Installation Instructions: XJ Scroll Condenser to E2
Document Part # 026-4909 Rev 1 20-OCT-2011
Page 8 of 13
©2011 Emerson Climate Technologies, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
technical bulletin
Network Connection to E2
Connecting an XJ Scroll Condenser to an E2
unit requires the E2 to be version 2.84 or
above. Contact Retail Solutions for upgrade
information if the controller is a version
before 2.84.
An E2 has up to three COM ports that can be
assigned for XJ Scroll board communication
(COM2, an RS485 port on the E2 power
interface board, and COM4 and COM6,
which are external RS485 cards). COM ports
can only be used for one function; in other
words, if COM2 is set up as the I/O network,
you cannot connect XJ Scroll boards to
COM2. If COM2 is not used for XJ Scroll
boards, ensure your E2 is equipped with an
RS485 COM Card
(P/N 637-4890)
and config-
ured in E2 General Services (
or
press
+
, Serial tab)
to enable COM4.
Connect the network cable to the three-terminal connector on the COM port that has been
configured as XJ Scroll.
When the E2 is at one end of the daisy chain, terminate the E2 with all three jumpers in the
terminated (UP) position.
E2 Setup of XJ Scroll Condensers
Set Up Network Ports
Before communicating to an XJ Scroll, the port on the E2 that has the cable connected to the
XJ Scroll Condenser must be configured to use the XJ Scroll Condenser.
1. Log in to the E2 with Level 4 access.
2. Press
followed by
-
General Controller Info
.
3. Press
+
to open the
Serial
tab of the General Controller Info setup screens:
E2 PIB COM PORT ASSOCIATIONS
COM1
COM4
COM6
COM2
Serial Device
RS485 COM Port
(2 Connectors)
RS485 COM Card
(2 Connectors)
Serial Device
RS232 Port
POWER INTERFACE BOARD
(PIB)
E2 Modem/Expansion
COM Card Mounted
Above PIB
Plug-In
Modem
Card
COM3
E2 Enclosure (Right Side)
RS485
RS232
Figure 4 - Location of E2 COM Ports
Содержание Copeland Scroll Series
Страница 9: ... 2017 Emerson Climate Technologies Inc 9 AE5 1377 R3 Figure 1 Nomenclature and Features ...
Страница 10: ... 2017 Emerson Climate Technologies Inc 10 AE5 1377 R3 Figure 2 Physical and Installation Requirements ...
Страница 14: ... 2017 Emerson Climate Technologies Inc 14 AE5 1377 R3 Drawings ...
Страница 15: ... 2017 Emerson Climate Technologies Inc 15 AE5 1377 R3 ...
Страница 16: ... 2017 Emerson Climate Technologies Inc 16 AE5 1377 R3 ...
Страница 17: ... 2017 Emerson Climate Technologies Inc 17 AE5 1377 R3 ...
Страница 18: ... 2017 Emerson Climate Technologies Inc 18 AE5 1377 R3 ...
Страница 19: ... 2017 Emerson Climate Technologies Inc 19 AE5 1377 R3 ...
Страница 20: ... 2017 Emerson Climate Technologies Inc 20 AE5 1377 R3 ...
Страница 21: ... 2017 Emerson Climate Technologies Inc 21 AE5 1377 R3 ...
Страница 22: ... 2017 Emerson Climate Technologies Inc 22 AE5 1377 R3 ...
Страница 23: ... 2017 Emerson Climate Technologies Inc 23 AE5 1377 R3 ...
Страница 39: ...APPENDIX 2 ...