background image

 

20 

 

C6.2.27/0716-0219/E 

6.8 

Starting sound

 

During the  very brief start-up, a clicking sound, resulting from initial contacting of the spirals, is 
audible; it is normal. No start-assist devices are required for single-phase compressors, even if a 
system uses non-bleed expansion valves. Due to the design of the Copeland scroll, the internal 
compression components  always start unloaded  even if system pressures are not balanced. In 
addition, since internal compressor pressures are always balanced at start-up, low-voltage starting 
characteristics are excellent for Copeland Scroll compressors. Moreover, if low voltage conditions 
exist at start up, protector trips could result. 

6.9 

Deep

 

vacuum

 

operation 

 

CAUTION 
Vacuum  operation!  Compressor  damage!

  Copeland  Scroll  compressors 

should never be used to evacuate refrigeration or air-conditioning systems. 

 

The scroll compressor can be used to pump down refrigerant in a unit as long as the pressures 
remain within the operating envelope. Low suction pressures will result in overheating of the scrolls 
and  permanent  damage  to  the  compressor  drive  bearing  or  will  cause  the  ASTP  to  activate. 
Copeland Scroll compressors incorporate internal low vacuum protection; the floating seal unloads 
when the pressure ratio exceeds approximately 10:1 for ZB* and 20:1 for ZF* compressors. 

6.10  Shell

 

temperature

 

The top shell and discharge line can briefly but repeatedly reach temperatures above 177°C if the 
compressor cycles on its internal protection devices. This only happens under rare circumstances 
and can be caused by the failure of system components such as the condenser or evaporator fan 
or loss of charge and depends upon the type of expansion control. Care must be taken to ensure 
that wiring or other materials that could be damaged by these temperatures do not come in contact 
with the shell. 

6.11  Pump-down cycle 

To control refrigerant migration a pump-down system should be used. The discharge check valve 
with  a  refrigeration  scroll  compressor  is  designed  for  low  leak  back  and  will  allow  the  use  of  a 
pump-down without the addition of an external check valve. 

If the compressor is stationary for prolonged periods, refrigerant could migrate into the compressor 
and therefore a crankcase heater must be installed. 

If  cold  air  is  constantly  drawn  over  the  compressor  this  could  make  the  crankcase  heater 
ineffective and therefore a pump-down system is recommended. 

For ZB* models care should be taken because the scroll sets  will unload at a  pressure ratio of 
approximately 10:1. If the unit fails to pump down, the pump-down pressure should be reset to a 
higher  value.  The  low-pressure  control  differential  for  all  models  needs  to  be  reviewed  since  a 
relatively lower volume of gas will re-expand from the discharge plenum of the compressor into 
the low side on shutdown.

 

6.12  Minimum run time 

Emerson recommends a maximum of 10 starts per hour. There is no minimum off time because 
Scroll compressors start unloaded even if the system has unbalanced pressures. The most critical 
consideration is the minimum run time required to return oil to the compressor after start-up. To 
establish the minimum run time obtain a sample compressor

 equipped with a sight tube (available 

from Emerson) and install it in a system with the longest connecting lines that are approved for 
the system. The minimum on time becomes the time required for oil lost during compressor start-
up to return to the compressor sump and restore a  minimal oil  level that will ensure oil  pick-up 
through  the  crankshaft.  Cycling  the  compressor  for  a  shorter  period  than  this,  for  instance  to 
maintain  very  tight  temperature  control,  will  result  in  progressive  loss  of  oil  and  damage  to  the 
compressor. 

Содержание Copeland Scroll ZB114K5E

Страница 1: ...Copeland Scroll Compressors for Refrigeration ZB50KCE to ZB114KCE ZB66K5E to ZB114K5E ZF25K5E to ZF54K5E Application Guidelines ...

Страница 2: ...ocation 5 3 1 4 Mounting parts 5 3 2 Brazing procedure 6 3 3 Shut off valves and adaptors 7 3 4 Suction accumulators 7 3 5 Screens 8 3 6 Mufflers 8 3 7 Suction line noise and vibration 8 4 ZF K5E compressors for low temperature applications 9 4 1 ZF K5E compressors with liquid injection 9 4 1 1 DTC valve specifications 9 4 1 2 Valve installation 9 4 1 3 Compressor or valve service 10 4 2 ZF K5E co...

