© 2017 Emerson Climate Technologies, Inc.

 

AE4-1372 R4 

Under  no  circumstances  should  the  hipot  test  be 
performed while the compressor is under a vacuum. 
 

MAINTENANCE AND REPAIR 

Service Procedures 

 

Copeland  Scroll  compressor  functional  check:  A 
functional  compressor  test  during  which  the  suction 
service valve is closed to check how low the compressor 
will pull the suction pressure is not a good indication of 
how  well  a  compressor  is  performing.  Such  a  test  will 
damage a scroll compressor in a few seconds. 
 
The  following  diagnostic  procedure  should  be  used  to 
evaluate  whether  a  Copeland  Scroll  compressor  is 
functioning properly: 

1.  Proper voltage to the unit should be verified. 

2.  Determine  if  the  internal  motor  overload  has 

opened or if an internal motor short or ground fault 
has  developed.  If  the  internal  overload  has 
opened, the compressor must be allowed to cool 
sufficiently to allow it to reset. 

3.  Check that the compressor is correctly wired. 

4.  Proper  indoor  and  outdoor  blower/fan  operation 

should be verified. 

5.  With  service  gauges  connected  to  suction  and 

discharge 

pressure 

fittings, 

turn 

on 

the 

compressor.  If  suction  pressure  falls  below 
normal levels the system is either low on charge 
or there is a flow blockage in the system. 

6.  Three  phase  compressors 

–  If  suction  pressure 

does  not  drop  and  discharge  pressure  does  not 
rise  to  normal  levels,  reverse  any  two  of  the 
compressor  power  leads  and  reapply  power  to 
make sure the compressor was not wired to run in 
reverse.  If  pressures  still  do  no  move  to  normal 
values, either the reversing valve (if so equipped) 
or  the  compressor  is  faulty.  Reconnect  the 
compressor  leads  as  originally  configured  and 
use  normal  diagnostic  procedures  to  check 
operation of the reversing valve. 

7.  To test if the compressor is pumping properly, the 

compressor  current  draw  must  be  compared  to 
published compressor performance curves using 
the  operating  pressures  and  voltage  of  the 
system. If the measured average current deviates 
more than +/-20% from published values, a faulty 
compressor  may  be  indicated.  A  current 
imbalance exceeding 20% of the average on the 

three phases of a three-phase compressor should 
be  investigated  further.  A  more  comprehensive 
trouble-shooting  sequence  for  compressors  and 
systems  can  be  found  in  Section  H  of  the 

Electrical Handbook, Form No. 6400

8.  Before  replacing  or  returning  a  compressor,  be 

certain that the compressor is actually defective. 
As  a  minimum,  recheck  compressors  returned 
from the field in the shop or depot by testing for a 
grounded, open or shorted winding and the ability 
to start. The orange tag in the service compressor 
box should be filled out and attached to the failed 
compressor  to  be  returned.  The  information  on 
this tag is captured in our warranty data base.  

 

Compressor Replacement After a Motor Burn 

In the case of a motor burn, the majority of contaminated 
oil will be removed with the compressor. The rest of the 
oil is cleaned with the use of suction and liquid line filter 
driers.  A  100%  activated  alumina  suction  filter  drier  is 
recommended but must be removed after 72 hours. See 

AE24-1105

 for clean-up procedures and 

AE11-1297

 

for 

liquid  line  filter-drier  recommendations.  It  is  highly 
recommended that the suction accumulator be replaced 
if  the  system  contains  one.  This  is  because  the 
accumulator oil return orifice or screen may be plugged 
with  debris  or  may  become  plugged  shortly  after  a 
compressor failure. This will result in starvation of oil to 
the replacement compressor and a second failure. The 
system  contactor  should  be  inspected  for  pitted/burnt 
contacts  and  replaced  if  necessary.  It  is  highly 
recommended that the run capacitor be replaced when 
a single phase compressor is replaced. 
 

General Guidelines and More Information 

For  general  Copeland  Scroll  compressor  and  CO

2

 

refrigerant please log in to Online Product Information at 

Emerson.com/OPI

,

 refer to the Application Engineering 

bulletins  listed  below,  or  contact  your  Application 
Engineer. 

 

AE4-1294

 

Megaohms 

Values 

of 

Copeland

™ 

Compressors 

AE24-1105

  Principles  of  Cleaning  Refrigeration 

Systems 

AE11-1297

  Liquid Line Filter-Driers 

AE4-1396

 

Application  Guidelines  for  Copeland™ 
Semi-Hermetic 

Compressors 

for 

Transcritical CO2 Applications 

Commercial CO2 Refrigeration Systems

 

Guide

 

Содержание Copeland Scroll ZO104KCE

Страница 1: ...pecially designed rubber grommets Kit 527 0157 00 12 Figure 3 Oil Management Control OMC CO2 12 Figure 4 Suction Side Pressure Relief Valve Requirements 13 Figure 5 Three Phase Power Circuit 14 Figure 6 ZO Compressor Operating Envelope 14 Figure 7 Compressor Electrical Connection 14 Revision Tracking R4 Pg 2 New Pressure Safety Icon added Pg 4 Caution tag added to superheat requirement Pg 4 Notes ...

Страница 2: ...e safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE is used to ...

Страница 3: ...and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warning...

Страница 4: ... with R 410A air conditioning compressors which operate at similar pressure levels as CO2 compressors CO2 FOR LOW TEMPERATURE APPLICATIONS SUB CRITICAL DX SYSTEM Figure 1 at the end of this bulletin shows a cascade system diagram with HFC refrigerant for the high side and sub critical CO2 for the low stage refrigerant Nomenclature The model designation contains the following technical information ...

Страница 5: ... port on the suction Rotalock valve This port is open to the compressor sump no matter what position the valve stem is located The relief valve itself can be remotely located as long as the path from compressor suction sump and the valve is always open 2 This flow path cannot be shut off in any way by a valve Figure 4 represents the correct a and incorrect b way to apply the pressure relief valve ...

Страница 6: ...r to Figure 5 for details The terminal box is IP21 for all models from ZO21K to ZO104K The ZO Scroll compressors have three phase induction motors connected in star Copeland Scroll compressors like several other types of compressors will only compress in one rotational direction Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance o...

Страница 7: ...eatedly reach temperatures above 350 F 176 7 C if the compressor cycles on its internal protection devices This only happens under rare circumstances and can be caused by the failure of system components such as the condenser or evaporator fan or loss of charge and depends upon the type of expansion control Care must be taken to ensure that wiring or other materials that could be damaged by these ...

Страница 8: ...l or refrigerant may damage the compressor resulting in failure New Installations The copper coated steel suction tube on scroll compressors can be brazed in approximately the same manner as any copper tube Recommended brazing materials Any SIL FOS material is recommended preferably with a minimum of 5 silver However 0 silver is acceptable Be sure suction tube fitting I D and suction tube O D are ...

Страница 9: ...r may be indicated A current imbalance exceeding 20 of the average on the three phases of a three phase compressor should be investigated further A more comprehensive trouble shooting sequence for compressors and systems can be found in Section H of the Electrical Handbook Form No 6400 8 Before replacing or returning a compressor be certain that the compressor is actually defective As a minimum re...

Страница 10: ...40V 70W 32 Lead Length 995 0018 00 018 0095 04 240V 70W 48 Lead Length 918 0043 00 018 0095 05 480V 70W 48 Lead Length 918 0043 01 018 0095 06 575V 70W 48 Lead Length 918 0043 02 018 0095 07 120V 70W 48 Lead Length 918 0043 07 018 0095 08 400V 70W 48 Lead Length 018 0095 09 277V 70W 21 Lead Length Table 1 ZO Family Models Model Nominal Horse power Displacement CFH Capacity BTU HR EER Weight LB kg ...

Страница 11: ...ime Delay for Low Level Signal 10 seconds Time Delay After Setpoint Recovery 5 seconds Alarm Delay Time Including Alarm Contact 120 seconds Alar Switch SPDT Alarm Contact Rating 10A 120VAC 50 60Hz 5A 250VAC 50 60 Hz 3A 30 VDC Refrigerant Temperature 40 to 180 F 40 C to 82 2 C Maximum Ambient Temperature Storage 40 to 120 F 40 C to 48 9 C Maximum Ambient Temperature Intermittent Duty 40 to 120 F 40...

Страница 12: ... 2017 Emerson Climate Technologies Inc 12 AE4 1372 R4 Figure 3 Oil Management Control OMC CO2 Figure 2 Specially designed rubber grommets Kit 527 0157 00 ...

Страница 13: ... 2017 Emerson Climate Technologies Inc 13 AE4 1372 R4 Figure 4 Suction Side Pressure Relief Valve Requirements ...

Страница 14: ... or services described herein or their use or applicability Emerson Climate Technologies Inc and or its affiliates collectively Emerson as applicable reserve the right to modify the design or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of...

Отзывы: