Installation and Operation Manual
E2K-405-0218 Rev. 2
February 2018
33
Section 4: Operation
Operation
4.3
Initializing the Actuator
NOTE:
The TEC2 has automatic phase correction.
4.3.1 Setting Position Limits
Limits must be set before operating. The actuator will not operate until limits are set.
NOTE:
A passcode is not needed for the initial position limit settings. However, any limit
setting changes required after initialization requires a passcode and are changed
via the
“CHANGE SETTINGS”
mode. See
Section 5.5.3, Set Valve Travel Limits.
CAUTION:
It is recommended that the final valve position be set using the handwheel
while setting the limits to prevent valve damage.
There are two different routines for setting limits. Initial limit settings can be set as
described in
Section 2, Quick Start
. Limit settings can be changed as described in
Section 5.5.3, Set Valve Travel Limits
.
Once the limits have been set, check the settings as follows.
For Electrical Operation:
1.
Run actuator electrically to verify correct operation.
For Manual Operation:
1.
Move the valve in the close direction. The Red LED should go off and the
Green LED should blink within one handwheel turn.
2.
Move the valve in the open direction. The Green LED should go off and the
Red LED should be blinking within one handwheel turn.
The actuator will operate in the normal LOCAL and REMOTE modes.
Exit “
SETUP
” mode.
1.
Rotate the selector knob to
NEXT
to cycle through the displays until
“
EXIT?
” is displayed.
2.
Rotate the control knob to
YES
.
4.3.2 View Existing Settings
Unless otherwise specified at the time the order is placed, the TEC2 actuator is
shipped with the following default configuration settings.