Страница 3: ...n 18 6 4 Preliminary checks Pre starting 18 6 5 Charging procedure 19 6 6 Initial start up 19 6 7 Rotation direction 19 6 8 Starting sound 20 6 9 Deep vacuum operation 20 6 10 Shell temperature 20 6 11 Pump down cycle 20 6 12 Minimum run time 20 6 13 Shut off sound 21 6 14 Frequency 21 6 15 Oil level 21 7 Maintenance repair 22 7 1 Exchanging the refrigerant 22 7 2 Rotalock valves 22 7 3 Replacing ...

Страница 4: ... the Manufacturers Declaration available at www climate emerson com en gb These instructions should be retained throughout the lifetime of the compressor You are strongly advised to follow these safety instructions 1 1 Icon explanation WARNING This icon indicates instructions to avoid personal injury and material damage CAUTION This icon indicates instructions to avoid property damage and possible...

Страница 5: ...other materials in the area of the compressor do not get in touch with it Lock and mark accessible sections CAUTION Overheating Bearing damage Do not operate compressors without refrigerant charge or without being connected to the system CAUTION Contact with POE Material damage POE lubricant must be handled carefully and the proper protective equipment gloves eye protection etc must be used at all...

Страница 6: ...the standard and vapour injection compressors ARI Conditions high medium temperature Evaporating temperature 6 67 C Liquid sub cooling 0K Condensing temperature 48 90 C Ambient temperature 35 C Suction gas return 18 33K ARI Conditions low temperature Evaporating temperature 31 67 C Liquid sub cooling 0K Condensing temperature 40 56 C Ambient temperature 35 C Suction gas return 18 33K 2 3 BOM Varia...

Страница 7: ...e 2 hereunder explains the differences and similarities between ZB KCE and ZB K5E models Equipment ZB KCE compressors ZB K5E compressors Suction and discharge connections Rotalock Rotalock raised suction fitting Oil connections Oil sight glass and Schraeder oil valve Electrical connection Traditional 3 screws Option Molded plug Traditional 3 screws Terminal box protection class IP21 standard IP66 ...

Страница 8: ...be making brazing difficult For all models the suction connection plug must be left in place until the compressor is set into the unit otherwise oil might spill out of the suction connection located low on the shell The compressor plugs must be removed as late as possible before brazing so that the air humidity does not affect the oil characteristics The copper coated steel suction tube should be ...

Страница 9: ...pper tube Recommended brazing materials any Silfos material is recommended preferably with a minimum of 5 silver However 0 silver is acceptable Be sure tube fitting inner diameter and tube outer diameter are clean prior to assembly Using a double tipped torch apply heat in area 1 As the tube approaches brazing temperature move the torch flame to area 2 Heat area 2 until braze temperature is attain...

Страница 10: ...shut off valves can be found in the Spare parts list available at www climate emerson com en gb 3 4 Suction accumulators CAUTION Inadequate lubrication Bearing destruction Minimise liquid refrigerant returning to the compressor Too much refrigerant dilutes the oil Liquid refrigerant can wash the oil off the bearings leading to overheating and bearing failure Irrespective of system charge oil dilut...

Страница 11: ...he scroll compressor although low includes two very close frequencies one of which is normally isolated from the shell by the suspension of an internally suspended compressor These frequencies which are present in all compressors may result in a low level beat frequency that can be detected as noise coming along the suction line into the building under some conditions Elimination of the beat can b...

Страница 12: ...eded and in the required quantity The DTC valve connections are 1 Rotalock for the compressor injection port and 3 8 braze for the connection to the liquid line To prevent a partial or full blockage at the injection port caused by shavings foreign bodies etc a filter should be installed in the liquid line prior to the DTC valve inlet Figure 6 DTC valve assembly 4 1 1 DTC valve specifications Openi...

Страница 13: ...nt evaporated through the heat exchanger is injected into the compressor and provides additional cooling at higher compression ratios Figure 7 Vapour injection line diagram During the sub cooling process a small amount of refrigerant is evaporated and superheated This superheated refrigerant is then injected into the mid compression cycle of the scroll compressor and compressed to discharge pressu...

Страница 14: ...out vapour injection please refer to Technical Information C7 19 1 Vapour Injection Scroll Compressors for Refrigeration 4 3 ZF K5E compressors with wet vapour injection When using scroll compressors in low temperature applications with R407A R407F R448A or R449A and an extended envelope see Chapter 2 4 3 Application limits additional liquid injection with a DTC valve is required in conjunction wi...

