Overview 

CPC’s CO

2

 sensor (P/N 210-2000) is a non-dispersive 

infrared analyzer designed for measuring 

environmental CO

2

 concentration in ventilation 

systems and indoor spaces. Its measurement range of 

0-2000 or 0-5000 ppm covers the range required to 

monitor compliance with ASHRAE and other 
ventilation efficiency standards. 

 

An LCD display is available to provide local indication 

of CO

2

 concentration and facilitate the setup and 

calibration process. An adjustable setpoint relay is 

available for direct control and alarm applications. 

Microprocessor-based digital electronics and a 

unique self-calibration algorithm improves long-term 

stability and accuracy 
  

Mounting 

Before mounting, remove the door from the circuit 

board by pressing a screwdriver against the locking 
tab on the top of the enclosure. Pry the circuit board 

 

 

 

 
 

 

 

 

 
 

 

 

 
 

 

 

 

 
 

 

 

 

 

 

away from the mounting plate using a screwdriver 
inserted into the two tab slots on the top of the 

enclosure. 

 

Choose a location for the sensor with good air 

circulation, away from ventilation inlets, doors, 
windows, or other points where fresh air enters the 

room. The sensor should be mounted at least 4-1/2 

feet above the floor. The environment temperature 

must be within 32°–112°F (0°–50°C). 

 
If wiring will be coming in through the mounting 

plate from the back, punch out openings in the 

mounting plate and use the plate as a template for 

locating holes. Mount the mounting plate against a 
wall or other flat surface by using the two mounting 

holes and the screws provided (use wall anchors for 

drywall installations). 

 

NOTE:  Sensors must be mounted vertically (straight 

up and down) to ensure proper readings. 

 

 

 
 
 
 
 

 
 
 
 
 

Figure 1 - CO

2

 Sensor (exploded view) 

Carbon Dioxide Sensor 

Product Information Sheet

 

40

Содержание Carbon Dioxide Sensor

Страница 1: ... by pressing a screwdriver against the locking tab on the top of the enclosure Pry the circuit board away from the mounting plate using a screwdriver inserted into the two tab slots on the top of the enclosure Choose a location for the sensor with good air circulation away from ventilation inlets doors windows or other points where fresh air enters the room The sensor should be mounted at least 4 ...

Страница 2: ...Relay Wiring The CO2 sensor has an on board relay that changes state to indicate a CO2 level higher that a programmed set point This relay can be used as a digital input on an input board point or it can be used to directly activate or deactivate an alarm annunciator or a device that controls ventilation The connector on the right side of the mounting plate is a Form C connector for the CO2 sensor...

Страница 3: ...ng or control use the and keys to adjust the value of the set point When the CO2 sensor s reading is above this set point the relay will energize Press ENTER to save the setpoint value Altitude To properly measure CO2 concentrations you must specify the approximate altitude of the site Use the and keys to select the number of feet above sea level closest to the site s altitude Press ENTER to save ...

Страница 4: ...resenting a concentration of 0 ppm and 5V representing the maximum concentration level either 2000 ppm or 5000 ppm depending on the value of the Span parameter you chose when setting up the sensor In order for Einstein and the REFLECS line of controllers RMCC BEC or BCU to read the signal from the CO2 sensor it must be set up under Sensor Control for REFLECS or the Analog Input Setup Screen for Ei...

Отзывы: