Status LED
Status LED Description
Status LED Troubleshooting Information
Green “POWER”
Module has power
Supply voltage is present at module terminals
Red “TRIP”
Thermostat demand signal Y is
present, but the compressor is
not running
1.Compressor protector is open
•Check for high head pressure
•Check compressor supply voltage
2.Outdoor unit power disconnect is open
3.Compressor circuit breaker or fuse(s) is open
4.Broken wire or connector is not making contact
5.Low pressure switch open if present in system
6.Compressor contactor has failed open
Yellow “ALERT”
Flash Code 1
Long Run Time
Compressor
is running extremely long run
cycles
1.Low refrigerant charge
2.Evaporator blower is not running
•Check blower relay coil and contacts
•Check blower motor capacitor
•Check blower motor for failure or blockage
•Check evaporator blower wiring and connectors
•Check indoor blower control board
•Check thermostat wiring for open circuit
3.Evaporator coil is frozen
•Check for low suction pressure
•Check for excessively low thermostat setting
•Check evaporator airfl ow (coil blockages or return air fi lter)
•Check ductwork or registers for blockage
4.Faulty metering device
•Check TXV bulb installation (size, location and contact)
•Check if TXV/fi xed orifi ce is stuck closed or defective
5. Condenser coil is dirty
6. Liquid line restriction (fi lter drier blocked if present in system)
7. Compressor Second Stage Cooling Wiring
•Solenoid plug not connected
•Y2 not wired at Comfort Alert
8. Thermostat is malfunctioning
•Check thermostat sub-base or wiring for short circuit
•Check thermostat installation (location, level)
9.Comfort Alert failure
Yellow “ALERT”
Flash Code 2
System Pressure Trip
Discharge or suction
pressure out of limits or
compressor overloaded
1. High head pressure
•Check high pressure switch if present in system
•Check if system is overcharged with refrigerant
•Check for non-condensable in system
2. Condenser coil poor air circulation (dirty, blocked, damaged)
3.Condenser fan is not running
•Check fan capacitor
•Check fan wiring and connectors
•Check fan motor for failure or blockage
4.Return air duct has substantial leakage
5.If low pressure switch present in system, check Flash
Code 1 information