13
© 2018 Emerson Climate Technologies, Inc.
AEX-XXXX
PRELIMINARY
AE8-1384 R6
Table 4 - CoreSense Modbus Map Continued
Parameters can be write using Function code 16 (Preset Multiple Registers)
Location in
Hex
Parameter
Message
Length in
Bytes
Message
Length
With Zero
Stuffing
Range
Default
100
Customer Id Code
4
8
104
Customer Location
17
34
115
Customer Name
17
34
126
Compressor Model Number Modified
18
36
138
Compressor serial number
12
24
144
Application code
3
6
147
Temperature code
4
8
14B
Refrigerant code
7
14
152
Functional Configuration
2
2
154
Compressor run time to count as
short cycle
1
2
Range: 1 min to 6 min
3
155
Scroll High Temp Trip
2
2
Range: 110 deg C to 150
deg C
140
157
Scroll High Temp Reset
2
2
Note: Reset set point
value should be always
(Trip set point value - 30
deg C)
15A
Future Use
1
2
15B
Future Use
2
2
15D
Future Use
2
2
15F
No. of Events to Scroll High Temp
Lockout
1
2
Range: 4 to 36
20
160
*No. of Events to Short Cycling Warn-
ing/Lockout
1
2
Range: 20 to 200
48
16A
Write Command
2
2
Options: 0x0800 (Alarm
Reset) & 0x8000
(Module Reset)
*Condition is set according to position of DIP switch #10