background image

Anderson Greenwood

 Pilot oPerated safety relief valves

Operating and Safety inStructiOnS

Before installation these instructions must be fully read and understood

service technicians are available to assist with 
your installation or other field problems. Call 
your nearest emerson representative.

emerson.com/FinalControl

wArninG

• If a gagging device is provided with the valve it 

must be removed before the valve is put into 
service.

• Removal of the seal wires in an attempt 

to adjust and/or repair this product by 
unauthorized or unqualified persons voids 
the product warranty and may cause damage 
to equipment and serious injury or death to 
persons.

• This product is a safety related component 

intended for use in critical applications. 
The improper application, installation or 
maintenance of the valve or the use of parts or 
components not manufactured by Emerson may 
result in a failure of the valve.

• Any obstruction due to polymerization, 

solidification or solid deposit will affect the 
safety performance of this valve. Methods to 
reduce such risk should be taken.

• A safety valve should be used only to protect a 

system from overpressure during a pressure 
upset. It should not be used as a control valve 
that is required to operate continuously or as 
a block valve to isolate portions of the system. 
It should not be used as a pipe fitting or 
transition piece in a piping system.

• Any installation, maintenance, adjustment, repair 

or test, performed on the safety valve must be 
done in accordance with the requirements of all 
applicable Emerson Procedures and Instructions 
as well as applicable National and International 
Codes and Standards.

• The information, specifications and technical 

data (the ‘Specifications’) contained in this 
document are subject to change without 
notice. Emerson does not warrant that the 
Specifications are current and assumes no 
responsibility for the use or misuse thereof. 
The Purchaser should verify that there have been 
no changes to the Specifications prior to use.

sAFety preCAutions

• When the safety valve is under pressure never 

place any part of your body near the outlet of 
the valve.

• The valve outlet and any separate drains should 

be piped or vented to a safe location.

• Always wear proper safety gear to protect 

hands, head, eyes, ears, etc. anytime you are 
near pressurized valves.

• Never attempt to remove the safety valve from a 

system that is pressurized.

• Never make adjustments to or perform 

maintenance on the safety valve while in 
service unless the valve is isolated from the 
system pressure. If not properly isolated from 
the system pressure, the safety valve may 
inadvertently open resulting in serious injury.

• Remove the safety valve prior to performing any 

pressure testing of the system.

• The safety of lives and property often depends 

on the proper operation of the safety valve. 
The valve must be maintained according 
to appropriate instructions and must be 

1 GenerAl

the intent of these instructions is to acquaint 
the user with the storage, installation and 
operation of this product.
this safety valve should only be used in 
accordance with the applicable operating 
instructions and within the application 
specifications of the purchase order.
these valves have been tested and adjusted at 
the factory. Contact the factory or a emerson 
authorized representative before making any 
changes to the settings.

© 2017 emerson. all rights reserved.

engineering doc. #05.9040.352 rev. B

VCosi-06034-en 18/01

tAble oF Contents

1. General ........................................................... 1
2.  storage and handling .................................... 2
3. installation ..................................................... 2
4.  inlet piping ..................................................... 2
5.  discharge piping............................................ 2
6.  remote pressure pick-up ............................. 3
7.  set pressure verification testing .................. 4

periodically tested and reconditioned to ensure 
correct function.

• For further information including adjustment, 

maintenance, cleaning lapping and detail 
illustrations obtain the appropriate Operation and 
Maintenance Manual from the table on page 4. 
These manuals may be requested from the factory 
or are available at Emerson.com/FinalControl

Содержание Anderson Greenwood 200 Series

Страница 1: ... use or misuse thereof The Purchaser should verify that there have been no changes to the Specifications prior to use Safety precautions When the safety valve is under pressure never place any part of your body near the outlet of the valve The valve outlet and any separate drains should be piped or vented to a safe location Always wear proper safety gear to protect hands head eyes ears etc anytime...

Страница 2: ...s since the discharge during operation is small When pilot discharge to the atmosphere is not permissible the pilot exhaust should be connected either to the discharge piping or through a supplementary piping system to a safe location When discharge piping is designed avoid the possibility of back pressure on the pilot unless the pilot is a balanced design Discharge piping must be drained properly...

Страница 3: ... piping up to 10 feet 3 m in length must have an inside diameter not less than 0 245 6 mm the inside diameter of x 0 065 wall 10 mm x 2 mm wall seamless tubing For lengths greater than 10 feet 6 m 1 25 mm or larger pipe should be used The remote sense line must be self draining and insulated to minimize condensate formation and freezing potential For Series 9000 valves Remote pressure pick up is s...

Страница 4: ...are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson com FinalControl 7 Set pressure verification testing Set pressure verification testing should be performed in accordance with instructions in the applicable Operation and Maintenance Manual Operation and Maintenance Manuals Valve model Operation and...