For  three  phase  Copeland  Discus  digital  compressors: 
the compressor’s T1, T2 and T3 wires must be routed 
through  the  holes  in  the  Digital  Compressor  Controller 
module  marked  “T1,”  “T2”  and  “T3.”  The  Digital 
Compressor Controller module is phase insensitive and 
will NOT detect reverse phasing of the compressor. 

NOTE:

  Do  not  bundle  low  voltage  wires  with 

compressor power or high voltage wires. 

NOTE: 

Attach  cable  ties  through  loops  on  side  of  the 

housing for wire strain relief. 

Control Requirements with CoreSense 
Diagnostics 

Discus  Digital  compressors  are  also  compatible  with 
CoreSense

 Diagnostics and newer technology. Using 

CoreSense  Diagnostics  eliminates  the  need  for  the 
separate  Copeland  Digital  Compressor  Controller  in 
system  wiring. 

NOTE:  Discus  digital  is  not 

compatible with Intelligent Store Discus 1.0.

 

Master Controller 

The Copeland Discus digital compressor is approved for 
use  with  E2  v2.3  facility  management  system  and 
higher. The compressor should be specifically identified 
as digital in the E2 in the staging setup. For any other 
system  controllers  please  check  with  your  Application 
Engineer.  If  using  a  Discus

  digital  compressor  with 

CoreSense  Diagnostics  with  the  E2  system  controller, 
E2  v  2.6  or  newer  is  required.  You  do  not  need  the 
Digital  Compressor  Controller  when  using  CoreSense 
Diagnostics.  For  more  information  on  the  E2  system 
controller access the E2 user manual at: 

http://www.emersonclimate.com/en-
us/Products/Controls/Facility_Controls/E2/Pages/e2.as
px

  

For  additional  information  on  CoreSense  Diagnostics 
refer  to  the  application  guidelines  in 

AE8-1368

CoreSense Diagnostics v2.11

Recommended Application Settings for the 
Modulation on Copeland Discus Digital 
Compressors 

The  system  design  should  follow  the  required  and 
recommended  guidelines  as  detailed  in  the  various 
Application Engineering bulletins, which can be found 
on 

the 

website 

at 

Emerson.com/OPI

.

 

The 

compressor  motor  should  only  be  restarted  after  an 
appropriate  time  delay.  The  digital  modulation  cycle 

time  recommended  is  20  seconds;  for  other  values, 
check with your Application Engineer. 

The minimum load and unload times should be limited 
to 2  seconds.  These  described  load  and  unload  times 
will give the compressor an operating range during a 20 
second cycle from 10% load up to 90% load (on 3D only 
– 4D and 6D minimum percent capacity would be 50%, 
33%  or  67%  depending  on  compressor  configuration). 
The compressor can also operate at a 100% load for the 
full modulation sequence. The 2 second minimum times 
will give the unloader piston assembly time to both load 
and unload fully. 

If the load required is less than 10% minimum percent 
capacity of the digital compressor (10% for 3D, 50% for 
4D or 33% or 67% for 6D) the compressor motor should 
be  shut  down.  Restarting  of  the  compressor  will  be 
governed by the capacity rising above the10% minimum 
percent capacity or more based on a modulation time of 
20 seconds, and by the motor starting logic. 

Solenoid Valve/Gaskets 

Due  to  the  high  life  cycle  requirements  in  a  hot  gas 
environment, a special valve has been developed. Due 
to  reliability  requirements,  only  Emerson  solenoid 
valves may be used. All compressor warranties are null 
and void if the Emerson valve is not used. Solenoid coils 
will  be  sold  separately  for  all  non-CoreSense 
Diagnostics  orders.  See 

Table

 

1

  for  the  appropriate 

solenoid  kit  number  for  your  application.

 

Furthermore, 

Discus digital compressors use special head and valve 
plate  gaskets  which  have  modifications  to  ensure  gas 
flow  for  proper  digital  modulation.  Only  Emerson 
approved  gaskets  may  be  used.  All  compressor 
warranties are null and void if the Emerson gaskets are 
not used.  

Table 1 

Solenoid Coil Voltage

 

Kit Part Number

 

24V 

923-0084-00 

120V 

923-0084-01 

240V 

923-0084-02 

 

Thermistor 

The thermistor must conform to the curve characteristics 
outlined i

Table

 

2

. The table expresses the ratio of the 

resistance  at  the  indicated  temperature  and  the 
resistance  at  25°C  (77°F).  The  resistance  at  25°C 
(77°F)  is  86K  ohms  nominal.  The  curve  fit  is:  Ratio  = 

Содержание COPELAND 3DSDR17ME-TFD

Страница 1: ... and More Information 10 TABLE OF FIGURES Figure 1 Copeland Discus Digital Unloaded Operation Shown on a Copeland 3D Discus 4 Figure 2 Copeland Discus Digital Loaded View shown on a Copeland 3D Discus 5 Figure 3 Typical Modulated Power Reduction for 3D Discus Digital 6 Figure 4 Loaded vs Time 6 Figure 5 Copeland R Digital Compressor Controller 7 Figure 6 Compressor Controller Wiring Diagram 7 Revi...

Страница 2: ... lifetime of the compressor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not ...

Страница 3: ...and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warning...

Страница 4: ...he 3D By varying the percentage of duty cycle that the compressor is loaded and unloaded capacity control between 10 and 100 can be achieved During blocked suction operation the flow of suction gas is blocked to all cylinders on a single bank therefore there is no gas to compress and the power consumption is significantly lower The unloader piston mechanism that controls flow of suction gas into t...

Страница 5: ...iscus compressor envelopes The head fan return gas and oil cooler requirements are the same as those for the standard Discus compressors Control Capacity modulation is achieved by energizing and de energizing the solenoid valve When the solenoid valve is de energized the compressor capacity is 100 When the solenoid valve is energized the compressor capacity is zero Therefore the capacity achieved ...

Страница 6: ... 2017 Emerson Climate Technologies Inc 6 AE21 1355 R4 Figure 3 Typical Modulated Power Reduction for 3D Discus Digital Figure 4 Loaded vs Time ...

Страница 7: ... Digital Compressor Controller inside the electrical enclosure near the compressor contactor wire routing for compressor power wiring will be easier in this position The maximum wire terminal screw torque is 7 in lbs The Digital Compressor Controller will operate in any mounting orientation where the green POWER LED is at the top Mount the Digital Compressor Controller such that all LEDs are visib...

Страница 8: ... Emerson com OPI The compressor motor should only be restarted after an appropriate time delay The digital modulation cycle time recommended is 20 seconds for other values check with your Application Engineer The minimum load and unload times should be limited to 2 seconds These described load and unload times will give the compressor an operating range during a 20 second cycle from 10 load up to ...

Страница 9: ...e on a 4D you have continuous capacity from 50 to 100 therefore when selecting a 4D digital compressor you should have a fixed compressor behind it that is 50 100 of the full load of the digital compressor Example1 You have selected a 4DAXF47KL TSK This compressor capacity is about 47 000 Btu per hour 50 capacity is about 23 500 Then D 47 000 BTU h As the first fixed capacity compressor you must c...

Страница 10: ...ow or contact your Application Engineer AE4 1135 Cooling Requirements for Copelametic and Copeland Discus Compressors AE4 1287 Copeland Discus Demand Cooling AE4 1334 Low Condensing Temperature Bulletin AE8 1328 Copeland Digital Compressor Controller AE8 1368 CoreSense Diagnostics v2 11 for Copeland Discus Compressors AE4 1357 Upgrade Procedures for Parallel Applications Using Digital Capacity Con...

Страница 11: ...4012 167 C 0 01250 15 C 8 29400 30 C 0 80560 75 C 0 14800 120 C 0 03900 168 C 0 01226 14 C 6 89570 31 C 0 77200 76 C 0 14310 121 C 0 03793 169 C 0 01203 13 C 6 52190 32 C 0 74010 77 C 0 13850 122 C 0 03690 170 C 0 01180 12 C 6 17110 33 C 0 70960 78 C 0 13400 123 C 0 03590 171 C 0 01157 11 C 5 84150 34 C 0 68060 79 C 0 12970 124 C 0 03494 172 C 0 01134 10 C 5 53190 35 C 0 65300 80 C 0 12550 125 C 0...

Отзывы: