PN 07 - 19 December 2012
IN THIS ISSUE
XWEB WITH COPELAND XJ
SCROLL CONDENSER UNITS
XJ Scroll One-Way Communication Board Configuration
XJ Scroll address is determined using dip switches on the One-Way Communication Board.
Switch numbers 1 to 6 set the slave address. Switch number 7 will set the Baud rate and
switch number 8 will set the parity. The range of allowable addresses is 1 through 63. Refer
to Table below for settings.
Make sure that you are setting parity to “No Parity” and baud rate to “9.6Kbps”.
pag. 3 di 6
Page 3 of 6