12
© 2018 Emerson Climate Technologies, Inc.
AEX-XXXX
PRELIMINARY
AE8-1384 R6
Table 4 - CoreSense Modbus Map Continued
Parameters can be read using Function code 3 (Read Holding Register)
Location in Hex
Parameter
Message Length in
Bytes
Message Length With
Zero Stuffing
100
Customer Id Code
4
8
104
Customer Location
17
34
115
Customer Name
17
34
126
Compressor Model Number Modified
18
36
138
Compressor serial number
12
24
144
Application code
3
6
147
Temperature code
4
8
14B
Refrigerant code
7
14
152
Functional Configuration
2
2
154
Compressor run time to count as short cycle
1
2
155
Scroll High Temp Trip
2
2
157
Scroll High Temp Reset
2
2
15A
Future Use
1
2
15B
Future Use
2
2
15D
Future Use
2
2
15F
No. of Events to Scroll High Temp Lockout
1
2
160
No. of Events to Short Cycling Warning/Lockout
1
2