Страница 15: ...e phases and the frequency match the nameplate data 5 2 Electrical installation Three phase compressors TF with internal motor protection Power circuit Control circuit Motor terminal connections Three phase compressors are connected to the T1 T2 and T3 connections Legend B1 Room thermostat K1 Contactor B3 Discharge gas thermostat R2 Crankcase heater F1 Fuse S1 Auxiliary switch F3 HP switch F4 LP s...

Страница 16: ... cable glands in order to reach the rated protection class We advise installers service providers to pay attention to this aspect every time they install or replace a Copeland Scroll compressor and to use cable glands according to EN 50262 or any other relevant standard of application in their country region Examples of correct electrical installations are shown in Figures 10 11 Figure 10 Correct ...

Страница 17: ...the Copeland Scroll s inherent ability to handle liquid refrigerant in flooded conditions a crankcase heater is not required as long as the system charge does not exceed 7 5kg If a crankcase heater is fitted it is recommended that the heater be turned on for a minimum of 12 hours prior to starting the compressor This will prevent oil dilution and bearing stress on initial start up The crankcase he...

Страница 18: ...ch applications it is strongly advised to install an additional external discharge thermostat To identify compressors with Advanced Scroll Temperature Protection a label has been added above the terminal box NOTE Depending upon the heat build up in the compressor it may take up to two hours for the ASTP and motor protector to reset 5 5 2 Discharge line thermostat The use of an external discharge t...

Страница 19: ...ody is in upward position on a horizontal tube installation Ensure that the thermostat is not tilted The wire must not be in contact with the top cap of the compressor or the discharge tube Care should be taken to route wires so that they do not come into contact with sharp objects To avoid any impact on tripping temperature by the ambient the discharge line thermostat must be insulated Wrap therm...

Страница 20: ...ion tests if the compressor housing is under vacuum Emerson subjects all Scroll compressors to a high voltage test after final assembly Each motor phase winding is tested according to EN 0530 or VDE 0530 part 1 at a differential voltage of 1000V plus twice the nominal voltage Since high voltage tests lead to premature ageing of the winding insulation further additional tests of that nature are not...

Страница 21: ...nd liquid lines is advisable Pressure must be measured using a vacuum pressure gauge on the access valves and not on the vacuum pump this serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump Evacuating the system only on the suction side of a Scroll compressor can occasionally result in a temporary no start condition for the compressor ...

Страница 22: ...ot good practice to use the compressor to test the high pressure switch function on the production line Switch function can be tested with nitrogen prior to installation and wiring can be checked by disconnecting the high pressure switch during the run test 6 7 Rotation direction Scroll compressors like several other types of compressors will only compress in one rotational direction Direction of ...

Страница 23: ...that could be damaged by these temperatures do not come in contact with the shell 6 11 Pump down cycle To control refrigerant migration a pump down system should be used The discharge check valve with a refrigeration scroll compressor is designed for low leak back and will allow the use of a pump down without the addition of an external check valve If the compressor is stationary for prolonged per...

Страница 24: ...ign inverter selection and operating envelopes at various conditions Only frequencies from 50 Hz to 60 Hz are acceptable Operation outside this frequency range is possible but should not be done without specific Application Engineering review The voltage must vary proportionally to the frequency If the inverter can only deliver a maximum voltage of 400V the amps will increase when the speed is abo...

Страница 25: ...ris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure When a single compressor or tandem is exchanged in the field it is possible that a major portion of the oil may still be in the system While this may not affect the reliability of the replacement compressor the extra oil will add to rotor drag and in...

Страница 26: ... there is uncertainty as to the moisture content in the system an oil sample should be taken and tested for moisture Sight glass moisture indicators currently available can be used with the HFC refrigerants and lubricants however the moisture indicator will just show the moisture content of the refrigerant The actual moisture level of POE would be higher than the sight glass indicates This is due ...

Страница 27: ...frigerant according to national legislation and regulations Dispose of compressor according to national legislation and regulations DISCLAIMER 1 The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability 2 Emerson Climate T...

Страница 28: ...81 00 Fax 971 4 886 54 65 mea sales emerson com ASIA PACIFIC Suite 2503 8 25 F Exchange Tower 33 Wang Chiu Road Kowloon Bay Kowloon Hong Kong Tel 852 2866 3108 Fax 852 2520 6227 CZECH REPUBLIC Hajkova 22 CZ 133 00 Prague Tel 420 733 161 651 Fax 420 271 035 655 Pavel Sudek emerson com SPAIN PORTUGAL C Pujades 51 55 Box 53 ES 08005 Barcelona Tel 34 93 412 37 52 iberica sales emerson com RUSSIA CIS D...

Отзывы: