Enter the motor rated power factor cos
ϕ
(taken from the motor name plate).
L1
:
Level 1 access - only the first 10 parameters can be accessed
L2
:
Level 2 access - All parameters from 01 to 60 can be accessed
L3
:
Level 3 access - All parameters from 01 to 95 can be accessed
LoC
: Used to lock a security code in the drive. See section 5.6
page 24 for further details.
6.2
Parameter descriptions - Level 2
*Jog can be used without the /Stop being active.
diS
: Mechanical brake software disabled
rEL
: Mechanical brake software enabled. Brake control via relay T5 & T6. The digital
output on terminal B3 is automatically programmed as a drive ok output.
d IO
: Mechanical brake software enabled. Brake control via digital output B3. The relay
outputs on terminals T5 and T6 are automatically programmed as a drive ok
output.
USEr
:Mechanical brake software enabled. Brake control to be programmed by user.
The relay and digital output are not programmed. The user should programme the
brake control to either the digital output or relay. The output not programmed to
the brake control can be programmed to indicate the required signal. (See
Commander SK Advanced User Guide
.)
No
Function
Range
Defaults
Type
09
Motor power factor
0 to 1
0.85
RW
The power factor value could be automatically changed after a rotating autotune. See Pr
NOTE
No
Function
Range
Defaults
Type
10
Parameter access
L1, L2, L3, LoC
L1
RW
No
Function
Range
Defaults
Type
11
Start/Stop logic select
0 to 6
Eur: 0, USA: 4
RW
Pr 11
Terminal B4
Terminal B5
Terminal B6
Latching
0
Enable
Run Forward
Run Reverse
No
1
/Stop
Run Forward
Run Reverse
Yes
2
Enable
Run
Forward / Reverse
No
3
/Stop
Run
Forward / Reverse
Yes
4
/Stop
Run
Jog*
Yes
5
User programmable Run Forward
Run Reverse
No
6
User Programmable User Programmable User Programmable
User Programmable
A change to Pr
11
is set by pressing the
MODE key on exit from parameter edit mode.
The drive must be disabled, stopped or tripped for a change to take place. If Pr
11
is
changed while the drive is running, when the
MODE key is pressed on exit from
parameter edit mode, Pr
11
will change back to its previous value.
NOTE
M
M
No
Function
Range
Defaults
Type
12
Brake controller enable
diS, rEL, d IO, USEr
diS
RW
A change to Pr
12
is set by pressing the
MODE key on exit from parameter edit mode.
The drive must be disabled, stopped or tripped for a change to take place. If Pr
12
is
changed while the drive is running, when the
MODE key is pressed on exit from
parameter edit mode, Pr
12
will change back to its previous value.
NOTE
M
M