C6.1.6/0117-1017/E
49
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
D06
Delay between two different loads start-up
[0÷99.5] min, resolution 10 sec
10
N.V.
N.V.
N.V.
D07
Delay between two different loads switch-off
[0÷99.5] min, resolution 10 sec
10
N.V.
N.V.
N.V.
D08
Minimum time a stage stays switched on
[0÷99.5] min, resolution 10 sec
0
L2
L2
L2
D09
Maximum time a stage stays switched on
[0.00÷24.00] hours, resolution 10 min
0
L2
L2
L2
D10
don delay enabled also for the first request
No (0-NO) - Yes (1-YES)
NO
L2
N.V.
N.V.
D11
doF delay enable also for the first switching off No (0-NO) - Yes (1-YES)
NO
L2
N.V.
N.V.
D12
Low suction pressure alarm delay
0 to 999 sec
0
L2
L2
L2
D13
Low suction pressure error signal enabling
No (0-NO) - Yes (1-YES)
YES
L2
L2
L2
D14
Compressor minimum off time for high-
pressure switch protection
0 to 15 min
5
L2
L2
L2
D15
Number of high-pressure switch activations
before compressor lockout
0 to 15
7
L2
L2
L2
D16
Bump start enable
No (0-NO) - Yes (1-YES)
NO
N.V.
N.V.
N.V.
D17
Bump start ambient threshold
-40°C to 110°C
0
N.V.
N.V.
N.V.
D18
Compressor stop time for next bump start
0 hour to 23 hours and 50 minutes
1 hour
N.V.
N.V.
N.V.
D19
Compressor on time during bump function
1 to 15 sec
2
N.V.
N.V.
N.V.
D20
Compressor off time during bump function
1 to 15 sec
15
N.V.
N.V.
N.V.
D21
Number of cycles during bump start
1 to 15
3
N.V.
N.V.
N.V.
D22
DLT alarm temperature to stop compressor
-40°C to 180°C
140
L2
L2
L2
D23
DLT alarm recover temperature to turn on
compressor
-40°C to 180°C
90
L2
L2
L2
D24
DLT alarm activation delay
0 to 255 sec
30
L2
L2
L2
D25
Compressor minimum off time for DLT Alarm
0 to 255 min
5
L2
L2
L2
D26
Number of DLT alarm activations before
compressor lockout
0 to 15
10
L2
L2
L2
D27
Time to ignore low DLT sensor error at start-
up
0 to 255 min
5
L2
L2
L2
D28
Compressor minimum off time for low
pressure switch protection
0 to 15 min
3
L2
L2
L2
D29
Low-pressure alarm value (from serial number
16EZ08855M onwards)
0 to 15 bar
0.5
L1
L1
L1
D30
Cold start enable
Disable (0) - Enable (1)
Disable
N.V.
N.V.
N.V.