straight or angled adaptors 
provides  a  way  to  convert  a  Rotalock  into  a  brazing 
connection. 
 

Tightening Torques

 

Torque 

 

Lbs.

 

Rotalock 1"-1 UNF 

60-70 ft.lb. 

Rotalock 1"1/4-12 UNF 

75-85 ft.lb 

 

High-Pressure Safety Controls 

 

A CO

2

 approved ASME safety pressure relief valve(s) 

with a setting of 500 PSIG (34.5 Bar) is required to be 
pre-installed for standstill conditions.  

 
All sections that can be isolated in the system must have 
relief  valves  pre-installed  by  the  system  manufacturer 
with a 500 PSIG (34.5 Bar) setting.  
 
These  high-pressure  cut-outs  should  have  a  manual 
reset feature. 
 
Additional Requirements: 

Low Pressure Cut-Out on Suction Side:  
80 PSIG (5.5 bar) 

High Pressure Cut-Out on Discharge Side: 625 
PSIG (43.1 Bar) 

Discharge Temperature Protection 

External discharge line thermostat 998-7022-02

 

 

Active Oil Management 

An OMC CO2 electronic oil level management system 
should  be  used  that  is  suitable  for  both  high  and  low- 

CAUTION

 

Содержание Copeland Scroll ZO104KCE

Страница 1: ...pecially designed rubber grommets Kit 527 0157 00 12 Figure 3 Oil Management Control OMC CO2 12 Figure 4 Suction Side Pressure Relief Valve Requirements 13 Figure 5 Three Phase Power Circuit 14 Figure 6 ZO Compressor Operating Envelope 14 Figure 7 Compressor Electrical Connection 14 Revision Tracking R4 Pg 2 New Pressure Safety Icon added Pg 4 Caution tag added to superheat requirement Pg 4 Notes ...

Страница 2: ...e safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to ...

Страница 3: ...and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warning...

Страница 4: ... with R 410A air conditioning compressors which operate at similar pressure levels as CO2 compressors CO2 FOR LOW TEMPERATURE APPLICATIONS SUB CRITICAL DX SYSTEM Figure 1 at the end of this bulletin shows a cascade system diagram with HFC refrigerant for the high side and sub critical CO2 for the low stage refrigerant Nomenclature The model designation contains the following technical information ...

Страница 5: ... port on the suction Rotalock valve This port is open to the compressor sump no matter what position the valve stem is located The relief valve itself can be remotely located as long as the path from compressor suction sump and the valve is always open 2 This flow path cannot be shut off in any way by a valve Figure 4 represents the correct a and incorrect b way to apply the pressure relief valve ...

Страница 6: ...r to Figure 5 for details The terminal box is IP21 for all models from ZO21K to ZO104K The ZO Scroll compressors have three phase induction motors connected in star Copeland Scroll compressors like several other types of compressors will only compress in one rotational direction Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance o...

Страница 7: ...eatedly reach temperatures above 350 F 176 7 C if the compressor cycles on its internal protection devices This only happens under rare circumstances and can be caused by the failure of system components such as the condenser or evaporator fan or loss of charge and depends upon the type of expansion control Care must be taken to ensure that wiring or other materials that could be damaged by these ...

Страница 8: ...l or refrigerant may damage the compressor resulting in failure New Installations The copper coated steel suction tube on scroll compressors can be brazed in approximately the same manner as any copper tube Recommended brazing materials Any SIL FOS material is recommended preferably with a minimum of 5 silver However 0 silver is acceptable Be sure suction tube fitting I D and suction tube O D are ...

Страница 9: ...r may be indicated A current imbalance exceeding 20 of the average on the three phases of a three phase compressor should be investigated further A more comprehensive trouble shooting sequence for compressors and systems can be found in Section H of the Electrical Handbook Form No 6400 8 Before replacing or returning a compressor be certain that the compressor is actually defective As a minimum re...

Страница 10: ...40V 70W 32 Lead Length 995 0018 00 018 0095 04 240V 70W 48 Lead Length 918 0043 00 018 0095 05 480V 70W 48 Lead Length 918 0043 01 018 0095 06 575V 70W 48 Lead Length 918 0043 02 018 0095 07 120V 70W 48 Lead Length 918 0043 07 018 0095 08 400V 70W 48 Lead Length 018 0095 09 277V 70W 21 Lead Length Table 1 ZO Family Models Model Nominal Horse power Displacement CFH Capacity BTU HR EER Weight LB kg ...

Страница 11: ...ime Delay for Low Level Signal 10 seconds Time Delay After Setpoint Recovery 5 seconds Alarm Delay Time Including Alarm Contact 120 seconds Alar Switch SPDT Alarm Contact Rating 10A 120VAC 50 60Hz 5A 250VAC 50 60 Hz 3A 30 VDC Refrigerant Temperature 40 to 180 F 40 C to 82 2 C Maximum Ambient Temperature Storage 40 to 120 F 40 C to 48 9 C Maximum Ambient Temperature Intermittent Duty 40 to 120 F 40...

Страница 12: ... 2017 Emerson Climate Technologies Inc 12 AE4 1372 R4 Figure 3 Oil Management Control OMC CO2 Figure 2 Specially designed rubber grommets Kit 527 0157 00 ...

Страница 13: ... 2017 Emerson Climate Technologies Inc 13 AE4 1372 R4 Figure 4 Suction Side Pressure Relief Valve Requirements ...

Страница 14: ... or services described herein or their use or applicability Emerson Climate Technologies Inc and or its affiliates collectively Emerson as applicable reserve the right to modify the design or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of...

Отзывы: