Status LED

Status LED Description

 Status LED Troubleshooting Information

Yellow “ALERT”

Flash Code 3

Short Cycling

Compressor is running 

only briefl y

1. Thermostat demand signal is intermittent

2. Time delay relay or control board defective

3. If high pressure switch present go to Flash Code 2 information

4. If low pressure switch present go to Flash Code 1 information

Yellow “ALERT”

Flash Code 4

Locked Rotor

1.Run capacitor has failed

2.Low line voltage (contact utility if voltage at disconnect is low)

•Check wiring connections

3.Excessive liquid refrigerant in compressor

4.Compressor bearings are seized 

•Measure compressor oil level

Yellow “ALERT”

Flash Code 5

Open Circuit

1.Outdoor unit power disconnect is open

2.Compressor circuit breaker or fuse(s) is open

3.Compressor contactor has failed open

•Check compressor contactor wiring and connectors

•Check for compressor contactor failure (burned, pitted or open)

•Check wiring and connectors between supply and compressor

•Check for low pilot voltage at compressor contactor coil

4.High pressure switch is open and requires manual reset

5.Open circuit in compressor supply wiring or connections

6.Unusually long compressor protector reset time due to  

extreme ambient temperature

7.Compressor windings are damaged

•Check compressor motor winding resistance

Yellow “ALERT”

Flash Code 6

Open Start Circuit

Current only in run circuit

1.Run capacitor has failed

2.Open circuit in compressor start wiring or connections

•Check wiring and connectors between supply and the    

 

compressor “S” terminal

3.Compressor start winding is damaged

•Check compressor motor winding resistance

Yellow “ALERT”

Flash Code 7

Open Run Circuit

Current only in start circuit

1.Open circuit in compressor run wiring or connections 

•Check wiring and connectors between supply and the 

compressor “R” terminal 

 

2.Compressor run winding is damaged

•Check compressor motor winding resistance

Yellow “ALERT”

Flash Code 8

Welded Contactor

Compressor always runs

1.Compressor contactor has failed closed

2.Thermostat demand signal not connected to module

Yellow “ALERT”

Flash Code 9

Low Voltage

Control circuit < 17VAC

1.Control circuit transformer is overloaded

2.Low line voltage (contact utility if voltage at disconnect is low)

•Check wiring connections

Flash Code number corresponds to a number of LED fl ashes, followed by a pause and then repeated.
TRIP and ALERT LEDs fl ashing at same time means control circuit voltage is too low for operation.

Содержание Comfort Alert 543-0033-00

Страница 1: ...1 User s Manual 543 0033 00 943 0033 00 ...

Страница 2: ... system condition through a unique flash code The ALERT LED will flash a number of times consecutively pause and then repeat the process The number of consecutive flashes defined as the Flash Code correlates to a particular abnormal condition Detailed descriptions of specific ALERT Flash Codes are shown in two tables on pages 8 and 9 of this manual TRIP LED Red indicates there is a demand signal from ...

Страница 3: ...ompressor contactor wire routing for compressor run common and start wires will be easier in this position Mount the Comfort Alert module so all LEDs are visible from a comfortable viewing position The module will operate in any mounting orientation For ease of reading labels the module should be oriented so that the green POWER LED is at the top WARNING Hazardous voltage inside air conditioning s...

Страница 4: ...spare wires in the thermostat cable to bring power to the module Connect the other end of the spare wire to R at the indoor unit or thermostat Refer to wiring schematic in Figure 4 and 5 Thermostat Demand Wiring The ComfortAlert module requires a thermostat demand signal to operate properly The thermostat demand signal input labeled Y on the module should always be connected to the compressor cont...

Страница 5: ...033 00 Y2 C R L Y1 Indoor Unit Terminal Block Two Stage Indoor Thermostat Ultra Tech Solenoid 529 0369 00 HPCO HTCO CC LPCO Y2 Y L R C DC SOL Y2 C R L Y1 Comfort Alert Diagnostics Module 543 0033 00 Y2 C R L Y1 Indoor Unit Terminal Block Defrost Board Schematic Abbrevation Descriptions HTCO High Temperature Cut Out Switch CC Compressor Contactor HPCO High Pressure Cut Out Switch LPCO Low Pressure ...

Страница 6: ...hite Rodgers thermostats an icon on the thermostat display will flash at the same rate as the Comfort Alert yellow Alert LED An advanced option on these thermostats is to lock out the compressor when certainAlert codes are detected indicating impending compressor damage Refer to White Rodgers thermostat manuals for more information DC SOL Connection The two pin DC SOL connector provides a connectio...

Страница 7: ...t LED will begin flashing a Code 8 indicating a Welded Contactor Disconnect power from the compressor and 24VAC from Comfort Alert While Comfort Alert is off reattach the wire to the Y terminal Reapply power to compressor and 24VAC to Comfort Alert the yellow Alert LED will flash the previous code 8 for 1 minute and then turn off If the yellow LED does not function as described refer to Table 1 to v...

Страница 8: ...ck for excessively low thermostat setting Check evaporator airflow coil blockages or return air filter Check ductwork or registers for blockage 4 Faulty metering device Check TXV bulb installation size location and contact Check if TXV fixed orifice is stuck closed or defective 5 Condenser coil is dirty 6 Liquid line restriction filter drier blocked if present in system 7 Compressor Second Stage Coolin...

Страница 9: ... wiring or connections 6 Unusually long compressor protector reset time due to extreme ambient temperature 7 Compressor windings are damaged Check compressor motor winding resistance Yellow ALERT Flash Code 6 Open Start Circuit Current only in run circuit 1 Run capacitor has failed 2 Open circuit in compressor start wiring or connections Check wiring and connectors between supply and the compresso...

Страница 10: ... OK coil Verify voltage at contactor coil falls below 0 5VAC when off Verify 24VAC is present across Y and C when thermostat demand signal is present If not R and C are reverse wired TRIP LED and ALERT LED Verify R and C terminals are supplied with 19 28VAC flashing together ALERT Flash Code 3 Verify Y terminal is connected to 24VAC at contactor coil Compressor Short Cycling Verify voltage at conta...

Страница 11: ...of the product use on improper voltage or current use contrary to the operating instructions disassembly repair or alteration by anyone other than Copeland Corporation Further the warranty does not cover acts of God such as fire flood hurricanes and tornadoes COPELAND CORPORATION MAKES NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE WITH RESPECT TO THE COMFORT ALERT MODULE...

Страница 12: ...ents Pending Form No 2004ECT 208 R2 Revised 3 05 Emerson Climate Technologies is a service mark and a trademark of Emerson Electric Co Comfort Alert is a trademark of Copeland Corporation Printed in the U S A 2005 2004 Copeland Corporation ...

Отзывы: